RDU Mk2 Installation & Programming Manual
Document No: LT0499
Alignment, Adjustment & Placing Into Operation
Page 9-4
8 April 2015
Issue 1.02
STEP 4
Check that the buzzer sounds and all LEDs on the Operator Display panel flash
for 2 seconds (except Mains On).
STEP 5
Check that the green "MAINS ON" LED indicator is on.
The Controller performs tests on its memory, electronics, and the LCD.
STEP 6
If doing an E2INIT, remove mini-jump SW1 and press "ACK" to complete the
sequence.
STEP 7
Check that the LCD has good visibility. The LCD displays the RDU PCB
configuration before showing the Base Display.
STEP 8
Install and connect the batteries.
Take care not to short the battery leads or connect in reverse polarity when
connecting.
STEP 9
If required, complete programming as per Chapters 6 & 7 and then fit Lk7 on the
Controller to the DATABASE PROTECT position.
Link Lk7 may be left in the write enabled position if software write protection is
enabled and it is desired that the RDU accept and use zone names as received
from the FIP. (Refer Section 6.4.4.2).
STEP 10
Perform a Battery Test.
- If this fails check the battery connections, leave for 24 hours and then retest.
STEP 11
Perform a Bells and System Test at the RDU, then a system test at the FIP (de-
isolate all zones first).
STEP 12
Check that zone status conditions at the FIP are received and annunciated
correctly at the RDU and that commands issued at the RDU act correctly to
acknowledge, reset and isolate zones as required.
A full commissioning test should be carried out as per AS1670.1.
9.2.3
PLACING INTO OPERATION: SLIMLINE RDU
VISUAL INSPECTION
Before switching on power (e.g., do not install RDU remote termination board Fuse F1),
inspect the cabinet and internals. Check as follows:
1.
Check that all equipment is securely mounted, and that all cables are connected at
the appropriate points. The factory checklist is included.
2.
Check that a 4 wire comms plus power connection has been made to the FIP with Tx
& Rx at the FIP routed to Rx & Tx respectively at the RDU. Also check that the FIP
has been programmed correctly to send status/ receive commands to/from the RDU.
3.
Double check the FIP MAF/PSU and battery to ensure there is sufficient capacity to
cope with the extra loading due to connection of the RDU. Refer Section 5.3.