background image

First verify that the sprinkler at the peak is considered to be
“Acceptable” or “Obstructed” by the sloped ceiling in accordance
with Figure 13 Graph.  Measure horizontally from the deflector to
the sloped ceiling, this is equal to the “D” dimension in the Figure
13 Graph.  If the “D” dimension is “Acceptable”, then Figure 8
applies.  If “D” is “Obstructed”, then the protection area of the
sprinkler at the peak will be the horizontal distance to the obstruct-
ing ceiling.  The minimum distance between sprinklers is mea-
sured horizontally.  Staggering sprinklers will help maintain
minimum horizontal distances in difficult situations.  Dimensions
“A” and “B” are measured along the slope.  For angles greater
than 60

°

, verify with Central's Technical Services Department.

A — NFPA minimum 4", maximum 1/2 of the Listed spacing that

the sprinkler was calculated for.

B — See “E” for minimum spacing.  Maximum Listed spacing that

the sprinkler was calculated for.

C — Maximum of 3'-0" vertically from the peak.

D — Horizontal distance from the deflector to the intersecting

sloped ceiling.

E — NFPA minimum of 8'-0" (when minimum of 8'-0" cannot be

obtained due to “B”, a baffle must be installed between
these sprinklers to obstruct the discharge and prevent cold-
solder).  See “B” for maximum.

F — Acceptable for angles 0

°

 to 60

°

.

Figure  8 - Spacing for Sprinkler at the Peak of a Sloped Ceiling

A

E

B

C

A

E

D

B

D

F

F

Figure 9 - Sprinkler Location on Opposing Slopes

First verify that the sprinkler nearest the peak is “Acceptable”
or “Obstructed” per Figure 15.  If “Acceptable”, Figure 9
applies.  If “Obstructed”, the horizontal distance to the
opposing slope is to be considered as the protected area. The
minimum distance between sprinklers is measured horizon-
tally, shown as dimension “E”.  Staggering the sprinklers will
help maintain minimum horizontal distances in difficult
situations.  Dimensions “A” and “B” are measured along the
slope.   For angles greater than 60

°

, verify with Central's

Technical Services Department.

A — NFPA minimum of 4", maximum 1/2 of the Listed spacing

that the sprinkler was calculated for.

B — See “E” for minimum spacing.  Maximum Listed spacing

that the sprinkler was calculated for.

C — Maximum of 3'-0" vertically from the peak.

D — Minimum 4".  Also, see note above.

E — NFPA minimum of 8'-0" (when minimum of 8'-0" cannot

be obtained due to “B”, a baffle must be installed
between these sprinklers to obstruct the discharge and
prevent cold-solder).  See “B” for maximum.

F — Acceptable for angles from 0

°

 to 60

°

.

A

A

D

C

F

E

B

Figure 10 - Sprinkler Location on Coffered Ceiling

First verify that “D” is “Acceptable” or “Obstructed” per Figure
14.  If “Acceptable”, Figure 10 applies.  If “Obstructed”,
additional sprinklers will be necessary to protect the flat ceiling
area.  The minimum distance between sprinklers is measured
horizontally.  Staggering sprinklers will help maintain minimum
horizontal distances in difficult situations.  Dimensions “A” and
“B” are measured along the slope.  For angles greater than
60

°

, verify with Central's Technical Services Department.

A — NFPA minimum of 4", maximum 1/2 of the Listed

spacing that the sprinkler was calculated for.

B — See “E” for minimum spacing.  Maximum Listed spacing

that the sprinkler was calculated for.

C — Maximum 3'-0" vertically from the peak.

D — Refer to Figure 14.

A

E

D

C

D

A

B

E — NFPA minimum of 8'-0" (when minimum of 8'-0" cannot

be obtained due to “B”, a baffle must be installed
between these sprinklers to obstruct the discharge and
prevent cold-solder).  See “B” for maximum.

F — Acceptable for angles 0

°

 to 60

°

.

OBSOLETE

Summary of Contents for CENTRAL LF

Page 1: ...They are to be used in wet pipe residential sprinkler systems for one and two family dwellings and mobile homes per NFPA 13D wet pipe residential sprinkler systems for residential occupancies up to an...

Page 2: ...18 8 psi 5 5 x 5 5m 53 0 lpm 1 50 bar 49 2 lpm 1 30 bar 20 x 20 16 GPM 28 4 psi 16 GPM 28 4 psi 6 1 x 6 1m 60 6 lpm 1 96 bar 60 6 lpm 1 96 bar Minimum Design Flow Coverage Multiple Area Single Sprinkl...

Page 3: ...kler system piping to the structure If the sprinkler is Figure 1 Model LF Pendent Figure 2 Model LF Recessed Pendent 1 3 16 30 2 mm Diameter 2 1 8 54 0 mm Reducing upling 11 16 9 mm Ref WRENCH FLAT 1...

Page 4: ...A minimum of 4 verify G dimension minimum of 4 maximum 1 2 of the Listed spacing that the sprinkler was calculated for i e 18 x 18 spacing is maximum of 9 0 from a wall B For angles 0 to 39 minimum B...

Page 5: ...e minimum distance between sprinklers is measured horizon tally shown as dimension E Staggering the sprinklers will help maintain minimum horizontal distances in difficult situations Dimensions A and...

Page 6: ...secting a Flat Ceiling First verify that D is Acceptable or Obstructed per Figure 14 If Acceptable Figure 12 applies If Ob structed additional sprinklers will be necessary to protect the flat ceiling...

Page 7: ...f the Sprinkler has been damaged replace the entire Sprinkler assembly Do not attempt to modify or repair a damaged sprinkler Step 6 Push the outer ring of the Recessed Escutcheon over the Re cessed S...

Page 8: ...ang anything from the sprinklers Do NOT cleanse the sprinklers with soap and water detergents ammo nia cleaning fluids or other chemi cals Remove dust lint cobwebs cocoons insects and larvae by gently...

Reviews: