Step 5.

 After the fi re sprinkler system 

pressure gauge indicates approxi-
mately the same pressure as the supply 
pressure gauge, fully open the Main 
Control Valve.

Step 6.

 Open the highest elevation 

outlet on the domestic system.

Step 7.

 Partially open the Domestic 

Control Valve until the sound of fl owing 
water begins. Allow the domestic 
piping to fi ll slowly with water.

Step 8.

 Close the highest elevation 

water outlet on the domestic system 
when unaerated water begins to fl ow.

Step 9.

 Completely open the Domes-

tic Control Valve, then check that the 
domestic system is properly pressur-
ized by verifying that at least three 
water outlets in the domestic system 
can fl ow full at the same time.

•  If the water outlets fl ow fully, the 

Model RSV-1 Valve is set and ready 
for service. Close the water outlets 
on the domestic system.

•  If the water outlets do not fl ow 

fully, re-close the Domestic 
Control Valve, wait a minimum 
of ten seconds, and ensure that 
there is no fl 

ow from the fi 

re 

sprinkler system piping. Reopen 
the Domestic Control Valve, then 
recheck that the water outlets are 
fl owing fully. 

Care and
Maintenance

The following inspection procedure for 
the TYCO RAPID RESPONSE Model 
RSV-1 Residential Shut-Off Valve must 
be performed as indicated, in addition 
to any specifi c requirements of the 
NFPA. Any impairment must be imme-
diately corrected.

Before closing a fi re protection system 
control valve for inspection or main-
tenance work on the fi re protection 
system  that  it  controls,  obtain  per-
mission to shut down the affected fi re 
protection system from the proper 
authorities and notify all personnel who 
may be affected by this action.

Make no attempt to repair any Model 
RSV-1 Valve component in the fi eld. 
The Model RSV-1 Valve is not fi eld-
repairable. If malfunction occurs, the 
entire unit must be replaced.

The operational test and fl ow test pro-
cedures result in operation of the asso-
ciated alarms, as well as an interruption 
of the domestic water supply service. 
You must notify the owner, building 
occupants, and the fi re department, 
central station, or other signal station 
to which the alarms are connected.

After placing a fi re protection system 
in service, notify the proper authorities 
and advise those responsible for moni-
toring proprietary and/or central station 
alarms.

The owner is responsible for the 
inspection, testing, and maintenance of 
their fi re protection system and devices 
in compliance with this document, as 
well as with the applicable standards 
of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the 
standards of any authority having juris-
diction. Contact the installing contrac-
tor or product manufacturer regarding 
any questions.

Automatic sprinkler systems should be 
inspected, tested, and maintained by a 
qualifi ed Inspection Service in accor-
dance with local requirements and/or 
national codes and standards.

Operation Test Procedure

Step 1.

 Fully open two or three water 

outlets in the domestic piping system. 

Step 2.

 To simulate a sprinkler opera-

tion, open the Alarm Test Connection 
of the fi re sprinkler system.

Step 3.

 Verify that any alarms are oper-

ating and that the fl ow from the domes-
tic water outlets decreases to no more 
than a trickle.

Step 4.

 Reset the Model RSV-1 Valve 

in accordance with the Valve Setting 
Procedure described in this data sheet.

Flow Test Procedure

Step A.

 While there is no water 

fl owing in the domestic system, com-
pletely open the Drain and Flow Test 
Connection.

Step B.

 While water is fl owing, record 

the pressure reading on the fi re sprin-
kler system pressure gauge and then 
compare this reading to previous 
readings.

If there is a signifi cant decrease in pres-
sure since the last time the pressure 
reading was taken and this decrease 
is not due to a normally expected drop 
in the water supply pressure, an impair-
ment may exist that should be immedi-
ately identifi ed and corrected.

Step C.

 Close the Drain and Flow Test 

Connection to allow the Model RSV-1 
Valve to reset automatically. Automatic 
resetting occurs within ten seconds. 

Step D.

 After waiting ten seconds, com-

pletely open at least three water outlets 
in the domestic system and allow these 
outlets to fl ow simultaneously.

If the water outlets flow fully, the 
Model RSV-1 Valve is set and ready for 
service. Close the water outlets on the 
domestic system.

If the water outlets do not fl ow fully, 
close the Domestic Control Valve and 
verify that there is no fl ow from the fi re 
sprinkler system piping, such as at 
the Inspector’s Test Connection. Wait 
a minimum of ten seconds. Re-open 
the Domestic Control Valve and then 
recheck that the domestic system 
water outlets are fl owing full.

Limited
Warranty

For warranty terms and conditions, visit 
www.tyco-fi re.com.

Ordering 
Procedure

Contact your local distributor for avail-
ability. When placing an order, indicate 
the full product name and Part Number 
(P/N).

Valves with NPT Connections

Specify: 1 Inch NPT (DN25) Model 
RSV-1 Residential Shut-Off Valve, 
P/N 52-540-1-001

Specify: 2 Inch NPT (DN50) Model 
RSV-1 Residential Shut-Off Valve, 
P/N 52-540-1-002

Summary of Contents for RAPID RESPONSE RSV-1

Page 1: ...ally resets thereby eliminating the need for valve disassembly after a fire sprinkler system test or operation NOTICE The Model RSV 1 Residential Shut Off Valves described herein must be installed and maintained in compliance with this document as well as with the applicable standards of the National Fire Protection Association in addi tion to the standards of any authorities having jurisdiction F...

Page 2: ...ossible resid Design Criteria The TYCO RAPID RESPONSE Model RSV 1 Residential Shut Off Valve must be installed vertically with the Water Supply Port at the bottom the Fire Sprinkler Port at the top and the Domestic Port at the side Ref Figures 4 and 5 Figure 1 shows the typical installation arrangement Refer to the Installation section for additional design considerations Water Supply Requirements...

Page 3: ...ly when performing hydraulic design calculations for the fire sprinkler system you do not need to consider trickle flow through the Model RSV 1 Valve Internal By Pass Restriction into the domestic system When using the 2 inch RSV 1 the maximum flow rate through the Internal By Pass Restriction when the Model RSV 1 Valve is in the operated position is no greater than 1 5 GPM 5 7 LPM for a typical r...

Page 4: ... to or less than the smallest K factor sprinkler in the system downstream of the Water flow Detector Step 6 Apply pipe thread sealant spar ingly only to the male pipe threads that are to be assembled to the three ports of the Model RSV 1 Valve The use of a non hardening pipe thread sealant such as TEFLON is recommended Valve Setting Procedure Perform steps 1 through 9 when initially filling the fi...

Page 5: ...E DOMESTIC SEAT OPERATED STANDBY SUPPLY SUPPLY TO FIRE SPRINKLERS TO DOMESTIC FIRE SPRINKLER FLOW PASSAGE SUPPLY PORT FIRE SPRINKLER PORT DOMESTIC PORT FIRE SPRINKLER SEAT SUPPLY PORT FIRE SPRINKLER SEAT DOMESTIC PORT FIRE SPRINKLER PORT PISTON ASSEMBLY DOMESTIC SEAT INTERNAL BY PASS RESTRICTION PISTON ASSEMBLY DOMESTIC FLOW PASSAGE DOMESTIC SEAT FIGURE 4 1 INCH DN25 MODEL RSV 1 RESIDENTIAL SHUT O...

Page 6: ... for the inspection testing and maintenance of their fire protection system and devices in compliance with this document as well as with the applicable standards of the National Fire Protection Associa tion e g NFPA 25 in addition to the standards of any authority having juris diction Contact the installing contrac tor or product manufacturer regarding any questions Automatic sprinkler systems sho...

Reviews: