Technical data
General technical data
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V01.00 | 2022/09 | 38
13.5
General technical data
Technical data
Calculated lifetime expectancy
3 AC, 400 V
3 AC, 480 V
n
At 24 V, 500 W, 40 °C
43000 h
37000 h
n
At 24 V, 250 W, 40 °C
177000 h
168000 h
n
At 24 V, 500 W, 25 °C
135000 h
119000 h
n
At 24 V, 250 W, 25 °C
466000 h
416000 h
MTBF
MTBF SN 29500, IEC 61709
3 AC, 400 V
3 AC, 480 V
n
At 24 V, 500 W, 40 °C
253000 h
233000 h
n
At 24 V, 500 W, 25 °C
461000 h
427000 h
MTBF MIL HDBK 217F
n
At 24 V, 500 W and 40 °C,
Ground Benign GB40
98000 h
93000 h
n
At 24 V, 500 W and 25 °C,
Ground Benign GB25
144000 h
138000 h
n
At 24V, 500 W and 40°C,
Ground Fixed GF40
25000 h
24000 h
n
At 24V, 500 W and 25 °C,
Ground Fixed GF25
33000 h
32000 h
EMC
According to EN 1000-6-1, EN 61000-6-2, EN 61000-6-3,
EN 61000-6-4, EN 61000-3-2 and EN 61000-3-3
Ambient conditions
Operating temperature
-25°C to +70 °C
(-13°F to 158 °F)
Operational temperature is the
same as the ambient or sur-
rounding temperature and is
defined as the air temperature
2cm below the unit.
Storage temperature
-40°C to +85 °C
(-40°F to 185 °F)
For storage and transportation
Output derating
10 W/°C
B45 °C and +70 °C
(113 °F and 140 °F)
33 W/1000 m or 5 °C/1000 m
For altitudes >2000 m (6560 ft),
s. fig.: Output power vs. ambient temperature [
The derating is not hardware controlled. Observe reduced current limits to avoid overloading
the device.
Humidity
5 to 95 % r.h.
According to IEC 60068-2-30
Atmospheric pressure
54…110 kPa
S. fig.: Output power vs.
ambient temperature [
Altitude
Max. 5000 m (16 400 ft)
S. fig.: Output power vs.
altitude [