The following can be used to verify that the panel settings correspond to the default values for
Double Interlock Preaction Electric-Electric configurations.
To verify the program settings of the standard program, push the Program switch to the right.
The panel displays the following:
L
O O K
A
T
H
I
S
T O R Y
?
SET
SELECT
FUNCTION
Press the FUNCTION button to move to the next
position.
S
E
T
T
I
M E
?
SET
SELECT
FUNCTION
Press the FUNCTION button to move to the next
position.