Operating
Process input data
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V01.00 | 2022/09 | 23
9
Operating
CAUTION
Operating the device outside the specification
Slight injuries and equipment damage possible.
Operate the unit only within the operating temperature specified in the tech-
nical data.
Use only thermally suitable connection cables.
9.1
Process input data
Byte
no.
Bit offset
7
6
5
4
3
2
1
0
Inputs
0
C3P2
(B)
C3P4
(A)
C2P2
(B)
C2P4
(A)
C1P2
(B)
C1P4
(A)
C0P2
(B)
C0P4
(A)
1
C7P2
(B)
C7P4
(A)
C6P2
(B)
C6P4
(A)
C5P2
(B)
C5P4
(A)
C4P2
(B)
C4P4
(A)
Module diagnostics
2
Group dia-
gnostics
-
-
Under-
voltage V2
Under-
voltage V1
Under-
voltage V
IOL
-
-
Connector diagnostics – overcurrent sensor supply
3
Overcurrent
C7
Overcurrent
C6
Overcurrent
C5
Overcurrent
C4
Overcurrent
C3
Overcurrent
C2
Overcurrent
C1
Overcurrent
C0
Channel diagnostics – overcurrent output
4
Overcurrent
C3P2
Overcurrent
C3P4
Overcurrent
C2P2
Overcurrent
C2P4
Overcurrent
C1P2
Overcurrent
C1P4
Overcurrent
C0P2
Overcurrent
C0P4
5
Overcurrent
C7P2
Overcurrent
C7P4
Overcurrent
C6P2
Overcurrent
C6P4
Overcurrent
C5P2
Overcurrent
C5P4
Overcurrent
C4P2
Overcurrent
C4P4
NOTE
The diagnostics can also be be accessed via IO-Link indices.
Designation
Meaning
Inputs
CxPy
0
Input inactive
1
Input active
Module diagnostics
Group diagnostics 0
No diagnostics
1
Module diagnostics
active
Evaluate the bit to monitor the dia-
gnostics cyclically.
ð
Bit = 0: no diagnostics active
ð
Bit = 1: Module diagnostics
Bit = 1: Evaluate further diagnostic
bits to determine the origin of the
diagnosctic message.