Tech
ni
cal
Sectio
n
45
CALIBRATE FLOW SUBMENU
CALCULATED FLOW ONLY
MENU ITEM
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
RESET FLOW
CALIBRATION
FHC50 Only
FLOW RESET
CAL
The
RESET CAL
menu item zeroes out the flow calibration
adjustments. When this menu item is entered, the controller
will prompt the user to verify that they want to do this by
displaying the message “
Are You Sure
.” Entering
YES
resets the flow calibration factors for this flow device to
defaults and shows the message “
Changes Saved
.”
Entering
NO
will cancel the reset and show the message
“
Changes Not Saved
.”
NONE
WARNING:
Controller alarm functions will not be
maintained after resetting flow calibration.
Immediately recalibrate controller after
resetting flow calibration.
FLOW K FACTOR
FHC50 Only
FLOW
KFACTOR
The
K FACTOR
menu item sets the “K” factor for the flow
signal. The flow signal is multiplied by the
K FACTOR
so
that the flow measurement matches the actual flow,
determined with a pitot tube traverse.
NOTE
:
FLOW K FACTOR
modifies the entire range of
the calibrated flow, not just a single point.
0.01 to 10.00
1.00
BALANCE MODE SUBMENU
MENU ITEM
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
DESIRED FLOW
FHC50 Only
DESIRED FLOW
The
DESIRED FLOW
item is used to set and hold the
controller at a desired flow to enable a balancing technician
to verify flow through the fume hood.
0 to 10000 cfm
0
BALANCE MODE
K FACTOR
FHC50 Only
FLOW
KFACTOR
The
FLOW KFACTOR
item is used to adjust the measured
flow to match the actual flow measured by the balancing
technician.
0.01 to 10.00
1.00
NOTE
: Changing the
FLOW KFACTOR
item also adjusts
the
FLOW KFACTOR
item stored under the
CALIBRATE FLOW
submenu.
Summary of Contents for FHC50
Page 2: ......
Page 4: ......
Page 10: ...2 This page intentionally left blank ...
Page 16: ...Part One 8 This page intentionally left blank ...
Page 56: ...48 Part Two This page intentionally left blank ...
Page 96: ...Appendix B 88 This page intentionally left blank ...
Page 98: ...Appendix C 90 Figure 7 Wiring Diagram Model FHC50 01 Controller ...
Page 99: ...Wiring Information 91 Figure 8 Wiring Diagram Model FHC50 02 Controller ...
Page 100: ...Appendix C 92 Figure 9 Wiring Diagram Model FHC50 03 Controller ...
Page 101: ...Wiring Information 93 Figure 10 Wiring Diagram Model FHC50 04 Controller ...
Page 102: ...Appendix C 94 Figure 11 Model FHM10 01 Monitor Wiring ...
Page 103: ...Wiring Information 95 Figure 12 Model FHM10 02 Monitor Wiring ...
Page 104: ...Appendix C 96 This page intentionally left blank ...
Page 106: ...Appendix C 98 This page intentionally left blank ...