Tech
ni
cal
Sectio
n
41
CALIBRATE FLOW SUBMENU
6PT VENTURI VALVE ONLY
MENU ITEM
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
FLOW DEVICE
SELECTED
FHC50 Only
FLOW DEVCE =
This item displays the
FLOW DEVICE
that was previously
selected through the
CONFIG WIZARD
item.
Lin Flo Sta
Press Flo Sta
LOM Venturi
6pt Venturi
Calculated
6Pt Venturi
(Read-only
value)
RESET FLOW
CALIBRATION
FHC50 Only
FLOW RESET
CAL
The
RESET CAL
menu item zeroes out the flow calibration
adjustments. When this menu item is entered, the controller
will prompt the user to verify that they want to do this by
displaying the message “
Are You Sure
.” Entering
YES
resets the flow calibration factors for this flow device to
defaults and shows the message “
Changes Saved
.”
Entering
NO
will cancel the reset and show the message
“
Changes Not Saved
.”
WARNING:
Controller alarm functions will not be
maintained after resetting flow calibration.
Immediately recalibrate controller after
resetting flow calibration.
NONE
VENTURI VALVE
POSITION 1 FLOW
FHC50 Only
VENTURI PT1
The
VENTURI PT1
item is used to calibrate a venturi valve
without feedback. When this item is entered, the display will
indicate a volumetric flow rate. Adjust the displayed value to
match the flow through the venturi valve when the venturi
valve is at the
0% OPEN
position.
NOTE:
The flow information can be obtained through a
direct flow measurement (i.e. duct traverse) after
using the
CONTROL OUT
item to set the damper
to 0% Open or from the label on the TSI Venturi
Valve.
The
VENTURI PT1
menu item must be completed before
moving on to the
VENTURI PT2
menu item.
0 to 10000 cfm
0 cfm
Summary of Contents for FHC50
Page 2: ......
Page 4: ......
Page 10: ...2 This page intentionally left blank ...
Page 16: ...Part One 8 This page intentionally left blank ...
Page 56: ...48 Part Two This page intentionally left blank ...
Page 96: ...Appendix B 88 This page intentionally left blank ...
Page 98: ...Appendix C 90 Figure 7 Wiring Diagram Model FHC50 01 Controller ...
Page 99: ...Wiring Information 91 Figure 8 Wiring Diagram Model FHC50 02 Controller ...
Page 100: ...Appendix C 92 Figure 9 Wiring Diagram Model FHC50 03 Controller ...
Page 101: ...Wiring Information 93 Figure 10 Wiring Diagram Model FHC50 04 Controller ...
Page 102: ...Appendix C 94 Figure 11 Model FHM10 01 Monitor Wiring ...
Page 103: ...Wiring Information 95 Figure 12 Model FHM10 02 Monitor Wiring ...
Page 104: ...Appendix C 96 This page intentionally left blank ...
Page 106: ...Appendix C 98 This page intentionally left blank ...