![Tyco Deluge Red-E Installation Manual Download Page 43](http://html1.mh-extra.com/html/tyco/deluge-red-e/deluge-red-e_installation-manual_1185845043.webp)
38
Step 1.
Close the System Main Control Valve (2).
Step 2.
Close the Diaphragm Supply Valve (5) and Air Supply Valve (27).
Step 3.
Open the Main Drain Valve (4), System Drain Valve (23), and all auxiliary drains in the system. Close the
auxiliary drain valves and the System Drain Valve (23) after water ceases to discharge. Leave the Main Drain
Valve (4) open.
At this time make certain that the Pressure Gauge Valves and the Alarm Control Valve (OP 1), as applicable,
are open.
Do not open the Inspector’s Test Connection and auxiliary drains if resetting after a system test; otherwise,
system air pressure will be relieved unnecessarily.
Step 4.
Depress the plunger of the Automatic Drain Valve (3) to verify that it is open.
Step 5.
Clean the Diaphragm Supply Strainer (13) by removing the clean-out plug and strainer basket. The Dia-
phragm Supply Strainer (13) may be flushed out by momentarily opening the Diaphragm Supply Valve (5).
Step 6.
Inspect for and clear all ice plugs where system piping has been exposed to freezing conditions and
when there has been a flow of water into the system.
1
DV-5A Valve
Auto.
2
System Main Control Valve
N.O.
3
Automatic Drain Valve
Auto.
4
Main Drain Valve
N.C.
5
Diaphragm Supply Valve
N.O.
6
Manual Reset Actuator
7
Solenoid Valve
Auto.
8
Manual Control Station
N.C.
9
Alarm Test Valve
N.C.
10
Drip Funnel Drain
11
Water Supply Gauge
12
Water Supply Gauge Test Valve
N.O.
13
Diaphragm Supply Strainer
14
Diaphragm Supply Check Valve
Auto.
15
Diaphragm Gauge
16
System Riser
17
Drain Header
18
Supply Header
19
Waterflow Pressure Switch
20
Water Motor Alarm Connection
21
Downstream Shut Off Valve
N.O.
22
Funnel Drain Check Valve
Auto.
23
System Drain Valve
N.C.
24
System Gauge
25
System Gauge Valve
N.O.
26
Air Check Valve
Auto.
27
Air Supply Valve
N.O.
28
Air Pressure Relief Valve
Auto.
29
Air Supply Connection
N.O.
30
Low Pressure Switch
31
Dry Pilot Actuation
Auto.
OP 1 Alarm Control Valve (Optional)
N.O.
Figure 14
Double Interlock Preaction Electric Pneumatic
Actuation Schematic Piping Diagram
Summary of Contents for Deluge Red-E
Page 1: ...Installation Guide Doc DV5A RED E 001 REV2 06 2019...
Page 2: ......
Page 5: ......
Page 80: ...75 Double Interlock Electric Pneumatic Wiring Schematic Non Integrated Releasing Panel...
Page 81: ...76 Double Interlock Electric Electric Wiring Schematic Non Integrated Releasing Panel...
Page 82: ...77 END...