TFP980

Page 2 of 6

Operating 
Principles

When a fi re sprinkler activates during 
domestic usage, the TYCO RAPID 
RESPONSE Model RSV-1 Residential 
Shut-Off Valve automatically diverts 
fl ow to the domestic system and diverts 
the available water supply to the fi re 
sprinkler system, thereby eliminating a 
reduced fl ow condition in the sprinkler 
system that might otherwise be caused 
by possible signifi cant domestic water 
usage.

When the Model RSV-1 Valve is in the 
normal standby position as shown in 
Figures 4 and 5, the Piston Assembly, 
assisted by its Spring, is in the down 
position. With the Piston Assembly in 
the down position, the Fire Sprinkler 
Seal permits the Model RSV-1 Valve 
to perform as a conventional check 
valve. Also, with the Piston Assembly 
in the down position, water is available 
on demand through the Domestic Flow 
Passage and out the Domestic Port.

Upon operation and with a minimum 
design water fl ow (e.g., 12.5 GPM (47,3 
LPM) for the 1 inch Valve or 8 GPM 
(30,5 LPM) for the 2 Inch Valve) to 
the automatic residential fi re  sprinkler 
system, the Piston Assembly moves 

upward. With the Piston Assembly in 
the up position, any water fl ow to the 
Domestic  Port  is  diverted  to  the  Fire 
Sprinkler Port.

The contours of the Piston Assembly 
are specifi cally confi gured to minimize 
its upward movement except under the 
level of sustained fi re sprinkler system 
fl ow resulting from operation of one or 
more fi re sprinklers. However, because 
most fi re sprinkler systems contain air 
pockets, the Piston Assembly tends to 
move momentarily upward when there 
is a surge in supply pressure.

The momentary opening and re-clos-
ing of the Piston Assembly at the Fire 
Sprinkler Line Seal traps a portion 
of the pressure increase within the 
fi re sprinkler system. Trapped pres-
sure increases within the fi re sprinkler 
system help to prevent a subsequent 
surge in the supply pressure from 
causing the water-flow detector to 
signal a false alarm.

As indicated above, domestic system 
usage can reduce the pressure avail-
able to the fire sprinkler system. 
However, when utilizing the Model 
RSV-1 Valve, you do not need to include 
additional hydraulic fl ow of the domes-
tic system, when otherwise required by 
NFPA standards (NFPA 13D or 13R), to 
determine the minimum possible resid-

Design Criteria

The TYCO RAPID RESPONSE Model 
RSV-1 Residential Shut-Off Valve 
must be installed vertically with the 
Water Supply Port at the bottom, the 
Fire Sprinkler Port at the top, and the 
Domestic Port at the side (Ref. Figures 
4 and 5). Figure 1 shows the typical 
installation arrangement. Refer to 
the Installation section for additional 
design considerations.

Water Supply Requirements

1 Inch (DN25) Valve

In order for the 1 Inch (DN25) Model 
RSV-1 Valve to operate automati-
cally upon sprinkler operation, the fi re 
sprinkler system from the water main 
to the most hydraulically remote sprin-
kler  must  be  designed  to  provide  a 
minimum single sprinkler fl ow of 12.5 
GPM (47,3 LPM) when the supply 
pressure at the main is at its minimum 
expected value.

The minimum single sprinkler flow 
rate of 12.5 GPM (47,3 LPM), required 
for use with the 1 Inch (DN25) Model 
RSV-1 Valve, does not take precedence 
over any more hydraulically demanding 
single sprinkler fl ow rate specifi ed  for 
the residential sprinklers in use.

When performing hydraulic design cal-
culations for the fi re sprinkler system, 
you need not account for the trickle 
fl ow through the 1 Inch (DN25) Model 
RSV-1 Valve By-Pass Restriction into 
the domestic system.

For the 1 Inch (DN25) Model RSV-1 
Valve, the maximum water supply 
service line is 1 inch (DN25).

2 Inch (DN50) Valve

In order for the 2 Inch (DN50) Model 
RSV-1 Valve to operate automatically 
at sprinkler activation, the fi re sprin-
kler system from the water supply 
main to the most hydraulically remote 
sprinkler must be designed to provide 
a minimum single sprinkler fl ow of 8 
GPM (30,5 LPM) when the water supply 
pressure at the water supply main is at 
its minimum expected value.

The minimum single sprinkler fl ow rate 
of 8 GPM (30,5 LPM), required for use 
with the 2 Inch (DN50) Model RSV-1 
Valve, does not take precedence over 
any more hydraulically demanding 
single sprinkler fl ow rate specifi ed  for 
the residential sprinklers in use.

FIRE SPRINKLER

SYSTEM PRESSURE

GAUGE

WATERFLOW

DETECTOR

(FIRE ALARM)

MODEL RSV-1

RESIDENTIAL

SHUT-OFF VALVE

(AUTOMATIC)

WATER
METER

MAIN

CONTROL

VALVE

WATER

SUPPLY

WATER

SUPPLY

GATE

VALVE

BACKFLOW PREVENTER AS

REQUIRED BY AUTHORITY

HAVING JURISDICTION

AUTOMATIC FIRE SPRINKLERS

TO DOMESTIC

SYSTEM

SUPPLY

PRESSURE

GAUGE

DOMESTIC

CONTROL

VALVE

DRAIN AND FLOW

TEST CONNECTION

ALARM TEST

CONNECTION

WATER SUPPLY

MAIN

FIGURE 1

MODEL RSV-1 RESIDENTIAL SHUT-OFF VALVE

TYPICAL INSTALLATION ARRANGEMENT

Summary of Contents for RAPID RESPONSE RSV-1

Page 1: ...ally resets thereby eliminating the need for valve disassembly after a fire sprinkler system test or operation NOTICE The Model RSV 1 Residential Shut Off Valves described herein must be installed and maintained in compliance with this document as well as with the applicable standards of the National Fire Protection Association in addi tion to the standards of any authorities having jurisdiction F...

Page 2: ...ossible resid Design Criteria The TYCO RAPID RESPONSE Model RSV 1 Residential Shut Off Valve must be installed vertically with the Water Supply Port at the bottom the Fire Sprinkler Port at the top and the Domestic Port at the side Ref Figures 4 and 5 Figure 1 shows the typical installation arrangement Refer to the Installation section for additional design considerations Water Supply Requirements...

Page 3: ...ly when performing hydraulic design calculations for the fire sprinkler system you do not need to consider trickle flow through the Model RSV 1 Valve Internal By Pass Restriction into the domestic system When using the 2 inch RSV 1 the maximum flow rate through the Internal By Pass Restriction when the Model RSV 1 Valve is in the operated position is no greater than 1 5 GPM 5 7 LPM for a typical r...

Page 4: ... to or less than the smallest K factor sprinkler in the system downstream of the Water flow Detector Step 6 Apply pipe thread sealant spar ingly only to the male pipe threads that are to be assembled to the three ports of the Model RSV 1 Valve The use of a non hardening pipe thread sealant such as TEFLON is recommended Valve Setting Procedure Perform steps 1 through 9 when initially filling the fi...

Page 5: ...E DOMESTIC SEAT OPERATED STANDBY SUPPLY SUPPLY TO FIRE SPRINKLERS TO DOMESTIC FIRE SPRINKLER FLOW PASSAGE SUPPLY PORT FIRE SPRINKLER PORT DOMESTIC PORT FIRE SPRINKLER SEAT SUPPLY PORT FIRE SPRINKLER SEAT DOMESTIC PORT FIRE SPRINKLER PORT PISTON ASSEMBLY DOMESTIC SEAT INTERNAL BY PASS RESTRICTION PISTON ASSEMBLY DOMESTIC FLOW PASSAGE DOMESTIC SEAT FIGURE 4 1 INCH DN25 MODEL RSV 1 RESIDENTIAL SHUT O...

Page 6: ... for the inspection testing and maintenance of their fire protection system and devices in compliance with this document as well as with the applicable standards of the National Fire Protection Associa tion e g NFPA 25 in addition to the standards of any authority having juris diction Contact the installing contrac tor or product manufacturer regarding any questions Automatic sprinkler systems sho...