background image

Installation

The Central Model LF Residential
Pendent Sprinklers must be installed in
accordance with the following instruc-
tions:

NOTES

Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble with
an approximate diameter of 1/16 inch
should be present.

A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7 to
14 ft.lbs. (9,5 to 19,0 Nm). A maximum of
21 ft.lbs. (28,5 Nm) of torque is to be
used to install 1/2 inch NPT sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leakage
or impairment of the sprinkler.

Step 1. The sprinkler must only be
installed in the pendent position and with
the deflector parallel to the mounting
surface.

Step 2. After installing the BV Res./QR
Recessed Support Cup (or other
acceptable escutcheon, as applicable)
over the sprinkler pipe threads and with
pipe thread sealant applied to the pipe
threads, hand tighten the sprinkler into
the sprinkler fitting.

Step 3. Wrench tighten the sprinkler
using only a LF Sprinkler Wrench (1025 -
Ref. Figure 3). The wrench recess of the
LF Sprinkler Wrench is to be applied to
the sprinkler wrench flats (Ref Figure 1).

Step 4. For Recessed Pendent Sprinkler
Applications, a  Protective Cap is
available which helps to prevent damage
to the sprinkler during ceiling installation
and/or during application of the finish
coating of the ceiling.  Place the Protec-
tive Cap over the Recessed Support Cup

and push it upwards until it bottoms out
against the sprinkler deflector.

NOTE

As long as the Protective Cap remains in
place, the system is considered to be
"Out  of Service"

Step 5. After the ceiling has been
completed , remove and discard the
Protective Cap. If the Sprinkler has been
damaged, replace the entire Sprinkler
assembly. Do not attempt to modify or
repair a damaged sprinkler.

Step 6. Push the outer ring of the
Recessed Escutcheon  over the Re-
cessed Support Cup.  Do not continue to
push on the Recessed Escutcheon such
that it lifts a ceiling panel out of its normal
position.  If the Recessed Escutcheon
cannot be engaged with the Support Cup
or the Recessed Escutcheon cannot be
engaged sufficiently to contact the
ceiling, the Sprinkler Fitting must be
repositioned.

A — NFPA minimum of 4", maximum 1/2 of the Listed

spacing that the sprinkler was calculated for.

D — Distance to opposing sloped ceiling.

F & G — Acceptable for angles 0

°

 to 60

°

.

Figure  14 - Obstruction to Discharge by Intersecting Flat Ceiling

If “D” is “Obstructed” per Figure 14 Graph, then “D” is to be
considered the area of coverage and additional sprinklers
along the horizontal ceiling will be necessary.  Only if “D” is
“Acceptable” can “A” be considered 1/2 of the maximum
Listed spacing that the sprinkler was calculated for.  Dimen-
sion “A” is measured along the slope.

A — Maximum 1/2 of the Listed spacing that the sprinkler

was calculated for.

D — Distance to intersecting horizontal ceiling.

F — Acceptable for angles 0

°

 to 60

°

.

Figure  15 - Obstruction to Discharge by an Opposing Sloped Ceiling

If “D” is “Obstructed” per Figure 15 Graph, then the
horizontal distance to the opposing slope is the extent of
coverage and additional sprinklers will be necessary to
protect the remainder of the opposing slope.  Only if “D” is
“Acceptable” can “A” equal 1/2 of the maximum Listed
spacing that the sprinkler was calculated for.  Dimension “A”
is measured along the slope.

D

F

A

0

°

     4

°

     8

°

     12

°

   16

°

    20

°

    24

°

    28

°

    32

°

   36

°

   40

°

  44

°

   48

°

   52

°

   56

°

   60

°

10'

9'

8'

6'

5'

4'

3'

2'

1'

7'

"D"

(in feet)

"F"

(in degrees)

Obstructed

Acceptable

20' x 20'

18' x 18'

16' x 16'

14' x 14'

12' x 12'

A

D

A

G

F

5'

4'

3'

2'

1'

"D"

(in feet)

"F" or "G" 

(whichever is greater)

(in degrees)

Obstructed

10

°

   15

°

   20

°

    25

°

    30

°

    35

°

    40

°

   45

°

Acceptable

20' x 20'

18' x 18'

16' x 16'

14' x 14'

12' x 12'

OBSOLETE

Summary of Contents for CENTRAL LF

Page 1: ...They are to be used in wet pipe residential sprinkler systems for one and two family dwellings and mobile homes per NFPA 13D wet pipe residential sprinkler systems for residential occupancies up to an...

Page 2: ...18 8 psi 5 5 x 5 5m 53 0 lpm 1 50 bar 49 2 lpm 1 30 bar 20 x 20 16 GPM 28 4 psi 16 GPM 28 4 psi 6 1 x 6 1m 60 6 lpm 1 96 bar 60 6 lpm 1 96 bar Minimum Design Flow Coverage Multiple Area Single Sprinkl...

Page 3: ...kler system piping to the structure If the sprinkler is Figure 1 Model LF Pendent Figure 2 Model LF Recessed Pendent 1 3 16 30 2 mm Diameter 2 1 8 54 0 mm Reducing upling 11 16 9 mm Ref WRENCH FLAT 1...

Page 4: ...A minimum of 4 verify G dimension minimum of 4 maximum 1 2 of the Listed spacing that the sprinkler was calculated for i e 18 x 18 spacing is maximum of 9 0 from a wall B For angles 0 to 39 minimum B...

Page 5: ...e minimum distance between sprinklers is measured horizon tally shown as dimension E Staggering the sprinklers will help maintain minimum horizontal distances in difficult situations Dimensions A and...

Page 6: ...secting a Flat Ceiling First verify that D is Acceptable or Obstructed per Figure 14 If Acceptable Figure 12 applies If Ob structed additional sprinklers will be necessary to protect the flat ceiling...

Page 7: ...f the Sprinkler has been damaged replace the entire Sprinkler assembly Do not attempt to modify or repair a damaged sprinkler Step 6 Push the outer ring of the Recessed Escutcheon over the Re cessed S...

Page 8: ...ang anything from the sprinklers Do NOT cleanse the sprinklers with soap and water detergents ammo nia cleaning fluids or other chemi cals Remove dust lint cobwebs cocoons insects and larvae by gently...

Reviews: