background image

TFP220

Page 5 of 8

FM Approval Requirements

Series EC-11 and EC-14 Extended 

Coverage Upright and Pendent Sprin-

klers are to be installed in accor-

dance with the applicable FM Loss 

Prevention Data Sheet for limited use 

in buildings of specific roof construc-

tion and for the protection of certain 

specific ordinary hazard (non-storage 

and/or non-flammable or combustible 

liquid) occupancies. Information pro-

vided in the FM Loss Prevention Data 

Sheets relates to, but is not limited to, 

hydraulic design, ceiling slope, and 

obstructions, minimum and maximum 

allowable spacing, and deflector-to-

ceiling distance.
These criteria may differ from UL 

and/or NFPA criteria. Therefore, the 

designer should review and become 

familiar with FM requirements before 

proceeding with design.

Installation

TYCO Series EC-11 and EC-14 

Extended Coverage Upright and 

Pendent Sprinklers must be installed 

in accordance with this section.

General Instructions

Do not install any bulb-type sprinkler 

if the bulb is cracked or there is a loss 

of liquid from the bulb. With the sprin-

kler held horizontally, a small air bubble 

should be present. The diameter of the 

air bubble is approximately 1/16 in.  

(1,6 mm) for the 135°F (57°C) to 

 

3/32 in. (2,4 mm) for the 286°F (141°C) 

temperature ratings.
A leak-tight 3/4 in. NPT sprinkler 

joint should be obtained by apply-

ing a minimum-to-maximum torque of  

10 to 20 ft-lb (13,4 to 26,8 N·m). Higher 

levels of torque may distort the sprin-

kler inlet with consequent leakage or 

impairment of the sprinkler.
Do not attempt to compensate for 

insufficient adjustment in an Escutch-

eon Plate by under or over-tightening 

the Sprinkler. Re-adjust the position of 

the sprinkler fitting to suit.

Step 1.

 Install the sprinkler with the 

deflector parallel to the mounting 

surface. Install pendent sprinklers in 

the pendent position; install upright 

sprinklers in the upright position.

Step 2.

 After installing the Style 30, 40, 

or 60 mounting plate (or other applica-

ble escutcheon) over the sprinkler pipe 

threads and with pipe-thread sealant 

applied to the pipe threads, hand-

tighten the sprinkler into the sprinkler 

fitting.

Step 3.

 For upright or pendent sprin-

klers, wrench-tighten using only the 

W-Type 3 (End A) Sprinkler Wrench. 

For the pendent sprinkler installed 

with Style 30, 40, or 60 Escutcheon, 

wrench-tighten the sprinkler using only 

the W-Type 22 Sprinkler Wrench.
Apply the wrench recess of the appli-

cable sprinkler wrench (Figure 5 and 6) 

to the sprinkler wrench flats (Figure 1).

Description

Area

ft x ft

Light Hazard 

0.10 GPM/ft

2

Group I 

Ordinary Hazard 

0.15 GPM/ft

2

Group II 

Ordinary Hazard  

0.20 GPM/ft

2

GPM

PSI

GPM

PSI

GPM

PSI

TY5137 

(K=11.2) Upright

14 x 14

30

7.2

30

7.2

39

12.1

16 x 16

30

7.2

39

12.1

51

20.7

18 x 18

33

8.7

49

19.1

65

33.7

20 x 20

40

12.8

60

28.7

80

51.0

TY5237 

(K=11.2) Pendent

14 x 14

30

7.2

30

7.2

39

12.1

16 x 16

30

7.2

39

12.1

51

20.7

18 x 18

33

8.7

49

19.1

65

33.7

20 x 20

40

12.8

60

28.7

80

51.0

TY6137 

(K=14.0) Upright

14 x 14

N/A

N/A

39

7.8

51

13.3

16 x 16

N/A

N/A

39

7.8

51

13.3

18 x 18

N/A

N/A

49

12.3

65

21.6

20 x 20

N/A

N/A

60

18.4

80

32.7

TY6237 

(K=14.0) Pendent 

14 x 14

37

7.0

39

7.8

51

13.3

16 x 16

37

7.0

39

7.8

51

13.3

18 x 18

37

7.0

49

12.3

65

21.6

20 x 20

40

8.2

60

18.4

80

32.7

NOTES

•  1 ft = 0.3048 m
•  1 ft

2

 = 0.093 m

2

•  1 GPM = 3.785 LPM
•  1 psi = 0.06895 bar
•  1 GPM/ft

= 40.74 mm/min

TABLE D 

FLOW CRITERIA FOR UL AND C-UL LISTING OF SERIES EC-11 AND EC-14 SPRINKLERS

Summary of Contents for EC-11 Series

Page 1: ...s beyond that which occurs when exposed to corrosive atmospheres Although corrosion resistant coated sprinklers passed standard corrosion tests of the applicable approval agencies this testing is not...

Page 2: ...ed by NFPA 13 for example Unobstructed combustible or noncombustible ceiling con struction with a deflector to ceiling roof deck distance of 1 to 12 in 25 to 300 mm Obstructed non combusti ble ceiling...

Page 3: ...ory Mutual Research Corporation FM 4 Approved by the City of New York under MEA 177 03 E 5 Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C UL Listed the sprinklers are UL and...

Page 4: ...14 0 EC Pendent or Upright Quick 10 20 100 400 Up to 30 Noncombustible Unobstructed Noncombustible Obstructed or Combustible Unobstructed 11 2 EC 14 0 EC Pendent Recessed Style 30 10 20 100 400 Up to...

Page 5: ...er or over tightening the Sprinkler Re adjust the position of the sprinkler fitting to suit Step 1 Install the sprinkler with the deflector parallel to the mounting surface Install pendent sprinklers...

Page 6: ...0 MALLEABLE IRON REDUCING SPRINKLER FITTING FITTING SIDE TOWARDS SPRINKLER FITTING WRENCH RECESS END A WRENCH RECESS WRENCH HEX 1 4 6 4 mm 1 2 12 7 mm MOUNTING SURFACE FACE OF SPRINKLER FITTING 1 2 1...

Page 7: ...y the corrosive conditions present The owner is responsible for the inspection testing and maintenance of their fire protection system and devices in compliance with this doc ument as well as with the...

Page 8: ...e Protection Association TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway Lansdale PA 19446 Telephone 1 215 362 0700 2019 Johnson Controls All rights reserved All specifications and o...

Reviews: