ual (fl owing)  pressure  available  to  the 
fi re sprinkler system.

For operation of the Model RSV-1 Resi-
dential Shut-Off Valve, you need only 
design the fi re sprinkler system from 
the water supply main to the most 
hydraulically remote sprinkler. Domes-
tic fl ow does not require consideration. 
As long as the single sprinkler fl ow  is 
equal to or greater than 12.5 GPM (47,3 
LPM) for the 1 Inch Valve or 8 GPM 
(30,5 LPM) for the 2 Inch Valve when 
the supply pressure at the main is at 
its minimum expected value, the Model 
RSV-1 Valve automatically diverts the 
domestic fl ow.

After the Piston Assembly has moved 
to the full up position, only a small 
amount of water is permitted to trickle 
through the Internal By-Pass Restric-
tion to the Domestic Port (Ref. Figures 
4 and 5). The trickle fl ow through the 
Internal By-Pass Restriction permits 
the Model RSV-1 Valve to reset auto-
matically after a sprinkler operation or 
test without draining the fi re  sprinkler 
system.

When the Domestic Control Valve is 
closed, the Internal By-Pass Restriction 
allows the Supply and Domestic Port 
pressures to equalize and the Piston 
Assembly to move back down to the 
standby position.

When using the 1 inch RSV-1, the 
maximum fl ow rate through the Internal 
By-Pass Restriction, when the Model 
RSV-1 Valve is in the operated position, 
is no greater than .25 GPM (0,9 LPM) 
for a typical residual (fl owing) pressure 
of 40 psi (2,8 bar) at the inlet. Conse-
quently, when performing hydraulic 
design calculations for the fi re sprinkler 
system, you do not need to consider 
trickle fl ow through the Model RSV-1 
Valve Internal By-Pass Restriction into 
the domestic system.

When using the 2 inch RSV-1, the 
maximum fl ow rate through the Internal 
By-Pass Restriction, when the Model 
RSV-1 Valve is in the operated position, 
is no greater than 1.5 GPM (5,7 LPM) 
for a typical residual (fl owing) pressure 
of 40 psi (2,8 bar) at the inlet. Conse-
quently, when performing hydraulic 
design calculations for the fi re sprin-
kler system, a 1.5 GPM (5,7 LPM) fl ow 
demand  is  required  to  be  added  at 
the RSV-1 and calculated back to the 
source.

Components:

-

2

Body

1 -

4

9

12

13

1

7

8

6

3

2

5

8-3/16"

(208,0 mm)

4-15/16"

(125,4 mm)

3-1/4"

(82,6 mm)

2-3/8"

(60,3 mm)

WATER

SUPPLY

PORT, 1" NPT

3-5/8" DIA.

(92,1 mm)

FIRE

SPRINKLER

PORT, 1" NPT

DOMESTIC

PORT,

1" NPT

11

14

15

10

5

Top Cover
Screw,
Upper Cap

3 -

Upper Cap

-

4

O-Ring,
Cover (2)

5 -

Upper Seal

6 -

O-Ring,
Upper Sleeve

7 -

Sleeve

8 -

Spring

9 -

Differential
Ring

10 -

Lower Seal

11 -

Screw,
Piston (4)

12 -

Bottom Cover

13 -

Piston

-

14

O-Ring,
Lower Sleeve

15 -

Components:

4-1/2"

(114,3 mm)

4-9/16"

(115,9 mm)

5-3/8" DIA.
(136,5 mm)

3-3/4"

(95,3 mm)

9-1/16"

(230,2 mm)

FIRE

SPRINKLER

PORT, 2" NPT

DOMESTIC

PORT,

2" NPT

WATER

SUPPLY

PORT, 2" NPT

-

2

Insert Sleeve

Cover O-Ring

Insert Sleeve
O-Ring (2)

Piston Seal

Bottom Seal

-

8

-

4

7 -

3 -

Body

1 -

Piston Nut

Piston Spring

-

6

5 -

Piston Cover

Piston Insert

Cover

Retainer Ring

9 -

10 -
11 -
12 -

-

13

Bottom Seal
O-Ring

3

7

9

4

2

9

11

10

6

5

1

12

8

13

FIGURE 2 

1 INCH (DN25) MODEL RSV-1 RESIDENTIAL SHUT-OFF VALVE

ASSEMBLY AND DIMENSIONS

FIGURE 3 

2 INCH (DN50) MODEL RSV-1 RESIDENTIAL SHUT-OFF VALVE

ASSEMBLY AND DIMENSIONS

Summary of Contents for RAPID RESPONSE RSV-1

Page 1: ...ally resets thereby eliminating the need for valve disassembly after a fire sprinkler system test or operation NOTICE The Model RSV 1 Residential Shut Off Valves described herein must be installed and maintained in compliance with this document as well as with the applicable standards of the National Fire Protection Association in addi tion to the standards of any authorities having jurisdiction F...

Page 2: ...ossible resid Design Criteria The TYCO RAPID RESPONSE Model RSV 1 Residential Shut Off Valve must be installed vertically with the Water Supply Port at the bottom the Fire Sprinkler Port at the top and the Domestic Port at the side Ref Figures 4 and 5 Figure 1 shows the typical installation arrangement Refer to the Installation section for additional design considerations Water Supply Requirements...

Page 3: ...ly when performing hydraulic design calculations for the fire sprinkler system you do not need to consider trickle flow through the Model RSV 1 Valve Internal By Pass Restriction into the domestic system When using the 2 inch RSV 1 the maximum flow rate through the Internal By Pass Restriction when the Model RSV 1 Valve is in the operated position is no greater than 1 5 GPM 5 7 LPM for a typical r...

Page 4: ... to or less than the smallest K factor sprinkler in the system downstream of the Water flow Detector Step 6 Apply pipe thread sealant spar ingly only to the male pipe threads that are to be assembled to the three ports of the Model RSV 1 Valve The use of a non hardening pipe thread sealant such as TEFLON is recommended Valve Setting Procedure Perform steps 1 through 9 when initially filling the fi...

Page 5: ...E DOMESTIC SEAT OPERATED STANDBY SUPPLY SUPPLY TO FIRE SPRINKLERS TO DOMESTIC FIRE SPRINKLER FLOW PASSAGE SUPPLY PORT FIRE SPRINKLER PORT DOMESTIC PORT FIRE SPRINKLER SEAT SUPPLY PORT FIRE SPRINKLER SEAT DOMESTIC PORT FIRE SPRINKLER PORT PISTON ASSEMBLY DOMESTIC SEAT INTERNAL BY PASS RESTRICTION PISTON ASSEMBLY DOMESTIC FLOW PASSAGE DOMESTIC SEAT FIGURE 4 1 INCH DN25 MODEL RSV 1 RESIDENTIAL SHUT O...

Page 6: ... for the inspection testing and maintenance of their fire protection system and devices in compliance with this document as well as with the applicable standards of the National Fire Protection Associa tion e g NFPA 25 in addition to the standards of any authority having juris diction Contact the installing contrac tor or product manufacturer regarding any questions Automatic sprinkler systems sho...