Code 

Meaning 

Range 

T  Description 

See also the acquisition procedure described in the ‘Maintenance’ section. 

BTE 

BlueTooth 
Enabling 

NO, YES 


BLUETOOTH

TM

  Enabling

.  

NO the 

BLUETOOTH

TM

  interface is disabled. 

YES the 

BLUETOOTH

TM

  interface is enabled: the detector can communicate with a 

PC equipped with a compatible interface. 

CH 

Transmission  
channel 

 0 - 99 


Transmission channel.

 

Select a proper channel to synchronize a multiple installation or to 

reject environmental electrical interference. 

0 - 49   for 50Hz power supply. 
50 - 99   for 60Hz power supply. 

CR 

Alarm counter 
reset 

-

Equipment fitted with photocells only.
Alarm counter reset. This command requests confirmation. 
NOTE: there are two counters, one at operator level and one at supervisor level: only the 
counter at the current level of programming is reset. 

EN 

Environmental 
electromagneti
c noise 
measurement 

NO, YES 

C  Displays the value of the electromagnetic environmental noise. 

This function is activated by pressing the ENTER key: the numeric values will then appear 
on the right, from 0 to 99, continually updated.  To end measurement, press any key. 

NOTE: if both GN and EN functions are activated, function EN has priority. 
NOTE: the function is terminated automatically after 2 minutes. 

EVA 

Environmental
vibration 
acquisition 

C  It activates the procedure for acquiring the environmental mechanical vibrations; this 

procedure is described in detail in the ‘Maintenance’ section. 

See also the  AVS parameter. 

HE 

HELP

-

Function  available in remote mode only. 
This selects a display of the meaning of the available programming functions. The read-out 
will give the correspondence table (function – function code). 
The   *   character indicates that the command is enabled at user level (see the UP 
command). 

IP 

IP Address 

xxx.xxx.xxx.xxx 

R  Command available only if a network adapter APSIM is installed. 

Read only function. Current IP address of the WTMD. It is displayed in two steps.  
Ex.: IP address 192.168.0.101: 

IP  
I192.168
 

.0.101

 

IS 

International 
Security 
Standard  

1-30


Selects a security level corresponding to an international standard.  
During normal operation the current Security Level is displayed by pressing the 

 key. 

NOTE: in remote programming, an IS status request provides the complete list of available 
settings and the current value.  
Example:

#IS 

<enter>

  NILECJ1 
  NILECJ2 
  : 
  : 

CURRENT SETTING: NILECJ2 

NOTE:  
If the selected setting has been modified affecting detection capability, an additional ‘MODIFIED’ 
indication appears.  
If the current setting does not correspond  to any Security levels pre-memorised in factory, a ‘NO SET’ 
message is provided. 
If an LD user-defined setting is selected, a previous IS setting is disabled. This also is signalled through 
the message ‘NO SET’: 

The available Security Levels are listed in detail in the ‘Factory Acceptance Test Report ‘ form included.

 

LBI 

Alarm 
indication 
enabling at the 
entry side LED 
bar  

ON 
OFF 


Alarm indication enabling at the entry side LED bar. 

ON 

the entry side LED bar provides an indication in case of an alarm   

OFF 

the entry side LED bar does not provide an indication in case of an alarm. 

NOTE: the entry and exit sides of the archway are defined by the GD parameter. 

LC 

Uniformity 
coefficient of 
the 
electromagneti
c field emitted 
by the antenna 
- ground level

-20,…,-1,
0,
1,…,20 


R  

Uniformity coefficient of the electromagnetic field emitted by the antenna at ground level. It 
allows the sensitivity equalization, due to metal reinforcement bars located inside  the floor 

-20 

maximum field attenuation 

no change (standard) 

+20 

maximum field increment 

This command is available on certain probe models only. 

LD 

Loading user-
defined 
settings 

0-19


Loading of a setting predefined according to the customer’s requirements. 
Besides the IS settings, which are compliant to security international standards, the LD 
settings can be used to select special operating modes specified by the customer. 

NOTE: in remote programming, an LD status request provides the complete list of the available settings 
and the current name.  

Example:

#LD 

0<enter>

selection of LD=0 setting 

#LD 

<enter>

303-670-1099

Summary of Contents for 02PN20

Page 1: ...lutions each model offers the best cost performance ratio for its specific application Options Some functions parts indicated as options in this manual are included as default in high level models Ell...

Page 2: ...S TO THE LOCAL PROGRAMMING PHASE USING THE PASSWORD 31 4 3 2 FREE ACCESS TO LOCAL PROGRAMMING PHASE WITHOUT PASSWORD 31 4 3 3 COMMAND EXECUTION IN LOCAL PROGRAMMING 32 4 3 4 EXIT FROM LOCAL PROGRAMMIN...

Page 3: ...n of the earth ground safety terminal will render the device dangerous Intentional cutting or disconnection is strictly forbidden Whenever there is any suggestion that the level of protection has been...

Page 4: ...ially dangerous substances Do not short circuit the contacts serious risk of burning and breakage Do not dispose of battery in fire danger of explosion Any maintenance or repair involving the device b...

Page 5: ...c casing or metal casing is designed to be attached directly to the crossbar of the archway An embedded Infra Red interface allows the use of an accessory remote control unit which acts as the control...

Page 6: ...na Rf Reflectors for transit counting options on column version C1 crossbar fitted with holes for mounting the control unit C2 crossbar without holes panel shape version K ON OFF special key Indicator...

Page 7: ...et LAN interface Web server for set up and remote data log Real Time clock with battery backup Non volatile Memory for Metal Detector events storage wireless Wi Fi interface APSIM3Plus version only su...

Page 8: ...is intended for upgrading the standard version to outdoor applications according to IEC 60950 22 This kit includes shelters crossbar protection covers for power supply and waterproof power supply ada...

Page 9: ...mperature 20 C to 70 C on demand 37 C to 70 C Storage temperature 37 C to 70 C Relative humidity 0 to 95 without condensation Standard Version UW 115 4 5 UW 50 2 630 00 24 3 4 6 5 1 4 UW 2255 88 8 205...

Page 10: ...30 24 8 6 5 1 4 2050 80 7 UW 115 4 5 UW 50 2 UW 170 6 7 UW 660 00 26 340 13 4 UW 155 6 1 2035 80 1 2275 89 6 401 15 8 440 17 3 990 39 560 22 UW 362 14 3 Dimensions UW 720mm OPTION 760mm or 820mm panel...

Page 11: ...ration This configuration can be applied in outdoor sheltered permanent installations or outdoor non sheltered short term installations single event entrance 3 1 1 Examples of possible sources of inte...

Page 12: ...ced in direct contact with the MD 6 Sources of vibration Unstable Floor The MD gate shall be anchored to a stable floor Avoid installing on wood or metal platforms unless necessary In this latter case...

Page 13: ...y the Security Authority Components needed Unpacking Scissors and Pliers Phillips screwdriver n 1 Kit C E I A FGA TFV Metal free clothes Clean Tester Tracksuit Gym shoes No metal personal effects meta...

Page 14: ...RX parts Configuration A Configuration B Configuration A Configuration B XRU XRU XRU XRU Configuration A Configuration B Configuration A Configuration B Typical application fitted with two Metal Detec...

Page 15: ...mp protection cover of the lower connection module ccp protection cover of CU control unit and C1 crossbar cp protection cover of C2 crossbar Pictures of main components Positioning the panels Tilt do...

Page 16: ...t of the panel taking care that the logo is facing the floor Attach the C2 crossbar with no holes to the upper part of the panel making sure that the logo is facing up RX C1 C2 Configuration B with TX...

Page 17: ...en key AW2 or TX1 to free them Configuration A Lift the archway placing it on the supports S1 and S2 Attach the control unit to the lower crossbar using vc screws and AW2 Allen key included in the ins...

Page 18: ...g panel connector Lock the cable connectors using the short screwdriver cK included into the installation kit Insert the cables into the crossbar groove Fix the cables in position using the clips on t...

Page 19: ...C2 Each cap s secured by a short cord to a cable clip Remount covers cp Attach the protection cover ccp of the crossbar C1 using the hooks h and the knobs vp taking care to push it towards the panel c...

Page 20: ...river photocell vc control unit mounting screw PC Protection covers ccp protection cover of CU control unit and C1 crossbar Pictures of main components Positioning the columns Place F spacers on the f...

Page 21: ...les for the control unit close to the TX column Insert the crossbar guide pins into the holes on the inside of the column Configuration A TX RX Configuration B with TX column on the right when facing...

Page 22: ...guration B Connecting the control unit Connect the cables coming from the control unit as illustrated in the figure below Connect each cable to the column connector winding the cable in excess if nece...

Page 23: ...PH2 AW Photocells Reflectors Phillips screwdriver and Allen wrench included in the installation kit Remove the pc cap using AW key pc Open the Ph photocell module using a PH2 cross head screwdriver Pa...

Page 24: ...ability and acting as an adapter allow the archway to be easily relocated In order to prevent the archway from tipping over in case of bumps the stable anchoring to the ground is anyway mandatory Meta...

Page 25: ...ribed in the previous step but passing the output cable of the AC DC adapter through one of the strain reliefs present on the protection cover Connect the input cable of the AC DC adapter to the mains...

Page 26: ...ext step use the UP and DOWN keys to change a numeric value or an answer Y yes to N no and vice versa In the following any operator s action is indicated between and OTS function can be executed also...

Page 27: ...TX mains ALARM VOLUME SELECT ENTER AV ENTER Selection of the Alarm Volume MINIMUM VOLUME SELECT ENTER MV ENTER Selection of the Minimum Volume lower limit for alarm volume adjustment ALARM TONE SELEC...

Page 28: ...onto the X ray unit belt Subject the floor to normal and above normal stress walk heavily change direction In case of strong gusts of air or wind EVA function can be useful to compensate archway vibra...

Page 29: ...d to be compatible For safety reasons anchoring the unit to the floor is mandatory Anchoring methods shall be agreed prior to proceeding with the following steps Marble or tiled floors or Carpeted flo...

Page 30: ...o bumps or mechanical exertion 3 7 Personalisation 3 7 1 Settings check If required by the specifications of the Security Authority change the programming setting to refine the operating mode Enter pr...

Page 31: ...will be terminated automatically if no commands are entered for a period of 2 minutes 4 3 Local programming Use the keypad on the inside panel of the control unit The PROG key is used to enter and ex...

Page 32: ...ower supply and serial communication cables together in order to avoid loops ATTENTION in order to avoid any damage to the PC s interface make sure that the cable does not include a connection to pin...

Page 33: ...TER P _10000 number of passages through the antenna TA_ 2350 the total number of passages with alarm TR_23 5 the alarms passages ratio as a percentage MA_ 1500 number of passages with alarm due to a m...

Page 34: ...92 168 0 101 IP I192 168 0 101 IS International Security Standard 1 30 C R Selects a security level corresponding to an international standard During normal operation the current Security Level is dis...

Page 35: ...stance will be required from C E I A personnel OFV Functionality check at operator level C Activates the OFV test For details of the procedure see the instructions included in the OFV kit OTS One Touc...

Page 36: ...ach command is changed by entering the opposite value to the current one to the right of the character If the user does not wish to change the command state he she can simply press ENTER and the curso...

Page 37: ...ction module power indicator entry pacing lights entry side GREEN transit allowed RED busy transit not allowed zone alarm indication exit side in case of alarm a group of LEDs lights up to pinpoint th...

Page 38: ...l be performed according to local Security Authority procedures taking into account that The indication given through light bars that illuminate where the presence of an object is detected is solely m...

Page 39: ...ming phase starts the last used command will appear Press the arrow keys to select the AV Alarm Volume or AT Alarm Tone function if a different one is displayed Press the ENTER key to change the AV se...

Page 40: ...eiver antenna A in the form of an archway made up of a transmitter part TX a receiver part RX a power supply adapter PSA FG PCU TX RX A CU PSA R RX PSA TX CU RX PSA TX CU Block diagram of a metal dete...

Page 41: ...e calibration Test piece specified by the Security Standard in use 12 months mandatory Battery replacement Supplied Allen Key N 5 2 batteries Recommended 3 years maximum 5 years 6 2 Diagnosis Generic...

Page 42: ...ing a chip card try at first to perform again the operation completely and correctly If the self diagnosis message appears again carry out the recommended action listed in the following table Display...

Page 43: ...out FGA step Increase LC parameter setting Excessive sensitivity at ground level f i detection of shoes Excessive sensitivity at ground level Start OTS procedure and carry out FGA step Decrease LC pa...

Page 44: ...rtment with batteries 49510 49510 49510 49510 49510 Pb 12V 9Ah battery 36891 36891 36891 36891 36891 100 240V 100W IP67 Power supply adaptor 48092 48092 48092 48092 48092 100 240V 80W Power supply ada...

Reviews: