Description

Smoke detector (smoke detection using optical light scattering
principle) with general building supervision approval from the
Institut für Bautechnik Berlin, for fire dampers with electric 
or electric/ pneumatic control device (voltage off to operate),
suitable for protection against smoke transmission in air
conditioning systems, even with cold smoke t 

 

72 °C;

suitable for air velocities of 1 m/s to 20 m/s.
With additional functions for monitoring the air flow in the
measurement area of the smoke alarm, the pollution level 
on the smoke alarm sampling chamber and the system
electronics (maintenance once/year).

Scope of supply: see page 2.

Order Example

Make:

TROX                      

Type:

RM-O-VS       

Quantity: 5                      

RM-O-VS

Order Code

Description:

Diagnostic instrument for smoke detector RM-O-VS to scan
pollution level. 
Measurement range 0 – 100 units; hand unit with 1m long
connection lead and plug; battery supply 9 V.

Order example

Make:

TROX                      

Type:

D-RM-O-VS 

Quantity: 1                      

D-RM-O-VS

Order Code

Description:

Remote control terminal for smoke detector RM-O-VS for
surface mounting or panel mounting (size 48 x 96 x 63) with
signal LEDs for alarm, air flow, pollution and system
monitoring; socket connection for diagnostic instrument 
D-RM-O-VS and pushbutton for test/reset function.

Order Example

Make:

TROX                              

Type:

T-RM-O-VS or T-RM-O-VS/1

Quantity: 5                     

T-RM-O-VS

or

T-RM-O-VS/1

Summary of Contents for RM-O-VS

Page 1: ...Smoke Detector Type RM O VS Approved by the German Institut f r Bautechnik 4 6 1 EN 3...

Page 2: ...y condensation and water vapour can cause false alarms Warning limit for air flow 2 m s Warning limit for high pollution 70 10 units System monitoring electric fault EMC interference suppression to EN...

Page 3: ...by an LED and closing relay contact The actual pollution value can be scanned directly at the smoke detector or on the remote control terminal using the diagnostic instrument Installation of a remote...

Page 4: ...r to replace the smoke alarm an inspection opening should be provided on the upper or lower side of the air duct Optional electrical connections mains connection and connection to control device of fi...

Page 5: ...trol device A on the fire damper to be controlled maximum switched power 250 V 10 A L1 Mains connection 230V 50 60 Hz L3 Control device connection volt free Switched power 250 V 10 A or 24 V 200 W L4...

Page 6: ...Velocity Monitoring Green LED System Monitoring Terminal Strip L9 6 5 Terminal Strip L9 4 3 Terminal Strip L9 2 1 Terminal Strip L3 2 3 1 Yellow LED Pollution Monitoring With air flow LED on Without a...

Page 7: ...rol devices on fire damper Response of smoke alarm to smoke aerosol e g cigarette smoke or smoke from smoke cartridge When the permitted concentration limit is exceeded the smoke alarm interrupts the...

Page 8: ...ution level on the smoke alarm sampling chamber and the system electronics maintenance once year Scope of supply see page 2 Order Example Make TROX Type RM O VS Quantity 5 RM O VS Order Code Descripti...