Operating
Process data (cyclic IO-Link data)
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V01.00 | 2022/09 | 26
9.2
Process data (cyclic IO-Link data)
The process data is sent cyclically to the IO-Link master. The device sends 2 bytes of process
data.
Data
Resolu-
tion
Sub
index
Data type Length
in bit
Bit offset
Description
Actual output total
current
2
-8
A/bit 1
UINT16
16
104
Total output current (actual value)
Actual output
voltage 1
2
-8
V/bit
2
UINT16
16
88
Actual Output Voltage
eFuse current ch1
2
-8
A/bit 3
72
UINT16
16
Output current eFuse (actual value)
eFuse current ch2
4
56
eFuse current ch3
5
40
eFuse current ch4
6
24
eFuse state ch1
10
16
BOOL
1
State of the eFuse:
0: inactive, cause: s. sub index 14…17 or
sub index 18…21
1: active: eFuse switched on, output
voltage available
eFuse state ch2
11
17
eFuse state ch3
12
18
eFuse state ch4
13
19
eFuse ch1 —
overload trip state
14
8
BOOL
1
Trip state of the eFuse in case of an
overload:
0: ok
1: tripped, overload at output
eFuse ch2 —
overload trip state
15
9
eFuse ch3 —
overload trip state
16
10
eFuse ch4 —
overload trip state
17
11
eFuse ch1 —
short-circuit state
18
0
BOOL
1
Trip state of the eFuse in case of as
short-circuit:
0: OK
1: tripped, short-circuit at output
eFuse ch2 —
short-circuit state
19
1
eFuse ch3 —
short-circuit state
20
2
eFuse ch4 —
short-circuit state
21
3