Installation Guide

Doc DV5A RED-E 001 REV2 06/2019

Summary of Contents for Deluge Red-E

Page 1: ...Installation Guide Doc DV5A RED E 001 REV2 06 2019...

Page 2: ......

Page 3: ...matic Electric 6 Deluge Valve Setting Procedure 22 Remote Resetting Deluge Valve Setting Procedure 26 Single Interlock Preaction Valve Setting Procedure 31 Double Interlock Preaction Valve Setting Pro...

Page 4: ...g Pressure Reducing Deluge Schematic Piping Diagram 28 Figure 13 DV 5A Valve Remote Resetting Pressure Reducing Trim System Outlet Pressure Pilot Valve Adjustment 31 Figure 14 Single Interlock Preacti...

Page 5: ......

Page 6: ...wner s and Insurer s test procedures NOTE This manual is not a replacement of the technical data sheets for assemblies and individual components used in a Red E DV 5A Cabinet The technical data sheets...

Page 7: ...trical conduits Connect the Piping q Connect the water supply to the cabinet q Connect the sprinkler system to the top outlet of cabinet q Connect the main drain header to a suitable drain Connect the...

Page 8: ...se the cabinet by turning the adjusting nut to raise the cabinet Use shims to fill voids between the cabinet base and the floor Figure 4 Wheel Base Extension The cabinet is provided with anchor point...

Page 9: ...Red E Cabinet models require power connections and initiating circuit connections Audible and visual signaling device circuit connections and remote signal circuit connections may also be required Ve...

Page 10: ...all for a bell or siren upon detection with strobe light or distinctive tone to signal water flow Check with the system designer to determine which signaling devices your system requires Remote signal...

Page 11: ...s will allow the user to custom program the panel Refer to PFC 4410RC Custom Program Information for Water Based Extinguishing Systems in the Installation Operation and Instruction Manual for the Pott...

Page 12: ...default message is When the up arrow has been advanced to the last selectable character pressing the FUNCTION button will cause the display to move to the next custom message The bottom line is set in...

Page 13: ...2 label is set in the same way as the banner The zone 2 label default value is When the up arrow has been advanced to the last selectable character pressing the FUNCTION button will cause the display...

Page 14: ...up arrow has been advanced to the last selectable character pressing the FUNCTION button will cause the display to move to the next programming section and the following screen will be displayed This...

Page 15: ...C in order to change the password The panel now displays the following Push the programming switch back to run in order to exit the programming mode The panel now displays the standby screen P U S H P...

Page 16: ...e circuit Operation Activation of either conventional detection zone will operate the release and the general alarm output and cause the alarm contact to change state Activation of the wateflow zone w...

Page 17: ...TEM SHUT OFF VALVE NOT USED SMOKE DETECTORS WHEN CONNECTING OBSERVE POLARITY SYSTEM 5 1 2 2 1 2 MAIN VALVE 1 1 5 2 2 1 5 1K 5 1K 5 1K FIELD WIRED 5 1K 2 1 2 2 STANDARD WIRING PFC 4410 RC CONTROL PANEL...

Page 18: ...HUT OFF VALVE FIELD WIRED SMOKE DETECTORS WHEN CONNECTING OBSERVE POLARITY SYSTEM 5 1 1 2 MAIN VALVE 1 1 5 2 5 1K 5 1K 5 1K 5 1K 5 1K 5 1K FIELD WIRED FIELD WIRED PS 10 WATERFLOW 2 2 2 1 5 1K 2 1 2 2...

Page 19: ...NOT USED SMOKE DETECTORS WHEN CONNECTING OBSERVE POLARITY SYSTEM 5 1 2 2 1 2 MAIN VALVE 1 1 5 2 2 1 5 1K 5 1K 5 1K FIELD WIRED 5 1K 2 1 2 2 STANDARD WIRING PFC 4410 RC CONTROL PANEL INSIDE THE POTTER...

Page 20: ...formation for Water Based Extinguishing Systems in Installation Operation and Instruction Manual for the Potter PFC 4410RC for custom program information PROGRAM 13 MODE 1 Apply power to panel 2 Move...

Page 21: ...peated to set the next character The default message is When the up arrow has been advanced to the last selectable character pressing the FUNCTION button will cause the display to move to the next cus...

Page 22: ...ing the FUNCTION button will cause the display to move to the next custom message The Zone 2 label is set in the same way as the banner The zone 2 label default value is SET SELECT Press the SELECT bu...

Page 23: ...ow has been advanced to the last selectable character pressing the FUNCTION button will cause the display to move to the next custom message The Zone 4 label is set in the same way as the banner The z...

Page 24: ...a password of 000 SET To leave the password at 000 press the SET button 3 times SELECT FUNCTION Refer to the Installation Operation and Instruction Manual for the Potter PFC 4410RC in order to change...

Page 25: ...one at the same time will operate the release and the general alarm output the alarm contact and the supervisory contact Activation of the wateflow zone will operate both waterflow bell outputs and th...

Page 26: ...OSS OF BATTERY TROUBLE CONDITION LOSS OF AC WIRING PROBLEM PANEL PROBLEM LIMITED AND NON POWER SUPERVISED RUN ALARM GENERAL BELL WATER BELL FLOW CIRCUIT RELEASE PANEL OUTPUTS INDICATING CIRCUITS NON P...

Page 27: ...or replace any smoke detector heads affected by smoke and to clear all smoke prior to resetting the control panel Follow the instructions in the Installation Operation and Instruction Manual for the...

Page 28: ...4 Diaphragm Supply Check Valve Auto 15 Diaphragm Gauge 16 System Riser 17 Drain Header 18 Supply Header 19 Waterflow Pressure Switch 20 Water Motor Alarm Connection 21 Downstream Shut Off Valve N O 22...

Page 29: ...n Replace operated pilot sprinklers and or reset the remote manual control stations Dry Pilot Actuation Replace operated pilot sprinklers and or reset the remote manual control stations Re establish d...

Page 30: ...amber pressurized per Step 8 temporarily close the Diaphragm Supply Valve 5 and then observe the Diaphragm Gauge 15 for a drop in pressure If a drop in pressure is noted the DV 5A Diaphragm is to be r...

Page 31: ...Step 5 Clean the Diaphragm Supply Strainer 13 by removing the clean out plug and strainer basket The Diaphragm Supply Strainer 13 may be flushed out by momentarily opening the Diaphragm Supply Valve 5...

Page 32: ...0 Partially open the System Main Control Valve 2 Slowly close the Main Drain Valve 4 as soon as water discharges from the Main Drain Valve 4 Observe the Automatic Drain Valve 3 for leaks If there are...

Page 33: ...orm Steps 1 through 13 when initially setting the TYCO DV 5A Valve with Remote Resetting Pressure Reducing Trim for service or after an operational test of the fire protection system Ref Figure 11 Fig...

Page 34: ...rop in pressure is noted the DV 5A Diaphragm is to be replaced and or any leaks must be corrected before proceeding to the next step If the Diaphragm Gauge 15 indicates no drop in pressure re open the...

Page 35: ...ectrically It is recommended that the valve is tripped electrically to test the entire system Step 2 Remove the Tamper Cap of the Pilot Valve by first loosening the Set Screw and unscrewing the Tamper...

Page 36: ...31 Figure 9 DV 5A Valve Remote Resetting Pressure Reducing Trim System Outlet Pressure Pilot Valve Adjustment...

Page 37: ...O 6 Manual Reset Actuator 7 Wet Pilot Line Connection 8 Manual Control Station N C 9 Alarm Test Valve N C 10 Drip Funnel Drain 11 Water Supply Gauge 12 Water Supply Gauge Test Valve N O 13 Diaphragm S...

Page 38: ...r Alarm Connection 21 Downstream Shut Off Valve N O 22 Funnel Drain Check Valve Auto 23 System Drain Valve N C 24 System Gauge 25 System Gauge Test Valve N O 26 Supervisory Air Check Valve Auto 27 Sup...

Page 39: ...o 15 Diaphragm Gauge 16 System Riser 17 Drain Header 18 Supply Header 19 Waterflow Pressure Switch 20 Water Motor Alarm Connection 21 Downstream Shut Off Valve N O 22 Funnel Drain Check Valve Auto 23...

Page 40: ...nual Control Stations Re establish dry pilot pneumatic pressure Electric Actuation Reset the electric detection system in accordance with the manufacturer s instructions to de energize the solenoid va...

Page 41: ...Automatic Drain Valve 3 for leaks If there are leaks determine correct the cause of the leakage problem before proceeding OTICE When the System Main Control Valve 2 is partially opened the pressure on...

