S0 Excess
Opt. functions / Add new function / S0 Excess
Adjustment channel
Description
Adjustment range / se-
lection
Factory setting
Duration
Impulse duration
30 … 120 ms
100 ms
Break
Impulse break
30 … 120 ms
30 ms
Impulses/kWh
Impulse rate
1 … 1000
100
Funct.
Activation / Deactivation Activated, Deactivated Activated
Save function / Delete
function
Save / Delete function
-
-
The S0 Excess function is used for activating the digital impulse output S0-2 of the
measuring unit, in order to issue the balanced excess energy in the form of impulses.
The impulse duration, break and rate can be adjusted.
Note:
This function is only available, if the variant Module has been selected in
the Measuring unit menu.
S0 Heating
Opt. functions / Add new function / S0 Heating
Adjustment channel
Description
Adjustment range / se-
lection
Factory setting
Duration
Impulse duration
30 … 120 ms
100 ms
Break
Impulse break
30 … 120 ms
30 ms
Impulses/kWh
Impulse rate
1 … 1000
100
Funct.
Activation / Deactivation Activated, Deactivated Activated
Save function / Delete
function
Save / Delete function
-
-
The S0 Heating function is used for activating the digital impulse output S0-1
of the measuring unit, in order to issue the balanced heat energy in the form of
impulses.
The impulse duration, break and rate can be adjusted.
Note:
This function is only available, if the variant Module has been selected in
the Measuring unit menu.