Document No: LT0499
RDU Mk2 Installation & Programming Manual
Alignment, Adjustment & Placing Into Operation
Issue 1.02
8 April 2015
Page 9-5
POWER UP
To place the RDU into operation, perform the following steps:
STEP 1
If an E2INIT is required before programming, fit Lk7 on the Controller to the
DATABASE WRITE ENABLE position and fit mini-jump SW1. (Refer to
Section 6.3.1).
Install the 2A Fuse supplied into holder F1 on the Remote Termination board.
STEP 2
Check that the buzzer sounds and all LEDs on the Operator Display panel
flash for 2 seconds (except Mains On).
STEP 3
The Controller performs tests on its memory, electronics, and the LCD.
STEP 4
If doing an E2INIT, remove mini-jump SW1 and press "ACK" to complete the
sequence.
STEP 5
Check that the LCD has good visibility. The LCD displays the RDU PCB
configuration before showing the Base Display.
STEP 6
If required, complete programming as per Chapters 6 and 7 and then fit Lk7
on the Controller to the DATABASE PROTECT position.
Link Lk7 may be left in the write enabled position if software write protection is
enabled and it is desired that the RDU accept and use zone names as
received from the FIP. (Refer Section 6.4.4.2).
STEP 7
Perform a System Test at the RDU, then a system test at the FIP (de-isolate
all zones first).
STEP 8
Check that zone status conditions at the FIP are received and annunciated
correctly at the RDU and that commands issued at the RDU act correctly to
acknowledge, reset and isolate zones as required. A full commissioning test
should be carried out as per AS1670.1.