RAPID RESPONSE  

Model RCP-1 Residential Control Panel  

1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) 

Worldwide 

Contacts

www.tyco-fire.com

Page 1 of 12 

JANUARY 2014 

TFP480

General  

Description 

The TYCO RAPID RESPONSE Mod-

el RCP-1 Residential Control Panel is 

an integrated valve manifold, air pres-

sure, and electronic control package 

for controlling the release of water into 

residential dry pipe sprinkler systems. 
The Model RCP-1 Panel is intended for 

use in one- and two- family dwellings 

and mobile homes per NFPA 13D when 

used with residential sprinklers that 

have been listed for use in residential 

dry pipe sprinkler systems. 
The Model RCP-1 Panel incorporates 

the Listed Model 4004R Household Fire 

Warning Unit Subassembly installed 

within the Model RCP-1 cabinet.
The Model RCP-1 Panel includes the 

following features:

• 

Pre-wired assembly containing pre-

programmed control panel, system 

performance gauges, and an en-

closed compressor 

• 

Pre-engineered riser design 

• 

Supervised system valve system

• 

Provision to trip test system without 

having water flow into the system. 

• 

High pressure supervision for indica-

tion of a false trip or failure of the au-

tomatic air supply cut-out switch

• 

Dry contacts for remote connection 

(dial-up systems or additional moni-

toring, for example)

• 

48-hour battery backup

SECTIONS

General Description   .  .  .  .  .  .  .  .  .  . 1
Warnings  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2
Technical Data   .  .  .  .  .  .  .  .  .  .  .  .  .  . 2
Operation   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3
Operator Interface   .  .  .  .  .  .  .  .  .  .  . 6
In Case of Supervisory/ 

Trouble Condition  .  .  .  .  .  .  .  .  .  .  .  . 7
In Case of Alarm Condition   .  .  .  . 7
System Resetting  .  .  .  .  .  .  .  .  .  .  .  . 7
Installation    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .10
Care and Maintenance    .  .  .  .  .  .  .11
Ordering Procedure   .  .  .  .  .  .  .  .  .  .12

FIGURES, GRAPHS, AND 

TABLES

Pressure Loss Graph   .  .  .  .  .  .  .  .  . 3
Model RCP-1 Assembly  .  .  .  .  .  .  . 4
Manifold Assembly    .  .  .  .  .  .  .  .  .  . 5
Operator Interface Card 

(Front Side)   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 6
Wiring Diagram  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8
Off-Site Remote Relays   .  .  .  .  .  .  . 9
On-Site Remote Signal    .  .  .  .  .  .  . 9
Battery Harness   .  .  .  .  .  .  .  .  .  .  .  .  .10
Operator Interface Card 

(Back Side)   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .11

Summary of Contents for RAPID RESPONSE RCP-1

Page 1: ...des the following features Pre wired assembly containing pre programmed control panel system performance gauges and an en closed compressor Pre engineered riser design Supervised system valve system P...

Page 2: ...is document The Model 4004R Household Fire Warning Unit Subassembly Electronic Control installed within the Model RCP 1 cabinet is UL and C UL Listed Maximum Water Pressure 175 psi 12 1 bar Friction L...

Page 3: ...tically maintained at a normal system air pressure of 10 to 14 psi 0 7 to 1 0 bar via the Air Com pressor Switch Air Compressor Fig ure 2 In the standby condition water is prevented from entering the...

Page 4: ...BLY AIR PRESSURE CONTROL Always consult local jurisdictions for water supply criteria and requirements Nominal Weight 95 LBS 43 kg MOUNTING BRACKETS 2 7 8 73 mm ELECTRONIC CONTROL 1 3 4 45 mm 5 127 mm...

Page 5: ...NORMALLY CLOSED PRESSURE SWITCH POTTER ELECTRIC PS10 2 INCREASE 16 1 PSI DECREASE 8 1 PSI TUBING TO SYSTEM WATER SUPPLY PRESSURE GAUGE FLOW TUBING TO SYSTEM AIR SUPPLY PRESSURE GAUGE SPRING LOADED CHE...

Page 6: ...ill functioning the Electronic Con trol is using battery power to oper ate The cause for loss of AC Power should be determined and correct ed The system is in a normal stand by condition when only the...

Page 7: ...re System or main control valve closure Step 5 Reset the system as soon as possible In Case of Alarm Condition Step 1 Verify that a fire condition ex ists and take appropriate action that is evacuate...

Page 8: ...10k 1 2 W 3 3k 1 2 W 3 3k 3 3k RAC 1 RAC 2 NAC 1 NAC 2 12 18 AWG 1A MAX NOTIFICATION CIRCUIT IDC 2 IDC 1 IDC 4 IDC 3 1 2 W 3 3k SPM 2 SPM 1 R SOLENOID PRE CONNECTED YEL RED TYPICAL 430687 TWIST ON WIR...

Page 9: ...TS LOWER RIGHT HAND CORNER OF ELECTRONIC CONTROL JUMPER SELECTION OPTIONS RELAY CONTACTS SET ALL RELAY JUMPERS TO NORMALLY OPEN JUMPER RIGHT AUXILIARY POWER TERMINALS UPPER RIGHT HAND CORNER OF ELECTR...

Page 10: ...Maximum alarm current is 1A and the maximum distance from the Model RCP 1 Panel to the last de vice is as follows 210 feet for 18 AWG wiring 334 feet for 16 AWG wiring 532 feet for 14 AWG wiring 845...

Page 11: ...se the Flow Test Valve The Water Supply Gauge should drop to a previously noted re sidual pressure and then return to the normal static pressure Step 4 Perform a lamp test by press ing and holding the...

Page 12: ...mber Step 5 Upon completing the program ming check place the PROGRAM SWITCH in the OFF position and then return the Operator Interface card to its normal position NOTICE Exercise care to ensure that a...