Maintenance
Ensure that the plug connections and cables are always in good condition.
The devices are maintenance-free, clean dry if required.
11.1
Executing the firmware update
11.1.1
Executing the firmware update via USB storage medium
Proceed as follows to update the firmware via a USB storage medium:
Create the folder FW_UPDATE on a USB stick.
Store the firmware as bin file in the folder FW_UPDATE.
Insert the USB stick into the device.
a
The RUN-LED flashes green with 0.5 Hz.
Press the SET-button within the next 30 seconds for at least 3 seconds.
a
The RUN LED flashes in the sequence 3 × green - pause (1 Hz) - 3 × green - pause (1 Hz)
- ....
a
The data is loaded into the device.
a
When the RUN LED blinks orange at 1 Hz, the firmware update is complete.
Remove the USB stick.
Execute a power cycle.
a
The device restarts.
11.1.2
Carry out firmware update via FDT/DTM
The firmware of the device can be updated via FDT/DTM. The PACTware™ FDT frame applica-
tion, the DTM for the device and the current firmware are available as downloads free of charge
from
.
NOTICE
Interruption of the power supply during the firmware update
Risk of device damage due to faulty firmware update
Do not interrupt the power supply during the firmware update.
During the firmware update do not reset the power supply.
Summary of Contents for TBEN-L Series
Page 1: ...Your Global Automation Partner Instructions for Use TBEN L PLC Compact CODESYS V3 PLC...
Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Page 53: ...V02 00 2019 11 53 Fig 57 Configuration of in and output data in TIA Portal CODESYS...
Page 105: ...V02 00 2019 11 105 Fig 101 Webserver I O channel diagnostics...
Page 107: ...V02 00 2019 11 107 Fig 103 Webserver module status...