Description

The Series DS-2, 11.2 K-factor,
ECLH/ECOH (Extended Coverage
Light Hazard / Extended Coverage Or-
dinary Hazard) Dry Type Sprinklers
are decorative glass bulb automatic
sprinklers designed for the following
typical uses:

where pendent sprinklers are re-
quired on dry pipe systems that
are exposed to freezing tempera-
tures (e.g. sprinkler drops from un-
heated portions of buildings)

where sprinklers and/or a portion
of the connecting piping may be
exposed to freezing temperatures
(e.g. sprinkler drops from wet sys-
tems into freezers)

WARNINGS

The Series DS-2 Dry Type Sprinklers
described herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the integrity of these devices.

The owner is responsible for maintain-
ing their fire protection system and de-
vices in  proper operating  condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.

The Series DS-2 Dry Type Sprinklers
must only be installed in fittings that
meet the requirements of the Design
Criteria section.

Model/Sprinkler
Identification
Numbers

TY5238

Technical
Data

Approvals

UL and C-UL Listed.
(Refer to Table A)

Maximum Working Pressure

175 psi (12,1 bar)

Inlet Thread Connection

1 inch NPT (Standard Order)
ISO 7-R1

*Discharge Coefficient

Refer to Table C

Temperature Ratings

Refer to Table A

Finishes

Sprinkler : Natural Brass, Chrome
Plated, White Polyester
Escutcheon: White Coated, Chrome
Plated, Brass Plated

Physical Characteristics

Inlet . . . . . . . . . . . . .

Copper

Yoke . . . . . . . . . Stainless Steel
Casing . . . Galvanized Carbon Steel
Insert

. . . . . . . . . . . . . Bronze

Bulb Seat . . . . . . . . . . . Bronze
Bulb . . . . . . . . . . . . . .

Glass

Compression Screw

. . . . . Bronze

Deflector . . . . . . . . . . . . Bronze
Frame . . . . . . . . . . . . . Bronze
Guide Tube . . . . . Stainless Steel
Water Tube

. . . . . Stainless Steel

Spring . . . . . . . . Stainless Steel

Plug

. . . . . . . . . . . . . Copper

Sealing Assembly . . . . . . . . . .

. . . . . . Beryllium Nickel w/Teflon*

Pin . . . . . . . . . . Stainless Steel
Button Spring

. . . . Stainless Steel

Helper Spring . . . . Stainless Steel
Escutcheon

. . . . . . Carbon Steel

Patents

U.S.A. Patent Number 5,188,185;
5,366,022; 5,579,846; 5,584,344; and,
5,609,211  may  be  applicable to the
Series DS-2, 11.2 K-factor, Standard
and Quick Response, Standard Cover-
age, Dry Type Sprinklers.

Page 1 of 6

TFP540

FEBRUARY, 2002

Series DS-2 — 11.2 K-factor*
Dry Type Sprinklers
Extended Coverage, Light & Ordinary Hazard

Technical Services:

Tel: (800) 381-9312 / Fax: (800) 791-5500

* Registered Trademark of DuPont

Customer Service/Sales:

Tel: (215) 362-0700 / (800) 523-6512

Fax: (215) 362-5385

TFP540 (5-14.1)

OBSOLETE

Summary of Contents for DS-2 Series

Page 1: ...at meet the requirements of the Design Criteria section Model Sprinkler Identification Numbers TY5238 Technical Data Approvals UL and C UL Listed Refer to Table A Maximum Working Pressure 175 psi 12 1 bar Inlet Thread Connection 1 inch NPT Standard Order ISO 7 R1 Discharge Coefficient Refer to Table C Temperature Ratings Refer to Table A Finishes Sprinkler Natural Brass Chrome Plated White Polyest...

Page 2: ...1 inch NPT Series DS 2 Dry Type Sprinklers on a dry pipe sprinkler system only use the side out let of maximum 2 1 2 inch size reduc ing tee s For wet pipe sprinkler systems the Series DS 2 Dry Type Sprinklers may also be installed in the 1 inch NPT outlet of a Central Figure 730 Mechani cal Tee NOTE Do not install the Series DS 2 into any other type fitting without first consult ing the Technical...

Page 3: ... space around the Sprinkler Casing Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb With the sprinkler held horizontally a small air bubble should be present The diameter of the air bubble is approximately 1 16 inch 1 6 mm for the 135 F 57 C rating to 1 8 inch 3 2 mm for the 286 F 141 C rating A leak tight 1 inch NPT sprinkler joint should be...

Page 4: ...2 inch 12 7 mm Recessed Order Length Fig 3 plus 1 4 inch 6 3 mm Extended Order Length Fig 4 plus 3 1 4 inch 82 6 mm FIGURE 2 SERIES DS 2 TY5238 ECLH ECOH DRY PENDENT w FLUSH ESCUTCHEON FIGURE 3 SERIES DS 2 TY5238 ECLH ECOH DRY PENDENT w RECESSED ESCUTCHEON 9 16 14 3 mm NOMINAL MAKE IN 1 NPT REFER TO DESIGN SPRINKLER FITTING FACE OF FITTING SPRINKLER CRITERIA SECTION FACE OF CEILING 2 1 4 1 8 57 2 ...

Page 5: ... The owner is responsible for the in spection testing and maintenance of their fire protection system and de vices in compliance with this docu ment as well as with the applicable standards of the National Fire Protec tion Association e g NFPA 25 in addition to the standards of any other authorities having jurisdiction The in stalling contractor or sprinkler manu facturer should be contacted relat...

Page 6: ...rder Length as measured per Figures 3 through 5 as applicable After the meas urement is taken round it to the nearest 1 4 inch increment Temperature Rating Sprinkler Finish Escutcheon Style and Finish as applicable 1 inch NPT or ISO 7 R1 Part Number from Table D 1 inch NPT Connection 2 W Type 17 Sprinkler Wrench P N 56 010 4 118 Refer to the Price List for complete listing of Part Numbers Page 6 o...

Reviews: