11
Red-E DV-5A Deluge, Single Interlock Preaction, Double Interlock
Preaction (Pneumatic-Electric) Program
ZONES
SUP 1
SUP 2
#1
#2
#3
#4
OUTPUTS
Supervisory Low Air
Supervisory
Conventional Conventional Tamper
Waterflow
GENERAL
ALARM
X
X
X
WATERFLOW
BELL
X
SOLENOID
VALVE (#7)
X
X
WATERFLOW
ALARM
X
Description:
Red-E DV-5A Deluge, Single Interlock Preaction or Double Interlock Preaction
(Pneumatic-Electric) release for single hazard
Inputs:
2 supervisory zones*, 2 conventional detection zones, 1 valve tamper zone, 1 waterflow
alarm zone
Outputs:
1 general alarm, 2 waterflow, 1 solenoid release circuit
Operation:
Activation of either conventional detection zone will operate the release and the general alarm
output, and cause the alarm contact to change state.
Activation of the wateflow zone will operate the general alarm bell output, the waterflow output,
the alarm contact, and cause the waterflow contact to change state.
Activation of any of the tamper or supervisory zones will operate the supervisory relay only.
When either zone 1 or 2 is in alarm, outputs 1 & 3 will operate
When zone 1 and 2 is in alarm, outputs 1 & 3 will operate
When zone 3 or either supervisory zones is activated, only the supervisory relay operates
When zone 4 is in alarm, outputs 1, 2, & 4 will operate
* The low air supervisory zone is not used on Deluge electric release and wet pilot release models
Summary of Contents for Deluge Red-E
Page 1: ...Installation Guide Doc DV5A RED E 001 REV2 06 2019...
Page 2: ......
Page 5: ......
Page 80: ...75 Double Interlock Electric Pneumatic Wiring Schematic Non Integrated Releasing Panel...
Page 81: ...76 Double Interlock Electric Electric Wiring Schematic Non Integrated Releasing Panel...
Page 82: ...77 END...