Page 42: ...iaphragm Supply Valve N O 6 Manual Reset Actuator 7 Solenoid Valve Auto 8 Manual Control Station N C 9 Alarm Test Valve N C 10 Drip Funnel Drain 11 Water Supply Gauge 12 Water Supply Gauge Test Valve...

Page 43: ...e 5 Step 6 Inspect for and clear all ice plugs where system piping has been exposed to freezing conditions and when there has been a flow of water into the system 1 DV 5A Valve Auto 2 System Main Cont...

Page 44: ...sure builds and reaches approximately 15 psi 1 0 bar on the Diaphragm Gauge 15 and water stops flowing from its drain tube Pressure will then build up in the DV 5A Diaphragm Chamber Step 12 Inspect th...

Page 45: ...Automatic Drain Valve 3 for leaks If there are leaks determine correct the cause of the leakage problem before proceeding When the System Main Control Valve 2 is partially opened the pressure on the D...

Page 46: ...DV 5A compressor is mounted on a quick access extendable rail to permit easy servicing of the compressor air filter follow the instructions in the compressor manual for air filter servicing requiremen...

Page 47: ...erlock preaction and Double Interlock Preaction Electric Pneumatic configurations To verify the program settings of the standard program push the Program switch to the PROGRAM position The panel displ...

Page 48: ...e to the next position SELECT FUNCTION I N I T Z O N E 1 E N A B L E D SET Press the SET button to move to the next position SELECT FUNCTION I N I T Z O N E 2 E N A B L E D SET Press the SET button to...

Page 49: ...button to move to the next position SELECT FUNCTION I N I T Z O N E 4 E N A B L E D SET Press the SET button to move to the next position SELECT FUNCTION O U T P U T 1 E N A B L E D SET Press the SET...

Page 50: ...button to move to the next position SELECT FUNCTION O U T P U T 2 E N A B L E D SET Press the SET button to move to the next position SELECT FUNCTION O U T P U T 4 E N A B L E D SET Press the SET but...

Page 51: ...on to move to the next position SELECT FUNCTION P R O G R A M 1 2 P R O G R A M 0 N O R M A L SET SELECT Press the SELECT button until the display reads PROGRAM 0 FUNCTION SET Press the SET button to...

Page 52: ...button to move to the next position SELECT FUNCTION SET Press the SET button to move to the next position SELECT FUNCTION I N I T Z O N E 1 D E T E C T I O N SET Press the SET button to move to the ne...

Page 53: ...to move to the next position SELECT FUNCTION I N I T Z O N E 4 W A T E R F L O W SET Press the SET button to move to the next position SELECT FUNCTION SET Press the SET button to move to the next pos...

Page 54: ...SET button to move to the next position SELECT FUNCTION O U T P U T 1 I N D I C A T I N G SET Press the SET button to move to the next position SELECT FUNCTION O U T P U T 2 I N D I C A T I N G SET Pr...

Page 55: ...button to move to the next position SELECT FUNCTION O U T P U T 4 I N D I C A T I N G SET Press the SET button to move to the next position SELECT FUNCTION O U T P U T 3 N O R M A L SET Press the SET...

Page 56: ...s the FUNCTION button to move to the next position Z O N E 1 V O U T P U T S 1 3 SET SELECT FUNCTION Press the FUNCTION button to move to the next position SET SELECT FUNCTION Press the FUNCTION butto...

Page 57: ...the next position B A N N E R M E S S A G E SET SELECT FUNCTION Press the FUNCTION button 10 times to move to the next position B O T T O M L I N E O U T P U T S 1 2 4 SET SELECT Press the SELECT but...

Page 58: ...display the current message FUNCTION SET SELECT FUNCTION Press the FUNCTION button 10 times to move to the next position Z O N E 1 M E S S A G E SET SELECT Press the SELECT button to display the curr...

Page 59: ...times to move to the next position Z O N E 2 M E S S A G E SET SELECT Press the SELECT button to display the current message FUNCTION Z O N E 2 SET SELECT FUNCTION Press the FUNCTION button 10 times t...

Page 60: ...the current message FUNCTION S Y S T V A L V E SET SELECT FUNCTION Press the FUNCTION button 10 times to move to the next position Z O N E 4 M E S S A G E SET SELECT Press the SELECT button to displa...

Page 61: ...E D E D V 5 A 0 1 0 1 R E A D Y 0 0 4 1 If all of the entries above match those on the actual panel the control panel is in the default Red E DV 5A deluge single interlock or double interlock preacti...

Page 62: ...lectric configurations To verify the program settings of the standard program push the Program switch to the right The panel displays the following L O O K A T H I S T O R Y SET SELECT FUNCTION Press...

Page 63: ...imes to move to the next position SELECT FUNCTION SET Press the SET button to move to the next position SELECT FUNCTION SET Press the SET button to move to the next position SELECT FUNCTION I N I T Z...

Page 64: ...tion SELECT FUNCTION I N I T Z O N E 4 E N A B L E D SET Press the SET button to move to the next position SELECT FUNCTION O U T P U T 1 E N A B L E D SET Press the SET button to move to the next posi...

Page 65: ...button to move to the next position SELECT FUNCTION SET Press the SET button to move to the next position SELECT FUNCTION O U T P U T 4 E N A B L E D SET Press the SET button to move to the next posi...

Page 66: ...move to the next position SELECT FUNCTION P R O G R A M 1 3 OR P R O G R A M 0 SET SELECT Press the SELECT button until the display reads PROGRAM 0 FUNCTION P R O G R A M 0 SET Press the SET button t...

Page 67: ...utton to move to the next position SELECT FUNCTION SET Press the SET button to move to the next position SELECT FUNCTION SET Press the SET button to move to the next position SELECT FUNCTION I N I T Z...

Page 68: ...to move to the next position SELECT FUNCTION I N I T Z O N E 4 W A T E R F L O W SET Press the SET button to move to the next position SELECT FUNCTION S U P E R V S R Y 1 Z O N E S U P E R V S R Y SE...

Page 69: ...FUNCTION SET Press the SET button to move to the next position SELECT FUNCTION S U P E R V S R Y 2 Z O N E S U P E R V S R Y SET Press the SET button to move to the next position SELECT FUNCTION O U...

Page 70: ...C A T I N G SET Press the SET button to move to the next position SELECT FUNCTION O U T P U T 3 C R O S S Z O N E D SET Press the SET button to move to the next position SELECT FUNCTION SET Press the...

Page 71: ...SET button to move to the next position SELECT FUNCTION SET SELECT FUNCTION Press the FUNCTION button to move to the next position Z O N E 1 V O U T P U T S 1 3 SET SELECT FUNCTION Press the FUNCTION...

Page 72: ...Press the FUNCTION button to move to the next position B A N N E R M E S S A G E SET SELECT Press the SELECT button to display the current message FUNCTION R E D E D V 5 A SET SELECT FUNCTION Press th...

Page 73: ...ELECT button to display the current message FUNCTION SET SELECT FUNCTION Press the FUNCTION button 10 times to move to the next position SET SELECT Press the SELECT button to display the current messa...

Page 74: ...T SELECT Press the SELECT button to display the current message FUNCTION SET Press the SET button to move to the next position SELECT FUNCTION SET SELECT FUNCTION Press the FUNCTION button 10 times to...

Page 75: ...ECT button to display the current message FUNCTION S Y S T V A L V E SET SELECT FUNCTION Press the FUNCTION button 10 times to move to the next position SET SELECT Press the SELECT button to display t...

Page 76: ...de The panel now displays the standby screen R E D E D V 5 A 0 1 0 1 R E A D Y 0 0 4 1 If all of the entries above match those on the actual panel the control panel is in the default Red E DV 5A doubl...

Page 77: ...72 APPENDIX A Electrical Wiring Schematics for Non Integral Panel Models Deluge Release Wiring Schematic Non Integrated Releasing Panel...

Page 78: ...73 Remote Resetting and Remote Resetting Pressure Reducing Deluge Wiring Schematic Non Integrated Releasing Panel ACTUATION...

Page 79: ...74 Single Interlock Wiring Schematic Non Integrated Releasing Panel NOT USED ON WET OR DRY PILOT MODELS...

Page 80: ...75 Double Interlock Electric Pneumatic Wiring Schematic Non Integrated Releasing Panel...

Page 81: ...76 Double Interlock Electric Electric Wiring Schematic Non Integrated Releasing Panel...

Page 82: ...77 END...