CAPACITIVE TOUCH SERIES

12

13

SENSOR SELECTION 

IN : INTERNAL SENSOR, OU: EXTERNAL SENSOR, IF 

CHOOSING EXTERNAL SENSOR, THE ROOM CARD 

FUNCTION WILL NOT BE AVAILABLE, DEFAULT IS IN

14 

BEE SOUND SETTING 

ON: ON, OF: OFF, DEFAULT IS OF

15 

PROGRAM SETTING

0: 5 WORKING DAYS AND 2 DAYS HOLIDAY A WEEK, 1: 6 

WORKING DAYS AND 1 DAY HOLIDAY A WEEK, 2: 7 WORKING 

DAYS A WEEK, 3: CLOSE PROGRAM SCHEDULE ,DEFAULT IS 0

17

FAN STOP/RUN SETTINGS 

16 

LO: FAN WILL BE SWITCHED TO LOW SPEED WHEN ROOM 

TEMP. REACHES TO SET-POINT&VALVE TURNS OFF 

OF: FAN WILL BE SWITCHED OFF WHEN ROOM TEMP. 

REACHES TO SET-POINT& VALVE TURNS OFF, DEFAULT IS 

OF

18

ON / OFF BACK-LIGHT SETTING

OF: OFF, THE BACK-LIGHT WILL BE OFF AFTER 30 

SECONDS IF NONE KEY PRESS 

ON: ON, THE BACK-LIGHT WILL BE ON ALWAYS EVEN 

NONE KEY PRESS, DEFAULT IS OF

19

ON / OFF MEMORY SETTING 

OF: OFF USER SETTING WILL NOT BE KEPT WHEN POWER 

OFF (WHILE ELECTRIFIED, THE THERMOSTAT WILL BE OFF) 

SU: ON, USER SETTING WILL BE KEPT WHEN POWER OFF 

(WHILE ELECTRIFIED, THE THERMOSTAT WILL BE ON), 

DEFAULT IS OF

21

22

23

24

25

26

20

BACK-LIGHT SETTINGS 

10-60 SECONDS(DEFAULT 30 SEC.,USER CAN

ADJUST BACK-LIGHT TIME ACCORDING TO ACTUAL

DEMANDS)

RESERVED FOR ADDITIONAL ISU SETTINGS

RESERVED FOR ADDITIONAL ISU SETTINGS

RESERVED FOR ADDITIONAL ISU SETTINGS

RESERVED FOR ADDITIONAL ISU SETTINGS

RESET TO DEFAULTS 

10

11

THIS FUNCTION IS RESETTING ALL ISU SETTINGS TO FACTORY 

DEFAULTS, OPERATION: PRESS “      ” 0>1>2>3>4, THEN PRESS

“      ” 4>3>2 AND PRESS “      ” TO CONFIRM DEFAULT: 0   

5

RESERVED FOR ADDITIONAL ISU SETTINGS

RESERVED FOR ADDITIONAL ISU SETTINGS

RESERVED FOR ADDITIONAL ISU SETTINGS

COMPRESSOR OFF TIME DELAY SETTING

RANGE 0-4 MINUTES, IF SETTING VALUE IS 0, WITHOUT 
DELAY,THIS IS FOR SIMPLE ON-OFF VALVE CONTROL, COM-
PRESSOR FUNCTION IS NOT AVAILABLE IF SETTING VALUE IS 
1-4,THIS IS FOR COMPRESSOR FUNCTION, WHEN SETTING IS 1, 
WITH 1 MINUTE OFF DELAY FOR COMPRESSOR CONTROL

RESERVED FOR ADDITIONAL ISU SETTINGS

Summary of Contents for TX1000 Series

Page 1: ...e sensor key card can be chosen as per site requirements FEATURES Modern touch pad design residential buildings Applicable for 2 pipe FCU cooling heating Simple on off valve or compressor Black LCD an...

Page 2: ...f valve or compressor Suitable Valve 2 line 3 line valve Relative Humidity 10 90 Installed on 75mm x 75mm box ORDERING PART NUMBERS TX1000 OF220 V21CE 85 240VAC 2 PIPE SINGLE STAGE 2 PIPE SINGLE STAGE...

Page 3: ...ault value is 18 C The value can be changed in ISU mode with step of 1 C For cooling mode if energy saving function is enabled the set point will be changed to remote setback cooling set point The ran...

Page 4: ...ILABLE DEFAULT 1 MODE BUTTON IS LOCKED OUT 2 FAN AND MODE BUTTON ARE LOCKED OUT 3 ALL BUTTONS ARE LOCKED 5 REMOTE SETBACK ENABLE METHOD NO HOTEL CARD NO NC HOTEL CARD NC BU BUTTON DEFAULT 6 FREEZE PRO...

Page 5: ...OWER OFF WHILE ELECTRIFIED THE THERMOSTAT WILL BE OFF SU ON USER SETTING WILL BE KEPT WHEN POWER OFF WHILE ELECTRIFIED THE THERMOSTAT WILL BE ON DEFAULT IS OF 21 22 23 24 25 26 20 BACK LIGHT SETTINGS...

Page 6: ...PRESSOR OPEN 6 VALVE COMPRESSOR CLOSE 7 COM FOR EXTERNAL SENSOR 8 NEUTRAL IN 9 L FM FH FL NO NC COM N AI EXTERNAL SENSOR TERMINALS NO 1 LIVE IN 3 MEDIUM SPEED FAN HIGH SPEED FAN 4 LOW SPEED FAN 2 DESC...

Page 7: ...n Wait five minutes for the cooling system to respond The Mode button does not work Check whether the Fan mode is set to Auto Check whether the heating or cooling system works well Check whether the k...