TFP220

Page 7 of 8

P/N 51 – XXX – X – XXX

Care and 

Maintenance

TYCO Series EC-11 and EC-14 

Extended Coverage Upright and 

Pendent Sprinklers must be maintained 

and serviced in accordance with this 

section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

systems from the proper authorities 

and notify all personnel who may be 

affected by this action.
Sprinklers which are found to be 

leaking or exhibiting visible signs of 

corrosion must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the sprinklers before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced. Also, replace any sprinkler 

that has a cracked bulb or that has lost 

liquid from its bulb. Refer to the Instal-

lation section, for more information. 
Frequent visual inspections are rec-

ommended to be initially performed 

for corrosion resistant coated sprin-

klers, after the installation has been 

completed, to verify the integrity of the 

corrosion resistant coating. Thereafter, 

annual inspections per NFPA 25 should 

suffice; however, instead of inspecting 

from the floor level, a random sampling 

of close-up visual inspections should 

be made, so as to better determine the 

exact sprinkler condition and the long 

term integrity of the corrosion resistant 

coating, as it may be affected by the 

corrosive conditions present.
The owner is responsible for the 

inspection, testing, and maintenance 

of their fire protection system and 

devices in compliance with this doc-

ument, as well as with the applicable 

standards recognized by the Approval 

agency, such as NFPA 25, in addition to 

the standards of any authorities having 

jurisdiction. Contact the installing con-

tractor or product manufacturer with 

any questions.
Automatic sprinkler systems are rec-

ommended to be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Ordering 

Procedure

Contact your local distributor for 

availability. When placing an order, 

indicate the full product name and Part 

Number (P/N).

Sprinkler Assemblies with 

NPT Thread Connections

Specify: Series EC-11 or EC-14 

(specify) Sprinkler, SIN (specify), 

(specify) K-factor, Pendent or Upright 

(specify) Extended Coverage, (specify) 

temperature rating, (specify) finish, P/N 

(from to Table E)

Recessed Escutcheon, Two-Piece

Specify: Style (30 or 40) Two-Piece 

Recessed Escutcheon with (specify) 

finish, P/N (specify*)

*Refer to Technical Data Sheet TFP770

Flush Escutcheon, Two-Piece

Specify: Style 60 Two-Piece Flush 

Escutcheon with (specify) finish, P/N 

(specify**)

**Refer to Technical Data Sheet TFP778

Sprinkler Wrenches

Specify: W-Type 3 Sprinkler Wrench, 

P/N 56-895-1-001
Specify: W-Type 22 Recessed Sprinkler 

Wrench, P/N 56-665-7-001

SIN

893

11.2K Pendent

TY5237

894

11.2K Upright

TY5137

895

14.0K Pendent

TY6237

896

14.0K Upright

TY6137

SPRINKLER 

FINISH

1

1

NATURAL BRASS

4

SIGNAL WHITE 

(RAL9003) 

POLYESTER

5

JET BLACK (RAL9005) 

POLYESTER

7

LEAD COATED

9

CHROME-PLATED

TEMPERATURE 

RATING

135

135°F (57°C)

155

155°F (68°C)

175

175°F (79°C)

200

200°F (93°C)

286

286°F (141°C)

000

OPEN

2

TABLE E 

SERIES EC-11 AND EC-14 UPRIGHT AND PENDENT SPRINKLERS 

PART NUMBER SELECTION

NOTES:

1.  Escutcheon ordered separately.
2.  OPEN indicates the sprinkler assembly without glass bulb, button, and sealing assembly.

Summary of Contents for EC-11 Series

Page 1: ...s beyond that which occurs when exposed to corrosive atmospheres Although corrosion resistant coated sprinklers passed standard corrosion tests of the applicable approval agencies this testing is not...

Page 2: ...ed by NFPA 13 for example Unobstructed combustible or noncombustible ceiling con struction with a deflector to ceiling roof deck distance of 1 to 12 in 25 to 300 mm Obstructed non combusti ble ceiling...

Page 3: ...ory Mutual Research Corporation FM 4 Approved by the City of New York under MEA 177 03 E 5 Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C UL Listed the sprinklers are UL and...

Page 4: ...14 0 EC Pendent or Upright Quick 10 20 100 400 Up to 30 Noncombustible Unobstructed Noncombustible Obstructed or Combustible Unobstructed 11 2 EC 14 0 EC Pendent Recessed Style 30 10 20 100 400 Up to...

Page 5: ...er or over tightening the Sprinkler Re adjust the position of the sprinkler fitting to suit Step 1 Install the sprinkler with the deflector parallel to the mounting surface Install pendent sprinklers...

Page 6: ...0 MALLEABLE IRON REDUCING SPRINKLER FITTING FITTING SIDE TOWARDS SPRINKLER FITTING WRENCH RECESS END A WRENCH RECESS WRENCH HEX 1 4 6 4 mm 1 2 12 7 mm MOUNTING SURFACE FACE OF SPRINKLER FITTING 1 2 1...

Page 7: ...y the corrosive conditions present The owner is responsible for the inspection testing and maintenance of their fire protection system and devices in compliance with this doc ument as well as with the...

Page 8: ...e Protection Association TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway Lansdale PA 19446 Telephone 1 215 362 0700 2019 Johnson Controls All rights reserved All specifications and o...

Reviews: