Setting
Parameters
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V01.00 | 2022/09 | 22
Enable undervoltage diagnostics V1, V2 and V
IOL
/threshold values for undervoltage
diagnostics — 0×46 (70), sub index 0
This parameter defines whether undervoltage diagnostic messages are sent in case of an V1, V2
or V
IOL
undervoltage. Additionally it defines the threshold values for undervoltage diagnostics
for V1, V2 and V
IOL
.
Format
Length
Array of byte
2 byte
3 bit per module
Default values are shown in
bold
.
Value
Meaning
Activate undervoltage diagnostics
0
No
1
Yes
Undervoltage diagnostics activated
Threshold value for undervoltage diagnostics V1, V2 and V
IOL
0
Standard
(IEC 61131-2)
Lower threshold: 19.2 V
Upper threshold: 20.4 V
1
Extended
Lower threshold: 17.5 V
Byte 0
Bit offset
7
6
5
4
3
2
1
0
-
-
-
-
-
-
-
-
Byte 1
Bit offset
15
14
13
12
11
10
9
8
-
-
-
-
-
Activate V2 under-
voltage diagnostics
Activate V1 under-
voltage diagnostics
Threshold