6
Standard Programs
The following standard programs are recommended for easy operation of the Red-E DV-5A.
Deluge, Single Interlock Preaction or Double Interlock Preaction (Pneumatic-Electric)
The PFC-4410RC, has more than 20 standard programs which are detailed in the
Installation,
Operation and Instruction Manual for the Potter PFC-4410RC
. Red-E Cabinet Deluge,
Single Interlock
Preaction or Double Interlock Preaction (Pneumatic-Electric)
configurations are pre-wired to function
with standard program
#12.
CAUTION
Selecting a standard program other than #12 can cause unintended results if pre-wired devices
are re-assigned (e.g. supervisory switch assigned as a manual dump).
If the standard program is not acceptable for the installation required, select the custom program
#0 then press the SET button. This will allow the user to custom program the panel. Refer to PFC-
4410RC Custom Program Information for Water Based Extinguishing Systems in the Installation,
Operation and Instruction Manual for the Potter PFC-4410RC for custom program information.
PROGRAM #12 MODE
1. Apply power to panel.
2. Move the program switch to program.
3. Press the FUNCTION button until the display reads “PASSWORD = 000”.
4. To enter a password, press the SELECT button until the proper number is displayed above the ^
symbol, then press the SET button to move to the next digit. After entering the third number the
display will change. (All panels are shipped with a 000 password.)
5. Press the FUNCTION button until the display reads “PROGRAM #”.
6. Press the SELECT button until the display reads “PROGRAM #12”.
7. Press the SET button.
8. The panel is completely programmed except for the custom banner and zone messages.
The panel should now display:
B A N N
E
R
M E S S A G E ?
SET
SELECT
Press the SELECT button to display the current message
FUNCTION
Summary of Contents for Deluge Red-E
Page 1: ...Installation Guide Doc DV5A RED E 001 REV2 06 2019...
Page 2: ......
Page 5: ......
Page 80: ...75 Double Interlock Electric Pneumatic Wiring Schematic Non Integrated Releasing Panel...
Page 81: ...76 Double Interlock Electric Electric Wiring Schematic Non Integrated Releasing Panel...
Page 82: ...77 END...