Commissioning
Put master/slave functions into operation in CODESYS
64
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
7.3.14
Commissioning TBEN-L...-PLC-... parallel as EtherNet/IP™ Scanner and Slave (Device)
If the device is used simultaneously as both a EtherNet/IP™ Scanner and a EtherNet/IP™ Slave
(Device), a second Ethernet interface must be added to the device. The assignment of the Eth-
ernet ports in CODESYS is as follows:
Ethernet interface in CODESYS
Function
eth0
Ethernet/IP™ Slave (Device)
eth1
EtherNet/IP™ Scanner
Adding and configuring the second Ethernet interface
Configuring the Ethernet/IP™ Scanner
ü
The Ethernet interface eth1 is configured as described under "Configuring the Ethernet in-
terfaces" [
ü
The EtherNet/IP Scanner from 3S - Smart Software Solutions GmbH is used.
Add the EtherNet/IP™ Scanner to Ethernet using the
Add Device
function and configure
it.
Fig. 68: Ethernet/IP™ Scanner at eth1