Step 5.
After the fi re sprinkler system
pressure gauge indicates approxi-
mately the same pressure as the supply
pressure gauge, fully open the Main
Control Valve.
Step 6.
Open the highest elevation
outlet on the domestic system.
Step 7.
Partially open the Domestic
Control Valve until the sound of fl owing
water begins. Allow the domestic
piping to fi ll slowly with water.
Step 8.
Close the highest elevation
water outlet on the domestic system
when unaerated water begins to fl ow.
Step 9.
Completely open the Domes-
tic Control Valve, then check that the
domestic system is properly pressur-
ized by verifying that at least three
water outlets in the domestic system
can fl ow full at the same time.
• If the water outlets fl ow fully, the
Model RSV-1 Valve is set and ready
for service. Close the water outlets
on the domestic system.
• If the water outlets do not fl ow
fully, re-close the Domestic
Control Valve, wait a minimum
of ten seconds, and ensure that
there is no fl
ow from the fi
re
sprinkler system piping. Reopen
the Domestic Control Valve, then
recheck that the water outlets are
fl owing fully.
Care and
Maintenance
The following inspection procedure for
the TYCO RAPID RESPONSE Model
RSV-1 Residential Shut-Off Valve must
be performed as indicated, in addition
to any specifi c requirements of the
NFPA. Any impairment must be imme-
diately corrected.
Before closing a fi re protection system
control valve for inspection or main-
tenance work on the fi re protection
system that it controls, obtain per-
mission to shut down the affected fi re
protection system from the proper
authorities and notify all personnel who
may be affected by this action.
Make no attempt to repair any Model
RSV-1 Valve component in the fi eld.
The Model RSV-1 Valve is not fi eld-
repairable. If malfunction occurs, the
entire unit must be replaced.
The operational test and fl ow test pro-
cedures result in operation of the asso-
ciated alarms, as well as an interruption
of the domestic water supply service.
You must notify the owner, building
occupants, and the fi re department,
central station, or other signal station
to which the alarms are connected.
After placing a fi re protection system
in service, notify the proper authorities
and advise those responsible for moni-
toring proprietary and/or central station
alarms.
The owner is responsible for the
inspection, testing, and maintenance of
their fi re protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the
standards of any authority having juris-
diction. Contact the installing contrac-
tor or product manufacturer regarding
any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualifi ed Inspection Service in accor-
dance with local requirements and/or
national codes and standards.
Operation Test Procedure
Step 1.
Fully open two or three water
outlets in the domestic piping system.
Step 2.
To simulate a sprinkler opera-
tion, open the Alarm Test Connection
of the fi re sprinkler system.
Step 3.
Verify that any alarms are oper-
ating and that the fl ow from the domes-
tic water outlets decreases to no more
than a trickle.
Step 4.
Reset the Model RSV-1 Valve
in accordance with the Valve Setting
Procedure described in this data sheet.
Flow Test Procedure
Step A.
While there is no water
fl owing in the domestic system, com-
pletely open the Drain and Flow Test
Connection.
Step B.
While water is fl owing, record
the pressure reading on the fi re sprin-
kler system pressure gauge and then
compare this reading to previous
readings.
If there is a signifi cant decrease in pres-
sure since the last time the pressure
reading was taken and this decrease
is not due to a normally expected drop
in the water supply pressure, an impair-
ment may exist that should be immedi-
ately identifi ed and corrected.
Step C.
Close the Drain and Flow Test
Connection to allow the Model RSV-1
Valve to reset automatically. Automatic
resetting occurs within ten seconds.
Step D.
After waiting ten seconds, com-
pletely open at least three water outlets
in the domestic system and allow these
outlets to fl ow simultaneously.
If the water outlets flow fully, the
Model RSV-1 Valve is set and ready for
service. Close the water outlets on the
domestic system.
If the water outlets do not fl ow fully,
close the Domestic Control Valve and
verify that there is no fl ow from the fi re
sprinkler system piping, such as at
the Inspector’s Test Connection. Wait
a minimum of ten seconds. Re-open
the Domestic Control Valve and then
recheck that the domestic system
water outlets are fl owing full.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fi re.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Valves with NPT Connections
Specify: 1 Inch NPT (DN25) Model
RSV-1 Residential Shut-Off Valve,
P/N 52-540-1-001
Specify: 2 Inch NPT (DN50) Model
RSV-1 Residential Shut-Off Valve,
P/N 52-540-1-002