Setting
Setting and visualization with the Turck Radar Monitor
36
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
9.4.4
Turck Radar Monitor – filtering signals
The Turck Radar Monitor is provided via four filter options for suppressing disturbance signals:
n
Foreground suppression (min. 0.3 m)
n
Background suppression (max. 10.05 m)
n
Min. signal intensity filter
n
Max. signal intensity filter (min. 10 %)
The minimum distance between the foreground and background suppression is 0.1 mm.
Example: If the foreground suppression is set to 1 m, the background suppression must be
≤ 0.9 m or ≥ 1.1 m.
Minimum and maximum signal intensity filters can be activated individually or together. The
step width is 1 %. The minimum distance between the minimum and maximum signal intensity
filter is 10 %.
Only peaks located within the signal ranges are forwarded for data processing.
Adjust the filter in the
Measurement specific parameters
.
a
The signal limits are displayed in a white area in the Turck Radar Monitor. Peaks without a
blue bar are not forwarded for data processing.
Fig. 31: Example– filtering signals