background image

defective shall be either repaired or
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.

IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED   AN   AMOUNT
EQUAL TO THE SALES PRICE.

THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.

Ordering
Procedure

Contact your local distributor for avail-
ability, and please specify the follow-
ing:

1. Sprinkler.

Model/SIN.

ECLH/ECOH, Dry Pendent

Sprinkler

11.2 K-factor.

Order Length.

Dry Type Sprinklers are furnished
based upon Order Length as

measured per Figures 3 through
5, as applicable. After the meas-
urement is taken, round it to the
nearest 1/4 inch increment.

Temperature Rating.

Sprinkler Finish.

Escutcheon Style and Finish, as
applicable.

1 inch NPT or ISO 7-R1.

Part Number from Table D (1 inch
NPT Connection).

2. W-Type 17 Sprinkler Wrench,
P/N 56-010-4-118.

Refer to the Price List for complete
listing of Part Numbers.

Page 6 of 6

TFP540

TYCO FIRE PRODUCTS

, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446

P/N 61 — XXX — X — XXX

48.00"

8.25"

480

082

ORDER

LENGTH (1)

(EXAMPLES)

5.50"

055

1

SPRINKLER

FINISH

TABLE D

PART NUMBER SELECTION

SERIES DS-2, ECLH/ECOH, DRY TYPE SPRINKLERS

WITH 1 INCH NPT CONNECTION

18.00"

372

18.75"

187

37.25"

180

WHITE POLYESTER

NATURAL BRASS

9

4

MODEL/SIN

CHROME PLATED

0

CHROME PLATED

40

Pendent

w/

Flush Escutcheon

TY5238

(Fig. 3)

Pendent

w/

Recessed Escutcheon

Pendent

w/

Extended Escutcheon

WHITE

WHITE

CHROME PLATED

WHITE

ESCUTCHEON

FINISH

TEMPERATURE

RATING (2)

0

135F/57C

1

155F/68C

2

175F/79C

3

200F/93C

4

286F/141C

TY5238

(Fig. 4)

TY5238

(Fig. 5)

41

42

NOTES

(1). Dry Type Sprinklers are furnished based upon “Order
Length” as measured per Figures 3 through 5, as applicable,
and for each individual sprinkler where it is to be installed. Af-
ter the measurement is taken, round it to the nearest 1/4
inch increment.

(2). 286F/141C temperature rating applies to
non-recessed sprinkler assemblies.

5

NATURAL BRASS

BRASS PLATED

OBSOLETE

Summary of Contents for DS-2 Series

Page 1: ...at meet the requirements of the Design Criteria section Model Sprinkler Identification Numbers TY5238 Technical Data Approvals UL and C UL Listed Refer to Table A Maximum Working Pressure 175 psi 12 1 bar Inlet Thread Connection 1 inch NPT Standard Order ISO 7 R1 Discharge Coefficient Refer to Table C Temperature Ratings Refer to Table A Finishes Sprinkler Natural Brass Chrome Plated White Polyest...

Page 2: ...1 inch NPT Series DS 2 Dry Type Sprinklers on a dry pipe sprinkler system only use the side out let of maximum 2 1 2 inch size reduc ing tee s For wet pipe sprinkler systems the Series DS 2 Dry Type Sprinklers may also be installed in the 1 inch NPT outlet of a Central Figure 730 Mechani cal Tee NOTE Do not install the Series DS 2 into any other type fitting without first consult ing the Technical...

Page 3: ... space around the Sprinkler Casing Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb With the sprinkler held horizontally a small air bubble should be present The diameter of the air bubble is approximately 1 16 inch 1 6 mm for the 135 F 57 C rating to 1 8 inch 3 2 mm for the 286 F 141 C rating A leak tight 1 inch NPT sprinkler joint should be...

Page 4: ...2 inch 12 7 mm Recessed Order Length Fig 3 plus 1 4 inch 6 3 mm Extended Order Length Fig 4 plus 3 1 4 inch 82 6 mm FIGURE 2 SERIES DS 2 TY5238 ECLH ECOH DRY PENDENT w FLUSH ESCUTCHEON FIGURE 3 SERIES DS 2 TY5238 ECLH ECOH DRY PENDENT w RECESSED ESCUTCHEON 9 16 14 3 mm NOMINAL MAKE IN 1 NPT REFER TO DESIGN SPRINKLER FITTING FACE OF FITTING SPRINKLER CRITERIA SECTION FACE OF CEILING 2 1 4 1 8 57 2 ...

Page 5: ... The owner is responsible for the in spection testing and maintenance of their fire protection system and de vices in compliance with this docu ment as well as with the applicable standards of the National Fire Protec tion Association e g NFPA 25 in addition to the standards of any other authorities having jurisdiction The in stalling contractor or sprinkler manu facturer should be contacted relat...

Page 6: ...rder Length as measured per Figures 3 through 5 as applicable After the meas urement is taken round it to the nearest 1 4 inch increment Temperature Rating Sprinkler Finish Escutcheon Style and Finish as applicable 1 inch NPT or ISO 7 R1 Part Number from Table D 1 inch NPT Connection 2 W Type 17 Sprinkler Wrench P N 56 010 4 118 Refer to the Price List for complete listing of Part Numbers Page 6 o...

Reviews: