ALARM MENU
(continued)
MENU ITEM
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
ALARM DELAY ALARM
DELAY
The ALARM DELAY determines the length of time the alarm is
delayed after an alarm condition has been detected. This delay
affects the visual alarm, audible alarm, and relay outputs. An
ALARM DELAY prevents nuisance alarms from staff opening
and closing doors, etc.
20 to 600 SECONDS
20
SECONDS
MUTE
TIMEOUT
MUTE
TIMEOUT
The MUTE TIMEOUT determines the length of time the audible
alarm is silenced after the
MUTE
key is pressed. This delay
temporarily mutes the audible alarm.
5 to 30 MINUTES
5 MINUTES
NOTE
: If the PresSura controller is in alarm when MUTE
TIMEOUT expires, the audible alarm turns on. When
the PresSura controller returns to the safe range, the
MUTE TIMEOUT is canceled. If the room goes back
into an alarm condition, the
MUTE
key must be
pressed again to mute the audible alarm.
ACCESS
CODE
ACCESS
CODE
The ACCESS CODE item selects whether an access code
(pass code) is required to enter the menu. The ACCESS CODE
item prevents unauthorized access to a menu. If the ACCESS
CODE is ON a code is required before the menu can be
entered. Conversely if the
ACCESS CODE is OFF no code is
required to enter the menu.
ON or OFF
OFF
END OF
MENU
The END OF MENU item informs you that the end of a menu
has been reached. You can either scroll back up the menu to
make changes, or press the
SELECT
or
MENU
key to exit out
of the menu.
ALARM CONSTRAINTS
There are a number of constraints built into the software that prevent users from programming conflicting alarm information. These are as
follows:
1.
Room mode. The positive pressure alarms are only active when positive pressure is enabled. Negative pressure alarms
are only active when negative pressure is enabled. In no isolation mode all alarms are turned off.
2.
The PresSura controller
is programmed not to allow the pressure alarms to be programmed within 40 ft/min (±0.00028 “
H
2
O at 0.001 “H
2
O) of each other.
Tech
ni
cal
Sectio
n
17
Summary of Contents for PRESSURA 8630-PM
Page 2: ......
Page 6: ...iv This page intentionally left blank...
Page 44: ...Specifications 38 This page intentionally left blank...
Page 45: ...Appendix B 39 Appendix B Wiring Diagram Figure 10 Wiring Diagram...
Page 46: ...Wiring Diagram 40 This page intentionally left blank...
Page 48: ...Access Codes 42 This page intentionally left blank...