Setting
Parameters
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V01.00 | 2022/09 | 18
ISDU
Index
Hex.
(dec.)
Object name
Access
Length
in bytes
Meaning/
default value
Comment
0x19
(25)
Function Tag
read/
write
32
Default "***"
Field for the applica-
tion specific device
function
0x1A
(26)
Location Tag
read/
write
32
Default "***"
Field for the applica-
tion-specific installa-
tion location of the
device
IO-Link object directory — ISDU device parameters: Preferred Index (parameters and
diagnostics of the digital in- and outputs)
ISDU
Index
Hex.
(dec.)
Object name
Access
Length
in bytes
Meaning
0x40
(64)
Parameter ID
read/
write
4
Customer-specific ID, for free use
0x41
(65)
Inverting input
read/
write
2
Invert digital input
0x42
(66)
Activate output
read/
write
2
Activate output
0x43
(67)
Impulse
stretching input
read/
write
16
Pulse stretching input
0x44
(68)
Short circuit re-
covery
read/
write
2
Manual output reset after overcurrent
0x45
(69)
Failsafe
read/
write
4
Output after error
0x46
(70)
Under voltage
diagnostics
read/
write
2
Enable V1 and V2 undervoltage diagnostics/
threshold values for undervoltage diagnostics
V1, V2 and V
IOL
Diagnostics
0x50
(80)
Supply error
read
only
2
n
Undervoltage supply V1, V2 and V
IOL
n
Overcurrent VAUX connector C0…C7
Diagnostics
0x51
(81)
Output short
circuit
read
only
2
Overcurrent output 0…15