CONFIGURE MENU
MENU ITEM
Monitor/
Controller
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
DISPLAY
MEASUREMENT
FHM10 and FHC50
DISPLAY
MEAS
The
DISPLAY MEAS
item selects which measurements will be
presented on the display during normal operating mode. Use the
DISPLAY UNITS
item to choose the units of measure:
Vel
Displays only the current face velocity.
Vel, Flow
Displays both the current face velocity and the
current flow.
Flow
Displays only the current flow.
None
Does not display face velocity or flow during normal
operating mode.
Vel
Vel, Flow
Flow
None
Vel
DISPLAY
AVERAGE
FHM10 and FHC50
DISPLAY
AVG
The
DISPLAY AVG
item selects the
display’s running average
period. The display-averaging period is the length of time the
face velocity has been averaged before being displayed. The
DISPLAY AVG
item value may be set between 0.5 and 40
seconds. The higher the averaging value, the more stable the
display.
0.5, 1, 2, 3, 5, 10, 20,
or 40 seconds
5 seconds
DISPLAY UNITS
FHM10 and FHC50
DISPLAY
UNITS
The
DISPLAY UNITS
item selects the unit of measure that the
controller displays all velocity and flow related menu items: set
points, alarms, calibration, etc.
ft/min, cfm
m/s, m
3
/h
m/s, l/s
ft/min, cfm
ALARM RESET
FHM10 and FHC50
ALARM
RESET
The
ALARM RESET
item selects how the alarms terminate
after the unit returns to control set point.
UNLATCHED
(alarm
follow) automatically resets the alarm when the face velocity is
20 ft/min (50 cfm for flow alarms) greater than the low alarm set
point, or 20 ft/min (50 cfm for flow alarms) below the high alarm
set point.
LATCHED
requires the staff to press the
RESET
key
to clear alarms. The
ALARM RESET
affects the audible alarm,
visual alarm, and relay output, which means all are latched or
unlatched.
LATCHED
or
UNLATCHED
UNLATCHED
Summary of Contents for FHC50
Page 2: ......
Page 4: ......
Page 10: ...2 This page intentionally left blank ...
Page 16: ...Part One 8 This page intentionally left blank ...
Page 56: ...48 Part Two This page intentionally left blank ...
Page 96: ...Appendix B 88 This page intentionally left blank ...
Page 98: ...Appendix C 90 Figure 7 Wiring Diagram Model FHC50 01 Controller ...
Page 99: ...Wiring Information 91 Figure 8 Wiring Diagram Model FHC50 02 Controller ...
Page 100: ...Appendix C 92 Figure 9 Wiring Diagram Model FHC50 03 Controller ...
Page 101: ...Wiring Information 93 Figure 10 Wiring Diagram Model FHC50 04 Controller ...
Page 102: ...Appendix C 94 Figure 11 Model FHM10 01 Monitor Wiring ...
Page 103: ...Wiring Information 95 Figure 12 Model FHM10 02 Monitor Wiring ...
Page 104: ...Appendix C 96 This page intentionally left blank ...
Page 106: ...Appendix C 98 This page intentionally left blank ...