Pendents Located Along Multiple Slopes

• Spacing is measured along the slope.

• One row of sprinklers is shown on the sloping ceiling for

clarity. Actual number of sprinklers within a compartment  is
unlimited.

• Cathedral ceiling applications:  An 8" minimum beam or

lintel is required at the peak.

• If a loft adjoins the sloped ceiling compartment, a

minimum 8" deep lintel is required between the loft and
the ceiling.

• Hydraulic calculations shall conform to the appropriate

NFPA standard.  Calculate the two (NFPA 13D) or four
(NFPA 13R) most demanding sprinklers along one slope.
If there are less than two (NFPA 13D) or four (NFPA 13R)
sprinklers along one slope, calculate all the sprinklers
along one slope.  For ceilings with adjoining lofts, add one
sprinkler in the loft to the hydraulic calculations.

• Openings in the perimeter walls, such as a doorway or

adjoining hallway, must maintain a maximum height of 8 feet
or less.

Figure  5 - UL & C-UL Specific Application Sloped Ceiling Design Criteria

a

a

b

b

D = MAXIMUM SLOPE

8:12 (33.7

O

)

D

a

a

Figure  6 - Sprinkler Location for Sloped Ceiling

Note the minimum distance between sprinklers changes by
the angle of the slope.  Verify the Listed flows and pressures
for “maximum” and “1/2  maximum” distances.   Dimensions
“A” and “B” are measured along the slope.  For angles
greater than 60

°

, verify with Central's Technical Services

Department.

A — NFPA minimum of 4" (verify “G” dimension minimum of

4"), maximum 1/2 of the Listed spacing that the sprinkler
was calculated for.  (i.e., 18' x 18' spacing is maximum of
9'-0" from a wall).

B — For angles 0

°

 to 39

°

 minimum B = 8'-0".

For angles 40

°

 to 45

°

 minimum B = 9'-0".

For angles 46

°

 to 60

°

 minimum B = 9'-6".

Maximum Listed spacing that the sprinkler was calcu-
lated for.

C — Maximum of 3'-0" vertically from the peak.

F — Acceptable for angles 0

°

 to 60

°

.

G — Minimum of 4", for maximum, refer to “A” and measure

along slope.

B

G

A

A

G

C

• a: minimum:

4"

maximum: one-half the maximum calculated

spacing

• b: minimum:

8'-0"

maximum:    20'-0"

• The minimum lateral distance between sprinklers on
    opposing slopes is 8'-0"

Figure  7 -  Symmetric Sprinkler Location on Opposing Slopes*

The minimum distance between sprinklers on opposing slopes
is measured horizontally, some difficult conditions can be
solved by staggering the sprinklers, thus increasing the
horizontal distance.  Remember to measure along the slope
for “A” and “B”.  For angles greater than 60

°

, verify with

Central's Technical Services Department.

A — NFPA minimum of 4", maximum 1/2 of the Listed spacing

that the sprinkler was calculated for.

B — See “E” for minimum spacing.  Maximum Listed spacing

that the sprinkler was calculated for.

 — Maximum 3'-0" vertically from the peak.

E — NFPA minimum of 8'-0" (when minimum of 8'-0" cannot

be obtained due to   “B”, a baffle must be installed
between these sprinklers to obstruct the     discharge
and prevent cold-solder).  See “B” for maximum.

F — Acceptable for angles 0

°

 to 60

°

.

*  For unequal spacing down from peak, see Figure 9.

A

A

A

A

E

C

B

F

F

OBSOLETE

Summary of Contents for CENTRAL LF

Page 1: ...They are to be used in wet pipe residential sprinkler systems for one and two family dwellings and mobile homes per NFPA 13D wet pipe residential sprinkler systems for residential occupancies up to an...

Page 2: ...18 8 psi 5 5 x 5 5m 53 0 lpm 1 50 bar 49 2 lpm 1 30 bar 20 x 20 16 GPM 28 4 psi 16 GPM 28 4 psi 6 1 x 6 1m 60 6 lpm 1 96 bar 60 6 lpm 1 96 bar Minimum Design Flow Coverage Multiple Area Single Sprinkl...

Page 3: ...kler system piping to the structure If the sprinkler is Figure 1 Model LF Pendent Figure 2 Model LF Recessed Pendent 1 3 16 30 2 mm Diameter 2 1 8 54 0 mm Reducing upling 11 16 9 mm Ref WRENCH FLAT 1...

Page 4: ...A minimum of 4 verify G dimension minimum of 4 maximum 1 2 of the Listed spacing that the sprinkler was calculated for i e 18 x 18 spacing is maximum of 9 0 from a wall B For angles 0 to 39 minimum B...

Page 5: ...e minimum distance between sprinklers is measured horizon tally shown as dimension E Staggering the sprinklers will help maintain minimum horizontal distances in difficult situations Dimensions A and...

Page 6: ...secting a Flat Ceiling First verify that D is Acceptable or Obstructed per Figure 14 If Acceptable Figure 12 applies If Ob structed additional sprinklers will be necessary to protect the flat ceiling...

Page 7: ...f the Sprinkler has been damaged replace the entire Sprinkler assembly Do not attempt to modify or repair a damaged sprinkler Step 6 Push the outer ring of the Recessed Escutcheon over the Re cessed S...

Page 8: ...ang anything from the sprinklers Do NOT cleanse the sprinklers with soap and water detergents ammo nia cleaning fluids or other chemi cals Remove dust lint cobwebs cocoons insects and larvae by gently...

Reviews: