Technical Section
53
High Flow Calibration
1. Enter
CALIBRATION FLOW
menu and raise the sash height to approximately 18 inches
(sash stop).
2. Select
FLO STA HI CAL
to enter a submenu with the following items:
FLO STA LO SETPT
Damper position for low flow calibration
PRESS ZERO VOLTAGE
Voltage from pressure transducer during Flow Station
Pressure Transducer Zero
PRESSURE VOLTAGE
Current voltage from pressure transducer
MEASURED FLOW
Current flow rate
ENTER ACTUAL FLOW
Input actual flow as measured with reference instrument
here
3. With the
FLO STA HI SETPT
at 100% (default), observe the
PRESSURE VOLTAGE
displayed on the screen, or use a voltmeter to read the voltage at the pressure signal
transducer input terminals 7-8 on the back of the controller.
4. Slowly
decrease
the
FLO STA HI SETPT
percentage value to adjust the damper position
until the
PRESSURE VOLTAGE
(pressure transducer output) shows the first noticeable
decrease
in voltage from the 100% position. A general rule of thumb is that the voltage
change should occur with the damper between approximately 70 to 90% open.
NOTE:
Adjusting the
FLO STA HI SETPT
with the quick keys allows the
PRESSURE VOLTAGE
to be displayed in real time.
5. For reference only, the
MEASURED FLOW
item will display the default measured flow
based on the current settings of the flow station (duct area, etc.).
6. Determine the actual flow with a duct traverse.
7. Enter the actual flow measurement under the
ENTER ACTUAL FLOW
menu item
8. Press the
ENTER
(
)
soft key to save the flow data.
9. The high flow calibration is complete. Exit the menu with the
ESC
key.
NOTE
: Use
BALANCE MODE
to verify flow station calibration.
Linear Flow Station Calibration
NOTE:
Flow stations are optional and may not be installed in your system.
1. Enter
CALIBRATE FLOW
item.
2. Set
FLO STA AREA
to the duct area at the linear flow station location.
3. Set
FLO STA TOP VEL
to match the range of the linear flow station used.
4. Set
FLO STA FS V
to match the voltage output (0 to 10V or 0 to 5V) of the linear flow
station used.
5. Linear flow station calibration should be complete. Exit the menu.
NOTE
: Use
BALANCE MODE
to verify flow station calibration.
Summary of Contents for FHC50
Page 2: ......
Page 4: ......
Page 10: ...2 This page intentionally left blank ...
Page 16: ...Part One 8 This page intentionally left blank ...
Page 56: ...48 Part Two This page intentionally left blank ...
Page 96: ...Appendix B 88 This page intentionally left blank ...
Page 98: ...Appendix C 90 Figure 7 Wiring Diagram Model FHC50 01 Controller ...
Page 99: ...Wiring Information 91 Figure 8 Wiring Diagram Model FHC50 02 Controller ...
Page 100: ...Appendix C 92 Figure 9 Wiring Diagram Model FHC50 03 Controller ...
Page 101: ...Wiring Information 93 Figure 10 Wiring Diagram Model FHC50 04 Controller ...
Page 102: ...Appendix C 94 Figure 11 Model FHM10 01 Monitor Wiring ...
Page 103: ...Wiring Information 95 Figure 12 Model FHM10 02 Monitor Wiring ...
Page 104: ...Appendix C 96 This page intentionally left blank ...
Page 106: ...Appendix C 98 This page intentionally left blank ...