Indications,
functions and options
Messages
Commissioning
Operation and function
Lightwheel
®
flashes red.
Sensor fault. An error code instead of a temperature is
shown on the sensor display channel.
°C
Ω
Pt1000
°C
Ω
Pt1000
-10
961
55
1213
-5
980
60
1232
0
1000
65
1252
5
1019
70
1271
10
1039
75
1290
15
1058
80
1309
20
1078
85
1328
25
1097
90
1347
30
1117
95
1366
35
1136
100
1385
40
1155
105
1404
45
1175
110
1423
50
1194
115
1442
Short circuit or line break.
Disconnected temperature sensors can be checked
with an ohmmeter. Please check if the resistance values
correspond with the table.
Wago 2091-1130
Etikett
RE
F1
RE
F2
1
2 3
4
5
6
7
8
9
10
Wago 2091-1130
Etiketttt
R
E
F2
1
2 3
4
5
6
7
8
9
10
R
E
F1
F5 A
T16 A
Power unit
The power unit is protected by a fuse (T16 A). The fuse holder becomes accessible
when the cover is removed. To replace the fuse, unfasten the fuse holder using a
screw driver and pull it from the base.
The modulating power stage is protected by a fuse (F5 A) in the power unit. The
fuse holder becomes accessible when the cover is removed. To replace the fuse,
unfasten the fuse holder using a screw driver and pull it from the base.
The thermal cut-out is located on the upper part of the power unit. In order to
unlock the thermal cut-out, remove the protective cap and push the button of the
thermal cut-out.
STB
tubra
®
-eTherm power
Made in Germany
T16A 250V~
PE
L
N
Out1_N
Out2_N
Out2_L
Out1_L
Out3_L
Out3_N
DE-33659 Bielefeld
10
9
8
7
6
5
4
3
2
1
VBus
VBus
PE
L'
N
Regle
r
Contr
oller
Netz
Main
s
800W
800
W
1400
W
800W
800
W
1400
W
F5A 250V~
Protective cap of
thermal cut-out