5� Upstream circuit breaker selection and aux power preparation:
Constructor or CPO is mandatory to select a circuit breaker which with “shunt
release accessory” or relevant devices so that the safety function can be activat-
ed. Below are reference SOR reference models from ABB:
12V : SOR-C 12V DC (1SDA066321R1)
24V : SOR-C 24-30V AC/DC (1SDA066322R1)\
Siemens Shunt release reference models :
3VA9988-0BL33(220-250VADC) (For 60KW CE)
3VA9978-0BL33(208-277Vac/220-250 Vdc) (For 60KW UL)
Schneider Shunt release reference models :
LV429387-208-277VAC 60Hz (For 60KW CE & UL)
6� Wires Spec Selection:
The wires from sensor board to upstream circuit breaker is recommended
UL1015 20AWG 105°C 600V or relevant.
14
NOTICE
Once the power been from upstream circuit breaker, in order to get
power back to charger’s auxiliary power supplies for maintenance
purpose, please disable door limit switch before recovery circuit
breaker.