37
Double Interlock Preaction Valve Setting Procedure
Perform Steps 1 through 20 when initially setting the TYCO DV-5A
Valve, after an operational test of the fire protection system,
or after system operation due to a fire. Refer to 16 or 17, as applicable, and determine which type actuation system is being set.
Figure 13
Double Interlock Preaction Electric Electric Actuation Schematic Piping Diagram
1
DV-5A Valve
Auto.
2
System Main Control Valve
N.O.
3
Automatic Drain Valve
Auto.
4
Main Drain Valve
N.C.
5
Diaphragm Supply Valve
N.O.
6
Manual Reset Actuator
7
Solenoid Valve
Auto.
8
Manual Control Station
N.C.
9
Alarm Test Valve
N.C.
10
Drip Funnel Drain
11
Water Supply Gauge
12
Water Supply Gauge Test Valve
N.O.
13
Diaphragm Supply Strainer
14
Diaphragm Supply Check Valve
Auto.
15
Diaphragm Gauge
16
System Riser
17
Drain Header
18
Supply Header
19
Waterflow Pressure Switch
20
Water Motor Alarm Connection
21
Downstream Shut Off Valve
N.O.
22
Funnel Drain Check Valve
Auto.
23
System Drain Valve
N.C.
24
System Gauge
25
System Gauge Valve
N.O.
26
Air Check Valve
Auto.
27
Air Supply Valve
N.O.
28
Air Pressure Relief Valve
Auto.
29
Air Supply Connection
N.O.
30
Low Pressure Switch
OP 1 Alarm Control Valve (Optional)
N.O.
Summary of Contents for Deluge Red-E
Page 1: ...Installation Guide Doc DV5A RED E 001 REV2 06 2019...
Page 2: ......
Page 5: ......
Page 80: ...75 Double Interlock Electric Pneumatic Wiring Schematic Non Integrated Releasing Panel...
Page 81: ...76 Double Interlock Electric Electric Wiring Schematic Non Integrated Releasing Panel...
Page 82: ...77 END...