Operating
Using the USB host port
110
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Function
Folder name Description
Status
CODESYS
program
Automatic
device re-
start
Restore 2
RESTORE_2 Load the CODESYS application and the device data from the
USB stick into the device.
The function can only be used if the data on the USB stick
comes from a device with identical firmware version.
The following files are loaded on the USB stick:
n
All *.app and *.crc files
n
PlcLogic folder
n
Folder USB_Data
n
IP address
n
PROFINET Device Name
n
Retain data (retain.bin)
The folder may only contain one application file (*.app).
All previous applications on the device will be deleted
without further warning.
The names of the CODESYS application and the file names of
the boot application (*.app and *.crc) must be the same. If
the names are different or have been changed, the applica-
tion cannot be started.
The device automatically restarts when the USB stick is re-
moved from the USB port.
STOPP
Yes
Firmware
Update
FW_UPDATE Update of the device firmware. The IP address, the PROFINET
device name and the CODESYS application are not overwrit-
ten.
File name: TBEN-Lx-…_V….bin
The device automatically restarts when the USB stick is re-
moved from the USB port.
STOPP
yes
Write user
data
USB_DATA_
WRITE
Load the
USB_Data
folder from the storage medium into
the device.
Existing files with the same name are overwritten. All other
files remain unchanged.
STOPP
Yes
Summary of Contents for TBEN-L Series
Page 1: ...Your Global Automation Partner Instructions for Use TBEN L PLC Compact CODESYS V3 PLC...
Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Page 53: ...V02 00 2019 11 53 Fig 57 Configuration of in and output data in TIA Portal CODESYS...
Page 105: ...V02 00 2019 11 105 Fig 101 Webserver I O channel diagnostics...
Page 107: ...V02 00 2019 11 107 Fig 103 Webserver module status...