TFP220

Page 2 of 8

The Style 60 Two-Piece Flush Escutch-

eon (Figure 4) is UL Listed for use with 

the Series EC-11 and EC-14 Pendent 

Sprinklers.

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connection

3/4 in. NPT

Discharge Coefficients

K = 11.2 GPM/psi

½

 (161,3 LPM/bar

½

K = 14.0 GPM/psi

½

 (201,6 LPM/bar

½

)

Temperature Ratings

Refer to Table A

Finish

Sprinkler: 

Refer to Table A
Recessed or Flush Escutcheon: 

White-Coated, Chrome-Plated, and 

Brass-Plated

Physical Characteristics

Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bronze

Button. . . . . . . . . . . . . . . . . . . . . . . . . . . . Bronze

Sealing Assembly  .  Beryllium Nickel w/TEFLON

Bulb  . . . . . . . . . . . . . . . . . . . . . . . . Glass (3 mm)

Compression Screw  . . . . . . . . . . . . . . . . Bronze

Deflector. . . . . . . . . . . . . . . . . . . . . . . . . . . Brass

Operation

The glass bulb contains a fluid that 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter 

the glass bulb, which- then allows the 

sprinkler to activate and flow water.

Design 

Criteria

TYCO Series EC-11 and EC-14 

Extended Coverage Upright and 

Pendent Sprinklers must only be 

installed in accordance with the appli-

cable UL and C-UL Listing or FM 

Approval requirements as indicated 

below. Only Style 30 or 40 Recessed 

Escutcheons are to be used for 

recessed installation, as applicable. 

Refer to Tables A, B, and C, for more 

information.

UL and C-UL 

Listing Requirements

1. 

Series EC-11 and EC-14 Extended 

Coverage Sprinklers may be used 

for the coverage areas shown in 

Table D, based on maintaining the 

minimum specified flow rate as a 

function of coverage area and haz-

ard group for all sprinklers in the 

design area.

2. 

Series EC-11 and EC-14 Extended 

Coverage Sprinklers are permitted 

to be used with unobstructed or 

non-combustible obstructed ceil-

ing construction as defined and 

permitted by NFPA 13; for example:

•  Unobstructed, combustible or 

noncombustible, ceiling con-

struction with a deflector to 

ceiling/roof deck distance of 

 

1 to 12 in. (25 to 300 mm).

•  Obstructed, non-combusti-

ble, ceiling construction with a 

deflector location below struc-

tural members of 1 to 6 in. 

 

(25 to 150 mm) and a maximum 

deflector to ceiling/roof deck dis-

tance of 22 in. (550 mm).

3. 

Series EC-11 and EC-14 Extended 

Coverage Sprinklers, specifically 

tested and listed for non-combus-

tible obstructed construction, are 

permitted to be used within truss-

es or bar joists having non-com-

bustible web members greater 

than 1 in. (25.4 mm) when apply-

ing the 4 times obstruction crite-

ria rule defined under “Obstruc-

tions to Sprinkler Discharge Pattern 

Development”.

4. 

To prevent cold soldering, the 

minimum allowable spacing be-

tween Series EC-11 and EC-14 Ex-

tended Coverage Sprinklers is 8 ft  

(2,4 m) for upright sprinklers and 9 ft  

(2,7 m) for pendent sprinklers.

5. 

Series EC-11 and EC-14 Extended 

Coverage Sprinklers are to be in-

stalled in accordance with all oth-

er requirements of NFPA 13 for 

extended coverage upright and 

pendent sprinklers; For exam-

ple, obstructions to sprinkler dis-

charge, obstructions to sprinkler 

pattern development, obstructions 

to prevent sprinkler discharge from 

reaching hazard and clearance to 

storage.

SECTION

CROSS

PENDENT

UPRIGHT

1

2

3

4

5

6

WRENCH

FLAT

ESCUTCHEON PLATE

SEATING SURFACE

1/2" (12,7 mm)

NOMINAL MAKE-IN

1-11/16"

(42,7 mm)

2-7/16"

(61,9 mm)

UPRIGHT &

PENDENT

*

**

3/4"

NPT

Pipe thread connections per

ISO 7-1 can be provided on

special request.

5

4

6

Components:

2

3

Temperature rating is

indicated on Deflector.

-

Compression Screw

-

Bulb

- Deflector

-

- Sealing Assembly

Button

Frame

1 -

**

*

*

FIGURE 1 

SERIES EC-11 AND EC-14 EXTENDED COVERAGE SPRINKLERS 

11.2 K-FACTOR UPRIGHT (TY5137) AND PENDENT (TY5237) 

14.0 K-FACTOR UPRIGHT (TY6137) AND PENDENT (TY6237) 

ASSEMBLY

Summary of Contents for EC-11 Series

Page 1: ...s beyond that which occurs when exposed to corrosive atmospheres Although corrosion resistant coated sprinklers passed standard corrosion tests of the applicable approval agencies this testing is not...

Page 2: ...ed by NFPA 13 for example Unobstructed combustible or noncombustible ceiling con struction with a deflector to ceiling roof deck distance of 1 to 12 in 25 to 300 mm Obstructed non combusti ble ceiling...

Page 3: ...ory Mutual Research Corporation FM 4 Approved by the City of New York under MEA 177 03 E 5 Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C UL Listed the sprinklers are UL and...

Page 4: ...14 0 EC Pendent or Upright Quick 10 20 100 400 Up to 30 Noncombustible Unobstructed Noncombustible Obstructed or Combustible Unobstructed 11 2 EC 14 0 EC Pendent Recessed Style 30 10 20 100 400 Up to...

Page 5: ...er or over tightening the Sprinkler Re adjust the position of the sprinkler fitting to suit Step 1 Install the sprinkler with the deflector parallel to the mounting surface Install pendent sprinklers...

Page 6: ...0 MALLEABLE IRON REDUCING SPRINKLER FITTING FITTING SIDE TOWARDS SPRINKLER FITTING WRENCH RECESS END A WRENCH RECESS WRENCH HEX 1 4 6 4 mm 1 2 12 7 mm MOUNTING SURFACE FACE OF SPRINKLER FITTING 1 2 1...

Page 7: ...y the corrosive conditions present The owner is responsible for the inspection testing and maintenance of their fire protection system and devices in compliance with this doc ument as well as with the...

Page 8: ...e Protection Association TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway Lansdale PA 19446 Telephone 1 215 362 0700 2019 Johnson Controls All rights reserved All specifications and o...

Reviews: