Table 3 - 155

°

F & 175

°

F LF Extended Pendent

 Hydraulic Design Requirements for NFPA 13D &

NFPA 13R Occupancies (Use with Figure 3)

Design
Criteria

The Model LF Residential Pendent and Recessed Pendent
Sprinklers are UL, C-UL Listed and MEA Approved for use in
accordance with current NFPA standards on wet pipe sprinkler
systems.  These sprinklers with a maximum ceiling to top of
sprinkler deflector distance of 4 inches, have been investigated for
use under smooth flat horizontal ceilings with slopes up to 2
inches per foot using the hydraulic design requirements found in
Table 1 or Table 2 as applicable. These sprinklers with a
maximum ceiling to top of sprinkler deflector distance of 8 inches,
have been investigated for use under smooth flat horizontal
ceilings with slopes up to 2 inches per foot using the hydraulic
design requirements found in Table 3. These sprinklers with a
maximum ceiling to top of sprinkler deflector distance of 4 inches,
have also been investigated for use under smooth flat sloping
ceilings with slopes up to 8 inches per foot using the hydraulic
design requirements found in Table 4 as well as the sloped ceiling
"Specific Application Design Criteria" found in Figure 5. When
conditions exist that do not meet all the parameters of the "sloped
ceiling "Specific Application Design Criteria" found in Figure 5, and
when acceptable to the local authority, additional guidance on the

Table 4 - 155

°

F LF Pendent & Recessed Pendent

UL & C-UL Specific Application Sloped Ceiling

Hydraulic Design Requirements for NFPA 13D &

NFPA 13R Occupancies (For use with Figure 5)

           Minimum Design Flow

Coverage

Multiple

   Area

Single Sprinkler

Sprinklers

12' x 12'

10 GPM (11.1 psi)

8 GPM (7.1 psi)

(3,7 x 3,7m)

37,9 lpm (0,77 bar)

30,3 lpm (0,49 bar)

14' x 14'

12 GPM (16.0 psi)

8 GPM (7.1 psi)

(4,3 x 4,3m)

45,5 lpm (1,10 bar)

30,3 lpm (0,49 bar)

16' x 16'

12 GPM (16.0 psi)

11 GPM (13.4 psi)

(4,9 x 4,9m)

45,5 lpm (1,10 bar)

41,6 lpm (0,92 bar)

18' x 18'

18 GPM (36.0 psi)

13 GPM (18.8 psi)

(5,5 x 5,5m)

68,1 lpm (2,48 bar)

49,2 lpm (1,30 bar)

20' x 20'

20 GPM (44.4 psi)

16 GPM (28.4 psi)

(6,1 x 6,1m)

75,7 lpm (3,06 bar)

60,6 lpm (1,96 bar)

Table 1 - 155

°

F LF Pendent & Recessed Pendent

Hydraulic Design Requirements for NFPA 13D &

NFPA 13R Occupancies

Table 2 - 175

°

F LF Pendent & Recessed Pendent

Hydraulic Design Requirements for NFPA 13D &

NFPA 13R Occupancies

           Minimum Design Flow

Coverage

Multiple

   Area

Single Sprinkler

Sprinklers

12' x 12'

10 GPM (11.1 psi)

8 GPM (7.1 psi)

(3,7 x 3,7m)

37,9 lpm (0,77 bar)

30,3 lpm (0,49 bar)

14' x 14'

10 GPM (11.1 psi)

8 GPM (7.1 psi)

(4,3 x 4,3m)

37,9 lpm (0,77 bar)

30,3 lpm (0,49 bar)

16' x 16'

11 GPM (13.4 psi)

11 GPM (13.4 psi)

(4,9 x 4,9m)

41,6 lpm (0,92 bar)

41,6 lpm (0,92 bar)

18' x 18'

14 GPM (21.8 psi)

13 GPM (18.8 psi)

(5,5 x 5.5m)

53,0 lpm (1,50 bar)

49,2 lpm (1,30 bar)

20' x 20'

16 GPM (28.4 psi)

16 GPM (28.4 psi)

(6,1 x 6,1m)

60,6 lpm (1,96 bar)

60,6 lpm (1,96 bar)

           Minimum Design Flow

Coverage

Multiple

  Area

Single Sprinkler

Sprinklers

12' x 12'

10 GPM (11.1 psi)

8 GPM (7.1 psi)

(3,7 x 3,7m)

37,9 lpm (0,77 bar)

30,3 lpm (0,49 bar)

14' x 14'

12 GPM (16.0 psi)

8.5 GPM (8.0 psi)

(4,3 x 4,3m)

45,5 lpm (1,10 bar)

32,2 lpm (0,55 bar)

16' x 16'

12 GPM (16.0 psi)

11 GPM (13.4 psi)

(4,9 x 4,9m)

45,5 lpm (1,10 bar)

41,6 lpm (0,92 bar)

18' x 18'

15 GPM (25.0 psi)

13 GPM (18.8 psi)

(5,5 x 5,5m)

56,8 lpm (1,72 bar)

49,2 lpm (1,30 bar)

20' x 20'

16 GPM (28.4 psi)

16 GPM (28.4 psi)

(6,1 x 6,1m)

60,6 lpm (1,96 bar)

60,6 lpm (1,96 bar)

           Minimum Design Flow

Coverage

Multiple

   Area

Single Sprinkler

 Sprinklers

12' x 12'

11 GPM (13.4 psi)

8 GPM (7.1 psi)

(3,7 x 3,7m)

41,6 lpm (0,92 bar)

30,3 lpm (0,49 bar)

14' x 14'

12 GPM (16.0 psi)

9 GPM (9.0 psi)

(4,3 x 4,3m)

45,5 lpm (1,10 bar)

34,1 lpm (0,62 bar)

16' x 16'

14 GPM (21.8 psi)

11 GPM (13.4 psi)

(4,9 x 4,9m)

53,0 lpm (1,50 bar)

41,6 lpm (0,92 bar)

18' x 18'

14 GPM (21.8 psi)

13 GPM (18.8 psi)

(5,5 x 5,5m)

53,0 lpm (1.50 bar)

49,2 lpm (1,30 bar)

20' x 20'

16 GPM (28.4 psi)

16 GPM (28.4 psi)

(6,1 x 6,1m)

60,6 lpm (1,96 bar)

60,6 lpm (1,96 bar)

Maximum Ceiling to top of Sprinkler Deflector 4 inches.

Maximum Ceiling to top of Sprinkler Deflector 8 inches.

Maximum Ceiling to top of Sprinkler Deflector 4 inches.

Maximum Ceiling to top of Sprinkler Deflector 4 inches.

placement of residential sprinklers on sloped ceilings has been
provided in Figures 6 -15.  This information will provide the
minimum spacing requirements necessary for preventing the
wetting (i.e., cold soldering) of the heat responsive element (Bulb)
of a non-operated Central Model LF, which is adjacent to one,
which has operated.  In these situations the minimum required
single and multiple sprinkler flow rates given in Table 1, Table 2, or
Table 3 as applicable, should be used.  Your local authority should
be consulted to determine the number of sprinklers required in the
hydraulic design area.

The Recessed Pendent Sprinklers are only listed with the Series
BV Res./QR Recessed Escutcheon Assembly.  These sprinklers
can be used with any metalic flush or extended escutcheon,
provided the maximum ceiling to top of sprinkler deflector
dimension specified in Table 1, Table 2, Table 3, or Table 4 is
maintained.

The minimum required single and multiple sprinkler flow rates for
systems designed to NFPA 13D or NFPA 13R occupancies are
given in Table 1, Table 2, Table 3, or Table 4 as a function of
temperature rating, ceiling to top of deflector distance, and the
maximum allowable coverage areas. The single sprinkler flow rate
is the minimum required discharge from the most hydraulically
demanding single sprinkler and, the multiple sprinkler flow rate is
the minimum required discharge from each of the total number of
"design sprinklers" as specified in NFPA 13D or NFPA 13R.

OBSOLETE

Summary of Contents for CENTRAL LF

Page 1: ...They are to be used in wet pipe residential sprinkler systems for one and two family dwellings and mobile homes per NFPA 13D wet pipe residential sprinkler systems for residential occupancies up to an...

Page 2: ...18 8 psi 5 5 x 5 5m 53 0 lpm 1 50 bar 49 2 lpm 1 30 bar 20 x 20 16 GPM 28 4 psi 16 GPM 28 4 psi 6 1 x 6 1m 60 6 lpm 1 96 bar 60 6 lpm 1 96 bar Minimum Design Flow Coverage Multiple Area Single Sprinkl...

Page 3: ...kler system piping to the structure If the sprinkler is Figure 1 Model LF Pendent Figure 2 Model LF Recessed Pendent 1 3 16 30 2 mm Diameter 2 1 8 54 0 mm Reducing upling 11 16 9 mm Ref WRENCH FLAT 1...

Page 4: ...A minimum of 4 verify G dimension minimum of 4 maximum 1 2 of the Listed spacing that the sprinkler was calculated for i e 18 x 18 spacing is maximum of 9 0 from a wall B For angles 0 to 39 minimum B...

Page 5: ...e minimum distance between sprinklers is measured horizon tally shown as dimension E Staggering the sprinklers will help maintain minimum horizontal distances in difficult situations Dimensions A and...

Page 6: ...secting a Flat Ceiling First verify that D is Acceptable or Obstructed per Figure 14 If Acceptable Figure 12 applies If Ob structed additional sprinklers will be necessary to protect the flat ceiling...

Page 7: ...f the Sprinkler has been damaged replace the entire Sprinkler assembly Do not attempt to modify or repair a damaged sprinkler Step 6 Push the outer ring of the Recessed Escutcheon over the Re cessed S...

Page 8: ...ang anything from the sprinklers Do NOT cleanse the sprinklers with soap and water detergents ammo nia cleaning fluids or other chemi cals Remove dust lint cobwebs cocoons insects and larvae by gently...

Reviews: