77
7.4
Commissioning TBEN-L…PLC-… as Cloud gateway
To transmit data to the Turck Cloud, the TBEN-L...PLC-... must be integrated into an Ethernet
network with Internet access. Access can be via any Internet router. Port 443 (SSL) must be en-
abled in the Internet router for the connection with the Turck Cloud.
Application example
NOTE
In Dual MAC mode, the connected networks are separated from each other by sep-
arating the Ethernet ports. For security reasons, Turck therefore recommends oper-
ating the TBEN-L...PLC-... in Dual MAC mode in cloud applications in order to separ-
ate the automation network from the Internet.
n
TBEN-L…PLC-… (firmware version ≥ 1.4.6.0):
DUAL MAC mode activated [
26], the TBEN-L PLC is a member of 2 separate Ethernet net-
works
n
IP addresses:
– Ethernet port P1 (locale network):
192.168.1.100
, assigned via Turck Service Tool [
– IP address for Ethernet port P2 (internet):
192.168.83.43
, assigned via DHCP server in the network
Fig. 81: Webserver – Ethernet port settings