Setting
Setting the device via IO-Link
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V01.00 | 2022/09 | 21
Configuration setting — index 0x67 (103)
This parameter defines the interface via which the device can be configured. In addition, the
device can also be locked against configuration.
Format
Length
UINT8
8 bit
Default values are shown in
bold
.
Value
Meaning
0
Human-machine interface only Configuration of the device
only possible directly on the
device via the user interface
1
IO-Link only
Configuration of the device
only possible via IO-Link
(IODD)
2
Both
Configuration of the device
possible both directly on the
device and via IO-Link (IODD)
3
None (button lock)
Configuration locked
Total converter current pre-alarm level — index 0x68 (104)
This parameter defines pre-alarm level for the total current.
Format
Length
UINT16
16 bit
Default values are shown in
bold
.
Unit:
2
-8
A/bit
Value range:
256…25600 = 1…100 A
Default value:
5120 = 20 A
Output voltage setpoint — index 0x69 (105)
This parameter defines the setpoint for the output voltage.
Format
Length
UINT16
16 bit
Default values are shown in
bold
.
Unit:
2
-8
V/bit
Value range:
6144…7168 = 24…28 V
Default value:
6272 = 24.5 V