![turck PSU67-3P-1S-2L-24250-IOL-F Instructions For Use Manual Download Page 24](http://html1.mh-extra.com/html/turck/psu67-3p-1s-2l-24250-iol-f/psu67-3p-1s-2l-24250-iol-f_instructions-for-use-manual_1181803024.webp)
Operating
Monitoring mode
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V01.00 | 2022/09 | 24
9
Operating
9.1
Monitoring mode
Mode: Monitoring output power (normal operation)
In the “Monitoring output power" mode, the LEDs display the current output power as a per-
centage of 500 W (50 % = 250 W, 100 % = 500 W). For values above 100 %, the orange 125 %
LED flashes. Immediately after switching on, the LEDs display the total output power.
Mode: Monitoring channel output current
In the "Monitoring output power" mode (normal operation), press [
Ó
] [
Ô
] buttons to
switch to the " Monitoring channel output current " mode.
a
LED OUT1 lights up constantly orange. The current output current for output 1 is dis-
played via the LED bar (2 A…12 A).
Press [
Ó
] [
Ô
] buttons to change the output channel.
To change to normal operation: Press [
Ó
] oder [
Ô
] buttons until OUT1 or OUT4 is
skipped.
a
When all channel LEDs are off, the unit is back in normal mode for monitoring the total
output power.
9.1.1
LED displays
The unit has the following LED indicators:
n
Operating status (Status)
n
Output power in % (%-LEDs)
n
Channel LEDs (OUT1…OUT4)
LED %
Meaning
0…100 %
Green
The DC output power is 20…100 % of the max. output power.
> 100 %
Orange
The DC output power above 100 % of the max. output power.
STATUS LED
Meaning
Green
The DC output voltage is above 90% of the setpoint voltage. All outputs op-
erate according to their settings.
Off
Possible causes:
n
The DC output voltage is below 90 % of the setpoint voltage
n
An output channel has tripped
n
The power supply is not switched on
Red
AC input voltage too low
Orange flashing
Output switched off and in Hiccup Plus mode (18 s)
Red flashing
The device has switched off due to overtemperature. As soon as the tem-
perature reaches the normal operating range, the output switches on again
and the STATUS LED lights up permanently green.