Setting
Setting and visualization with the Turck Radar Monitor
32
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
9.3
Setting via IO-Link
The device can be parameterized within the technical specifications (see data sheet) via the IO-
Link communication interface – both offline, e.g. with the configuration tool as well as also on-
line via the controller. An overview of the different functions and properties that can be set and
used for IO-Link or SIO mode can be found in the chapter “Setting” and in the IO-Link para-
meter manual of the device. Detailed instructions on the parameterization of devices via the IO-
Link interface are provided in the IO-Link commissioning manual.
All the parameters can be changed in IO-Link mode via the controller during commissioning as
well as during operation. In SIO mode the device operates according to the last setting made in
IO-Link mode.
9.4
Setting and visualization with the Turck Radar Monitor
The device can be parameterized and tested via a Turck IO-Link master (e.g. TBEN-S2-4IOL). The
integrated web server of the IO-Link master offers access to all parameters of the sensor IODD.
For an overview of IO-Link parameters and descriptions see the IO-Link parameter manual. The
Turck Radar Monitor is also available for the visualization of process data.
A Turck IO-Link master is required for accessing the sensor parameters and the Turck Radar
Monitor. The following table shows the firmware version of the IO-Link master, which is re-
quired for using the Turck Radar Monitor:
IO-Link master
Firmware status
FEN20-4IOL
V1.1.0.0
TBEN-L4/5-8IOL
V3.3.0.0
TBEN-LL-8IOL
V1.1.0.0
TBEN-S2-4IOL
V3.4.0.0
Refer to the specific device instructions for use to obtain information on the Turck IO-Link mas-
ters.
Connect the IO-Link master to the power supply.
Connect the IO-Link master to a PC via the Ethernet interface.
Connect the radar sensor to an IO-Link port of the IO-Link master.
9.4.1
IO-Link master – opening the web server
To open the web server of the IO-Link master, enter the IP address in the address bar of a
web browser (default:
A login is required on the IO-Link master in order to edit settings via the web server and to call
up the Turck Radar Sensor.
Enter the password in the Login field on the start page of the web server. The default
password is “password”.
Click
Login
.