CAPACITIVE TOUCH SERIES
12
13
SENSOR SELECTION
IN : INTERNAL SENSOR, OU: EXTERNAL SENSOR, IF
CHOOSING EXTERNAL SENSOR, THE ROOM CARD
FUNCTION WILL NOT BE AVAILABLE, DEFAULT IS IN
14
BEE SOUND SETTING
ON: ON, OF: OFF, DEFAULT IS OF
15
PROGRAM SETTING
0: 5 WORKING DAYS AND 2 DAYS HOLIDAY A WEEK, 1: 6
WORKING DAYS AND 1 DAY HOLIDAY A WEEK, 2: 7 WORKING
DAYS A WEEK, 3: CLOSE PROGRAM SCHEDULE ,DEFAULT IS 0
17
FAN STOP/RUN SETTINGS
16
LO: FAN WILL BE SWITCHED TO LOW SPEED WHEN ROOM
TEMP. REACHES TO SET-POINT&VALVE TURNS OFF
OF: FAN WILL BE SWITCHED OFF WHEN ROOM TEMP.
REACHES TO SET-POINT& VALVE TURNS OFF, DEFAULT IS
OF
18
ON / OFF BACK-LIGHT SETTING
OF: OFF, THE BACK-LIGHT WILL BE OFF AFTER 30
SECONDS IF NONE KEY PRESS
ON: ON, THE BACK-LIGHT WILL BE ON ALWAYS EVEN
NONE KEY PRESS, DEFAULT IS OF
19
ON / OFF MEMORY SETTING
OF: OFF USER SETTING WILL NOT BE KEPT WHEN POWER
OFF (WHILE ELECTRIFIED, THE THERMOSTAT WILL BE OFF)
SU: ON, USER SETTING WILL BE KEPT WHEN POWER OFF
(WHILE ELECTRIFIED, THE THERMOSTAT WILL BE ON),
DEFAULT IS OF
21
22
23
24
25
26
20
BACK-LIGHT SETTINGS
10-60 SECONDS(DEFAULT 30 SEC.,USER CAN
ADJUST BACK-LIGHT TIME ACCORDING TO ACTUAL
DEMANDS)
RESERVED FOR ADDITIONAL ISU SETTINGS
RESERVED FOR ADDITIONAL ISU SETTINGS
RESERVED FOR ADDITIONAL ISU SETTINGS
RESERVED FOR ADDITIONAL ISU SETTINGS
RESET TO DEFAULTS
10
11
THIS FUNCTION IS RESETTING ALL ISU SETTINGS TO FACTORY
DEFAULTS, OPERATION: PRESS “ ” 0>1>2>3>4, THEN PRESS
“ ” 4>3>2 AND PRESS “ ” TO CONFIRM DEFAULT: 0
5
RESERVED FOR ADDITIONAL ISU SETTINGS
RESERVED FOR ADDITIONAL ISU SETTINGS
RESERVED FOR ADDITIONAL ISU SETTINGS
COMPRESSOR OFF TIME DELAY SETTING
RANGE 0-4 MINUTES, IF SETTING VALUE IS 0, WITHOUT
DELAY,THIS IS FOR SIMPLE ON-OFF VALVE CONTROL, COM-
PRESSOR FUNCTION IS NOT AVAILABLE IF SETTING VALUE IS
1-4,THIS IS FOR COMPRESSOR FUNCTION, WHEN SETTING IS 1,
WITH 1 MINUTE OFF DELAY FOR COMPRESSOR CONTROL
RESERVED FOR ADDITIONAL ISU SETTINGS