INTERFACE MENU
(continued)
MENU ITEM
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
OUTPUT
RANGE
OUTPUT
RANGE
(continued)
The PresSura controller updates the analog output every 0.1
second. This signal outputs a linear 0 to 10 volt direct current
(VDC) or 4 to 20 mA DC analog output which corresponds to
the measured room pressure.
LOW or HIGH
HIGH
OUTPUT
SIGNAL
OUTPUT
SIG
The OUTPUT SIG item selects the type of analog pressure
signal output. The analog output signal can either be 0 to 10
VDC or
4 to 20 mA.
0 to 10 VDC or
4 to 20 mA
0 to 10 VDC
ACCESS
CODE
ACCESS
CODE
The ACCESS CODE item selects whether an access code
(pass code) is required to enter the menu. The ACCESS CODE
item prevents unauthorized access to a menu. If the ACCESS
CODE is ON a code is required before the menu can be
entered. Conversely if the
ACCESS CODE is OFF no code is
required to enter the menu.
ON or OFF
OFF
END OF
MENU
The END OF MENU item informs you that the end of a menu
has been reached. You can either scroll back up the menu to
make changes, or press the
SELECT
or
MENU
key to exit out
of the menu.
24
Pa
rt
Two
Summary of Contents for PRESSURA 8630-PM
Page 2: ......
Page 6: ...iv This page intentionally left blank...
Page 44: ...Specifications 38 This page intentionally left blank...
Page 45: ...Appendix B 39 Appendix B Wiring Diagram Figure 10 Wiring Diagram...
Page 46: ...Wiring Diagram 40 This page intentionally left blank...
Page 48: ...Access Codes 42 This page intentionally left blank...