Care and
Maintenance

The Series DS-2 Dry Type Sprinklers
must be maintained and serviced in
accordance with the following instruc-
tions:

NOTES

Absence of the outer piece of an es-
cutcheon, which is  used to cover a
clearance hole, may delay the time to
sprinkler operation in a fire situation.

Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection systems must
be obtained from the proper authori-
ties and all personnel who may be
affected by this action must be notified.

A Vent Hole is provided in the Bulb
Seat (Ref. Figure 1) to indicate if the
Dry Sprinkler is remaining dry. Evi-
dence of leakage from the Vent Hole is
an indication that there may be
weepage past the Inlet seal and that
the sprinkler needs to be removed for
determining the cause of leakage (e.g.
an improper installation or an ice plug).
The fire protection system control
valve must be closed and the system

drained before removing the sprinkler.

Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.

Automatic sprinklers must  never be
shipped or stored where their tem-
perature will exceed 100°F/38°C and
they must never  be painted, plated,
coated, or otherwise altered after leav-
ing the factory. Modified sprinklers
must be replaced. Sprinklers that have
been exposed to corrosive products of
combustion, but have not operated,
should be completely cleaned by wip-
ing the sprinkler with a cloth or by
brushing it with a soft bristle brush.

Care must be exercised to avoid dam-
age - before, during, and after instal-
lation. Sprinklers  damaged  by drop-
ping, striking, wrench twist/slippage,
or the  like,  must  be replaced. Also,
replace any sprinkler that has a
cracked bulb or that has lost liquid from
its bulb (Ref. Installation Section).

The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25),  in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.

It is recommended that automatic
spr inkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.

Limited
Warranty

Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty

is

given

for

products

or

components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be

TFP540

Page 5 of 6

FIGURE 4

SERIES DS-2 (TY5238) ECLH/ECOH DRY PENDENT

w/ EXTENDED ESCUTCHEON

ADJUSTMENT

WILL PERMIT

ESCUTCHEON

±1-3/8" (34,9 mm)

ADJUSTMENT

WILL PERMIT

ESCUTCHEON

±5/8" (15,9 mm)

9/16"

(14,3 mm)

NOMINAL

MAKE-IN:

1" NPT,

FACE OF

FITTING

SPRINKLER

FACE OF

CEILING

(REFER TO DESIGN

SPRINKLER FITTING

CRITERIA SECTION)

4-13/16±1/8" (122,2±3,2 mm)

4-1/16±1/8" (103,2±3,2 mm)

FOR ORDER LENGTHS

< 3-1/4" (82,6 mm):

> 3-1/4" (82,6 mm):

FOR ORDER LENGTHS

-or-

2-3/4" DIA.

(69,9 mm)

*

**

(92,1 mm)

3-5/8" DIA.

*

**

ORDER LENGTHS:

INCREMENTS

IN 1/4" (6,4 mm)

(0,0 to 1149,4 mm)

0" to 45-1/4"

FIGURE 5

W-TYPE 17 SPRINKLER WRENCH

RECESS

WRENCH

WITH SPRINKLER

ENGAGEMENT

IN TO ENSURE

WRENCHING AREA

PUSH WRENCH

AREA

WRENCHING

SPRINKLER

OBSOLETE

Summary of Contents for DS-2 Series

Page 1: ...at meet the requirements of the Design Criteria section Model Sprinkler Identification Numbers TY5238 Technical Data Approvals UL and C UL Listed Refer to Table A Maximum Working Pressure 175 psi 12 1 bar Inlet Thread Connection 1 inch NPT Standard Order ISO 7 R1 Discharge Coefficient Refer to Table C Temperature Ratings Refer to Table A Finishes Sprinkler Natural Brass Chrome Plated White Polyest...

Page 2: ...1 inch NPT Series DS 2 Dry Type Sprinklers on a dry pipe sprinkler system only use the side out let of maximum 2 1 2 inch size reduc ing tee s For wet pipe sprinkler systems the Series DS 2 Dry Type Sprinklers may also be installed in the 1 inch NPT outlet of a Central Figure 730 Mechani cal Tee NOTE Do not install the Series DS 2 into any other type fitting without first consult ing the Technical...

Page 3: ... space around the Sprinkler Casing Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb With the sprinkler held horizontally a small air bubble should be present The diameter of the air bubble is approximately 1 16 inch 1 6 mm for the 135 F 57 C rating to 1 8 inch 3 2 mm for the 286 F 141 C rating A leak tight 1 inch NPT sprinkler joint should be...

Page 4: ...2 inch 12 7 mm Recessed Order Length Fig 3 plus 1 4 inch 6 3 mm Extended Order Length Fig 4 plus 3 1 4 inch 82 6 mm FIGURE 2 SERIES DS 2 TY5238 ECLH ECOH DRY PENDENT w FLUSH ESCUTCHEON FIGURE 3 SERIES DS 2 TY5238 ECLH ECOH DRY PENDENT w RECESSED ESCUTCHEON 9 16 14 3 mm NOMINAL MAKE IN 1 NPT REFER TO DESIGN SPRINKLER FITTING FACE OF FITTING SPRINKLER CRITERIA SECTION FACE OF CEILING 2 1 4 1 8 57 2 ...

Page 5: ... The owner is responsible for the in spection testing and maintenance of their fire protection system and de vices in compliance with this docu ment as well as with the applicable standards of the National Fire Protec tion Association e g NFPA 25 in addition to the standards of any other authorities having jurisdiction The in stalling contractor or sprinkler manu facturer should be contacted relat...

Page 6: ...rder Length as measured per Figures 3 through 5 as applicable After the meas urement is taken round it to the nearest 1 4 inch increment Temperature Rating Sprinkler Finish Escutcheon Style and Finish as applicable 1 inch NPT or ISO 7 R1 Part Number from Table D 1 inch NPT Connection 2 W Type 17 Sprinkler Wrench P N 56 010 4 118 Refer to the Price List for complete listing of Part Numbers Page 6 o...

Reviews: