Technical data

General technical data

Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com

V01.00 | 2022/09 | 40

Technical data

Degree of protection

IP65/IP67

According to EN/IEC 60529

Overtemperature protection

Yes, internal

Output shut down with auto-
matic restart.

Input transient protection

MOV (Metal Oxide Varistor)

Internal input fuse

Not user replaceable, slow-
blow high-breaking capacity
fuse

Touch current (leakage cur-
rent)

Max. 0.45/ 1.5 mA

At 3 × 480 AC, 60 Hz, TN-,TT-
mains/IT-mains, lower currents
at lower voltages and frequen-
cies.

Installing

4 × M4 screw

Standard orientation: vertical,
connection level downwards
with two screws each at the
upper and lower mounting
holes
Other mounting orientations:
reduce the output current, 
derating: 
max. output power ar max.
ambient temperature (s. fig.:
Derating – standard mounting
orientation):

n

max. 500 W at max. 45 °C

n

max. 350  W at max. 60 °C

350

500

600

+ 45

- 25

+ 55

+ 70

P

Out

/W

T

/°C

0

Fig. 22: Derating – standard mounting orientation

Summary of Contents for PSU67-3P-1S-2L-24250-IOL-F

Page 1: ...Your Global Automation Partner Instructions for Use PSU67 3P 1S 2L 24250 IOL F Smart switching power supply in IP67...

Page 2: ...3 Functional principle 9 4 4 Functions and operating modes 10 4 4 1 User interface 10 4 4 2 AC voltage input 10 4 4 3 DC voltage outputs 11 4 4 4 IO Link interface 13 5 Installing 14 5 1 Special inst...

Page 3: ...Link data 26 9 3 Diagnostic and status messages acyclic IO Link data 27 9 4 IO Link Events 30 9 5 IO Link error codes 31 10 Maintenance 32 11 Repair 32 11 1 Returning devices 32 12 Disposal 32 13 Tec...

Page 4: ...Table of Contents Hans Turck GmbH Co KG T 49 208 4952 0 more turck com www turck com V01 00 2022 09 4...

Page 5: ...jury if not avoided WARNING WARNING indicates a dangerous situation with medium risk of death or severe in jury if not avoided CAUTION CAUTION indicates a dangerous situation of medium risk which may...

Page 6: ...ID 100025929 2 2 Scope of delivery The scope of delivery includes n IP67 power supply n Quick Start Guide 2 3 Turck service Turck supports you with your projects from initial analysis to the commissio...

Page 7: ...use at altitudes up to 5000 m 16400 ft Above 2000 m 6560 ft the output current and overvoltage category must be reduced The devices may only be used as described in these instructions Any other use i...

Page 8: ...vice has four internal eFuses to protect the output voltage The IO Link interface is designed as an A coded M12 connector X0 Configuration and dia gnostics are performed either via buttons and LEDs di...

Page 9: ...1 3 Display elements The device has an LED bar monitoring mode 24 to display n Total output power in n Channel output voltage in V and channel output current in A n Channel LEDs OUT1 OUT4 n Operating...

Page 10: ...C nominal range Inrush current limitation The power supply is equipped with an active inrush current limiting circuit which limits the in put inrush current to a very low value after switching on The...

Page 11: ...8 PSU67 DC AC L1 PE L2 L3 L1 L2 L3 open Fig 4 2 phase operation 290 460 570 320 300 400 500 550 POut W UIn VAC 0 Fig 5 Performance in 2 phase operation 4 4 3 DC voltage outputs The DC voltage outputs...

Page 12: ...output power High prio CH1 without load Fig 6 Tripping of the channel with the lowest priority when the total output power is exceeded After having been switched off the outputs start automatically on...

Page 13: ...the short time load pulse must be below 200 of the nominal output power n The duration of the load pulse must be shorter than the max permissible duration for the additional power n The average power...

Page 14: ...tion clearances 50 mm on top and bottom 10 mm on the front and 10 mm left and right side Device cooling The device uses convection cooling An external fan is not necessary 5 1 Special installation ins...

Page 15: ...ice has two 5 pin L coded M12 connectors for connecting the DC output voltage side The maximum tightening torque is 0 6 Nm Connect the output voltage side according to the pin assignment shown below v...

Page 16: ...Hans Turck GmbH Co KG T 49 208 4952 0 more turck com www turck com V01 00 2022 09 16 7 Commissioning After connecting the wires and by switching on the AC input voltage the device automatically goes i...

Page 17: ...ly of each other In the delivery state all outputs of the device are switched off Press and hold the pushbutton on the output channel OUT1 OUT4 for at least 1 s to switch a channel on or off manually...

Page 18: ...0x0A Device ID R 3 E g PSU67 3P 1S 2L 24250 IOL F 2228224 0x220000 0x0B 0x0C 0x10 Standard command R W 1 129 application reset 130 restore factory settings 8 2 2 Identification ISDU Index Hex dec Obj...

Page 19: ...for the application specific install ation location of the device 8 2 3 Index 0x02 System commands according to IO Link specification Command 129 Application reset 130 Restore factory settings 8 2 4...

Page 20: ...16 2 8 A bit RW 0x69 105 0 Output Voltage Setpoint UINT16 16 2 8 V Bit RW 0x6A 106 0 eFuses channel on off Set of BOOL 8 RW 0x6C 108 0 eFuse trip value Ch1 UINT16 16 2 8 A bit RW 1 2 3 eFuse trip val...

Page 21: ...face 1 IO Link only Configuration of the device only possible via IO Link IODD 2 Both Configuration of the device possible both directly on the device and via IO Link IODD 3 None button lock Configura...

Page 22: ...el 1 3 eFuse ch3 on off 2 4 eFuse ch4 on off 3 eFuse trip value ch index 0x6C 108 This parameter defines the trigger value of the eFuse for the respective channel Format Length UINT16 2 bytes per chan...

Page 23: ...t the respective channel Format Length 32 bit record UINT8 8 bit per channel Sub index Object name Bit offset 1 eFuses pre alarm level Ch1 24 2 eFuses pre alarm level Ch2 16 3 eFuses pre alarm level C...

Page 24: ...uttons until OUT1 or OUT4 is skipped a When all channel LEDs are off the unit is back in normal mode for monitoring the total output power 9 1 1 LED displays The unit has the following LED indicators...

Page 25: ...tch off channel manually via pushbutton at output OUT1 OUT4 Conditions n PSU with NEC outputs Difference between positive and negative current of the output has been 1 A for 6 6 5 s n PSU without NEC...

Page 26: ...al value eFuse current ch2 4 56 eFuse current ch3 5 40 eFuse current ch4 6 24 eFuse state ch1 10 16 BOOL 1 State of the eFuse 0 inactive cause s sub index 14 17 or sub index 18 21 1 active eFuse switc...

Page 27: ...itional power PSU delivers additional power for more than 1 s 4 3 Bit 3 Overtemperature CAP 5 4 Bit 4 Overtemperature PSU The temperature of the internal unit is too high 6 5 Bit 5 Overload Total outp...

Page 28: ...S phase phase Value range 0 24000 0 1500 V Actual output voltage 0x4F 79 0 UINT16 15 0 2 8 V bit Value range 0 12544 0 49 V Converter average current 0x51 81 0 UINT16 15 0 2 8 A bit Value range 0 1280...

Page 29: ...alue range 0 150000 Turn on Counter 0x52 82 0 UINT32 31 0 Value range 0 150000 Uptime since last turn on 0x53 83 0 Parameter access via sub index 0 only n Hours 1 UINT32 39 8 h n Hours 2 UINT8 7 0 min...

Page 30: ...longer than 3 s 0x1802 Overload Warning The total output load is higher than permitted 0x1803 High voltage input Warning The AC input voltage exceeds the operating range 0x1804 Low voltage input Warni...

Page 31: ...s to parameters possible device does not allow ac cess in current state 0x8021 Service temporarily not available local control No access to parameters possible device in local operating mode operation...

Page 32: ...acceptance conditions when returning the device to Turck 11 1 Returning devices Returns to Turck can only be accepted if the device has been equipped with a Decontamination declaration enclosed The d...

Page 33: ...steady state end value s fig Voltage range input voltage AC Switch on delay Typ 2 s at 500 W symmetrical phase voltages s fig Switch on beha vior Rise time Typ 10 ms at 500 W constant current load 0 m...

Page 34: ...oltage Output Voltage Fig 14 Switch on behavior POut W IIn A typ 0 0 0 2 0 4 0 6 0 8 1 0 0 100 200 300 400 500 600 3 400 VAC 3 480 VAC Fig 15 Input current vs output power at 24 VDC output voltage POu...

Page 35: ...put current Max 12 A per output s fig Trip curve diagram max 12A Total output power continu ous at ambient temperature n At 45 C n At 55 C n At 70 C 600 W 500 W 350 W Linear derating between 45 C and...

Page 36: ...com V01 00 2022 09 36 25 0 45 70 55 T C 1000 350 500 600 700 short term max 5 s continuous POut W 0 Fig 18 Derating output power vs ambient temperature POut W 0 0 2000 80 110 5000 54 Altidue m AP kPa...

Page 37: ...f load Typ 22 W Typ 23 W At 24 VDC 500 W full load POut W E ciency 91 92 93 94 95 96 0 100 200 300 400 500 600 3 400 VAC 3 480 VAC Fig 20 Power factor vs output power at 24 VDC typ POut W Power Losses...

Page 38: ...00 h n At 24V 500 W and 25 C Ground Fixed GF25 33000 h 32000 h EMC According to EN 1000 6 1 EN 61000 6 2 EN 61000 6 3 EN 61000 6 4 EN 61000 3 2 and EN 61000 3 3 Ambient conditions Operating temperatur...

Page 39: ...8 bumps in total According to IEC 60068 2 27 Degree of pollution 3 According to IEC 62477 1 not conductive Vibration sinusoidal 2 17 8 Hz 1 6 mm 17 8 500 Hz 2g 2 hours per axis According to IEC 60068...

Page 40: ...h breaking capacity fuse Touch current leakage cur rent Max 0 45 1 5 mA At 3 480 AC 60 Hz TN TT mains IT mains lower currents at lower voltages and frequen cies Installing 4 M4 screw Standard orientat...

Page 41: ...A S 11 rue de Courtalin Bat C Magny Le Hongre F 77703 MARNE LA VALLEE Cedex 4 www turckbanner fr Great Britain TURCK BANNER LIMITED Blenheim House Hurricane Way GB SS11 8YT Wickford Essex www turckban...

Page 42: ...CK RUS OOO 2 nd Pryadilnaya Street 1 105037 Moscow www turck ru Sweden Turck Sweden Office Fabriksstr ket 9 433 76 Jonsered www turck se Singapore TURCK BANNER Singapore Pte Ltd 25 International Busin...

Page 43: ...Over 30 subsidiaries and 60 representations worldwide www turck com 100032475 2022 09 100032475...

Reviews: