Operation

When the Series DS-2 is in service,
water is prevented from entering the
assembly by the Plug with Sealing As-
sembly (Ref. Figure 1) in the Inlet of the
Sprinkler. The glass Bulb contains a
fluid that expands when exposed to
heat. When the rated temperature is
reached, the fluid expands sufficiently

to shatter the glass Bulb, and the Bulb
Seat is released. The compressed
Spring is then able to expand and push
the Water Tube as well as the Guide
Tube outward. This action simultane-
ously pulls inward on the Yoke, with-
drawing the Plug with Sealing Assem-
bly from the Inlet allowing the sprinkler
to activate and flow water.

Design
Criteria

The Series DS-2, ECLH/ECOH, Sprin-
klers are intended for use in fire sprin-
kler systems designed in accordance
with the extended coverage installa-
tion rules recognized by the applicable
Listing agency (e.g., UL Listing is
based on NFPA 13 requirements). Re-
fer to Table B for coverage and flow
rate criteria.

The Series DS-2 Dry Type Sprinkler is
to be installed in the 1 inch NPT outlet
or run of malleable or ductile iron
threaded tee fittings that meet the di-
mensional requirements of ANSI
B16.3 or cast iron threaded tee fittings
that meet the dimensional require-
ments of ANSI B16.4 with the end
sprinkler fitting on a branch line to be
plugged as shown in Figure 3, 4, or 5.

When

installing 1 inch NPT Series

DS-2 Dry Type Sprinklers on a dry pipe
sprinkler system, only use the side out-
let of maximum 2-1/2 inch size reduc-
ing tee’s.

For wet pipe sprinkler systems, the
Series DS-2 Dry Type Sprinklers may
also be installed in the 1 inch NPT
outlet of a Central Figure 730 Mechani-
cal Tee.

NOTE

Do not install the Series DS-2 into any
other type fitting without first consult-
ing the Technical Services Depart-
ment. Failure to use the appropriate
fitting may result in: failure of the sprin-
kler to properly operate due to forma-

Page 2 of 6

TFP540

FIGURE 1

SERIES DS-2 ECLH/ECOH

DRY PENDENT SPRINKLER ASSEMBLY

SPRINKLER FINISH

Temperature

Rating

Bulb

Color Code

Natural

Brass

Chrome

Plated

135°F/57°C

155°F/68°C

175°F/79°C

Red

Yellow

Orange

TY5238

w/ Recessed Escutcheon

(Ref. Fig. 3)

TY5238

w/ Flush Escutcheon

(Ref. Fig. 2)

1, 2

Notes:

1. Listed by Underwriters Laboratories, Inc. per Table C and with order lengths per Figures 2, 3, and 4.
2. Listed by Underwriters Laboratories for use in Canada per Table C and with order lengths per Figures 2, 3, and 4.
N/A - Not Available.

TABLE A

SERIES DS-2, ECLH/ECOH, DRY TYPE SPRINKLERS

LABORATORY LISTINGS AND APPROVALS

Natural

Brass

Chrome

Plated

200°F/93°C

286°F/141°C

Green

Blue

TY5238

w/ Extended Escutcheon

(Ref. Fig. 4)

Natural

Brass

Chrome

Plated

N/A

White

Polyester

White

Polyester

White

Polyester

1, 2

1, 2

COMPRESSION

SCREW

VENT HOLE

FRAME

SPRING

HELPER

INSERT

GASKETED SPRING

PLATE SEAL

PLUG WITH

WATER

TUBE

SPRING

CASING

SEAT

BULB

DEFLECTOR

BULB

TUBE

GUIDE

BUTTON

SPRING

PIN

INLET

YOKE

OBSOLETE

Summary of Contents for DS-2 Series

Page 1: ...at meet the requirements of the Design Criteria section Model Sprinkler Identification Numbers TY5238 Technical Data Approvals UL and C UL Listed Refer to Table A Maximum Working Pressure 175 psi 12 1 bar Inlet Thread Connection 1 inch NPT Standard Order ISO 7 R1 Discharge Coefficient Refer to Table C Temperature Ratings Refer to Table A Finishes Sprinkler Natural Brass Chrome Plated White Polyest...

Page 2: ...1 inch NPT Series DS 2 Dry Type Sprinklers on a dry pipe sprinkler system only use the side out let of maximum 2 1 2 inch size reduc ing tee s For wet pipe sprinkler systems the Series DS 2 Dry Type Sprinklers may also be installed in the 1 inch NPT outlet of a Central Figure 730 Mechani cal Tee NOTE Do not install the Series DS 2 into any other type fitting without first consult ing the Technical...

Page 3: ... space around the Sprinkler Casing Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb With the sprinkler held horizontally a small air bubble should be present The diameter of the air bubble is approximately 1 16 inch 1 6 mm for the 135 F 57 C rating to 1 8 inch 3 2 mm for the 286 F 141 C rating A leak tight 1 inch NPT sprinkler joint should be...

Page 4: ...2 inch 12 7 mm Recessed Order Length Fig 3 plus 1 4 inch 6 3 mm Extended Order Length Fig 4 plus 3 1 4 inch 82 6 mm FIGURE 2 SERIES DS 2 TY5238 ECLH ECOH DRY PENDENT w FLUSH ESCUTCHEON FIGURE 3 SERIES DS 2 TY5238 ECLH ECOH DRY PENDENT w RECESSED ESCUTCHEON 9 16 14 3 mm NOMINAL MAKE IN 1 NPT REFER TO DESIGN SPRINKLER FITTING FACE OF FITTING SPRINKLER CRITERIA SECTION FACE OF CEILING 2 1 4 1 8 57 2 ...

Page 5: ... The owner is responsible for the in spection testing and maintenance of their fire protection system and de vices in compliance with this docu ment as well as with the applicable standards of the National Fire Protec tion Association e g NFPA 25 in addition to the standards of any other authorities having jurisdiction The in stalling contractor or sprinkler manu facturer should be contacted relat...

Page 6: ...rder Length as measured per Figures 3 through 5 as applicable After the meas urement is taken round it to the nearest 1 4 inch increment Temperature Rating Sprinkler Finish Escutcheon Style and Finish as applicable 1 inch NPT or ISO 7 R1 Part Number from Table D 1 inch NPT Connection 2 W Type 17 Sprinkler Wrench P N 56 010 4 118 Refer to the Price List for complete listing of Part Numbers Page 6 o...