Mini Smoke Detector (Mini-SD-ZBS)  

 

  Every time the battery is removed and reinserted, the Mini Smoke Detector will also take the new threshold value following the 

warming and calibration process. 
 

 

ZigBee Network Setup 

 

ZigBee Device Guideline 

ZigBee is a wireless communication protocol that is reliable and has low power consumption and high transmission efficiency. Based on the 
IEEE802.15.4 standard, ZigBee allows a large amount of devices to be included in a network and coordinated for data exchange and signal 
transmission. 
Due to the fundamental structure of ZigBee network, ZigBee device will actively seek and join network after powering on. Since performing 
a task in connecting network may consume some power, it is required to follow the instructions to avoid draining battery of a ZigBee device 
- Ensure your ZigBee network router or coordinator is powered on before inserting battery into the ZigBee device. 
- Ensure the ZigBee network router or coordinator is powered on and within range while a ZigBee device is in use. 
- Do not remove a ZigBee device from the ZigBee network router or coordinator without removing the battery from a ZigBee device. 

 

Joining the ZigBee Network 

As a ZigBee device, the Mini Smoke Detector needs to join a ZigBee network to transmit signal when smoke concentration or temperature 
is detected. Please follow the steps bellow to join the Mini Smoke Detector into ZigBee network. 
The Mini Smoke Detector has 3 ZigBee Endpoints for PIR, Smoke Detector and Temperature Sensor function. When joining ZigBee network, 
it will be recognized as

 3 separate ZigBee devices 

and will occupy 

3 zones

 in your ZigBee network coordinator. 

1.  Insert the battery into the battery compartment to power on the Mini Smoke Detector. 
2.  The Mini Smoke Detector will emit 2 short beeps, and begin warm up for 

1

 minute, LED flashes every 2 seconds. 

3.  After 1-minute warm  up period expires, the Mini Smoke Detector will emit a beep to indicate it now enters calibration process.  The 

calibration process takes 1~7  minutes; the LED will continue to flash during calibration. Joining ZigBee network is 

prohibited

  during 

warm up calibration process. After calibration process the Mini Smoke Detector will emit a 2-tone beep, LED will turn off. 

4. 

The Mini Smoke Detector is only available for joining the ZigBee network 3 minutes after completing calibration

  

Press and hold the Test Button for 10 seconds and release to search for existing ZigBee network. Please make sure the permit-to-join 
feature on the router or coordinator of your ZigBee network is enabled. 

5.  After joining the ZigBee network, the Mini Smoke Detector will be registered in the network automatically. Please check the ZigBee 

coordinator, security system control panel or CIE (Control and Indicating Equipment) to confirm if joining and registration is successful. 

6.  When calibration is complete, the Mini Smoke Detector will emit 2 beeps and LED will stop flashing to indicate it is now under normal 

operation. If calibration fails, the Mini Smoke Detector will sound continuous beep. 

7.  Under normal operation, if the Mini Smoke Detector loses connection to its current ZigBee network, the LED indicator will flash every 20 

minutes to indicate the situation. Please check your ZigBee network condition and Mini Smoke Detector signal range to correct  the 
situation. 

 

Removing Device from ZigBee Network (Factory Reset) 

To remove the Mini Smoke Detector  from current ZigBee network, the device  must be put to Factory Reset to complete 
device removal. Factory Reset function will clear the Mini Smoke Detector of its stored setting information and prompt the 
device to search for new ZigBee network.  

Before removing device, make sure the Mini Smoke Detector is within current ZigBee network signal range 

1.  Delete the Smoke Detector from current control panel / CIE. 
2.  The Mini Smoke Detector can only be reset 

within 3 minutes

 after power up. If it has been powered up for more than 3 

minutes, remove and reinsert the batteries. 

3.  Press and hold the function button for 10 seconds, then release the button to reset Smoke Detector. 
4.  Upon reset, the Smoke Detector will clear current ZigBee network setting and transmit signal to ZigBee coordinator to 

remove itself from current ZigBee network. It will then actively search for available ZigBee network again and join the 
network automatically.  

 

 

Installation 

 

Installation Guideline 

  It is recommended that the installation site be in the center area of the ceiling. 

  Do not locate the detector in the following locations: 

 

The Kitchen – Smoke from cooking might cause an unwanted alarm. 

 

Near a ventilating fan, florescent lamp or air-conditioning equipment – air drafts from them 

may affect the sensitivity of the detector. 

 

Near ceiling beams or over a cabinet – stagnant air in these areas may affect the sensitivity 

of the detector. 

 

In the peak of an “

A

” frame type of ceiling.

 

 

 

Installation Recommendation 

 

It is recommended to install the Mini Smoke Detector in the following locations. 

  In a ceiling area with full view of its detection coverage unobstructed by appliances and furniture. 

  Near the entrance of a room or house to monitor entry activity. 

 

Summary of Contents for Mini-SD-ZBS

Page 1: ...tor has lost connection to its current ZigBee network Orange LED Flash every second Device power on Calibration failed Flashes every 5 seconds Detecting smoke failed or device malfunctioning Flashes every 4 seconds battery exhausted Flashes every 45 seconds Low battery condition Test Button Press and hold the button for 10 seconds then release to reset the Mini Smoke Detector Press and hold the bu...

Page 2: ...rueGuard Control Panel Only The Smoke and Heat Detection function of the Mini Smoke Detector can be disabled by sending ZigBee command from the Control Panel if needed to accommodate different installation environment To disable the Smoke or Heat detection function 1 Go to the Device List in the Control Panel setting select Edit Device and find the Bypass option 2 Before sending command from the C...

Page 3: ... the permit to join feature on the router or coordinator of your ZigBee network is enabled 5 After joining the ZigBee network the Mini Smoke Detector will be registered in the network automatically Please check the ZigBee coordinator security system control panel or CIE Control and Indicating Equipment to confirm if joining and registration is successful 6 When calibration is complete the Mini Smo...

Page 4: ...tector with the hooks on the mounting bracket Fit the Mini Smoke Detector onto bracket and rotate clockwise to lock the hook Installation is now complete The Mini Smoke Detector is designed to be mounted on the ceiling The ideal mounting height for the Mini Smoke Detector is 2 4 meters to 3 meters Mounting above 3 meters can affect detection performace One side of the Mini Smoke Detector has less ...

Page 5: ...nsertion latches to stabilize Each latch correspond to the insertion holes on the Mini Smoke Detector Match the numbers as below picture shown to place the top cover back to the Mini Smoke Detector Latch 1 is located next to a small dot Få meget mere ud af din TrueGuard alarm FACEBOOK Her kan du følge os og få løbende tips og tricks på facebook https www facebook com TrueGuardAlarm YOUTUBE Se også...

Reviews: